| 2007-02-08 15:28:56 | *****DENIED***** |
| | |
| | |
| | 01.THE ADDRESS OF WHERE THE SCOPE OF WORK WILL BE |
| | CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED |
| | PLAN SHEET. |
| | 02.NFPA 101- 2003 EDITION AND THE FLORIDA FIRE |
| | PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED. 03. |
| | STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. 04. |
| | CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT |
| | HINDER OR INTERFERE WITH EMERGENCY RESPONSE ACCESS TO |
| | THE SAID PROPERTY OR THE VICINITY THEREOF (INCLUDING |
| | FIRE LANES). |
| | 05.FIRE DEPARTMENT CONNECTIONS (FDC) SHALLBE |
| | POSITIONED AS TO NOT BEING BLOCKED BY LANDSCAPING, |
| | STORAGE, VESSELS, AND SUPPLIES.PROPER CLEARANCES ARE |
| | TO BE MAINTAINED AT ALL TIMES. |
| | 06.KNOXLOCKING CAPS ARE REQUIRED FOR NEW FIRE |
| | DEPARTMENT CONNECTIONS. |
| | 07. KNOX BOX FOR THE BUILDING WILL BE REQUIRED. CONTACT |
| | THE FIRE PREVENTION BUREAU AT (561) 804-4724 FOR |
| | APPLICATIONS. |
| | 08.THE FIRE SPRINKLER SYSTEM IN CONJUNCTION WITH THE |
| | FIRE ALARM SYSTEM SHALL BE MONITORED BY A LICENSED UL |
| | LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION |
| | SERVICE. |
| | 09. ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA |
| | 80.PANIC HARDWARE OR FIRE EXIT PANIC HARDWARE SHALL |
| | REQUIRED ON ALL EXIT DOORS THAT SERVE AND OCCUPANT LOAD |
| | OF 100 OR MORE PERSONS. |
| | 10. DELAYED-EGRESS LOCKS OR ACCESS-CONTROLLED EGRESS |
| | DOORS SHALL COMPLY NFPA 101, CH. 7.2.1.6 |
| | 11.EXIT/EGRESS FROM THE BUILDING AND/OR FLOOR SHALL |
| | COMPLY WITH APPLICABLE FIRE AND BUILDING CODES (SEE |
| | BUILDING PLAN REVIEW COMMENTS). |
| | 12.NO EQUIPMENT SHALL BE ALLOWED INSIDE OR PENETRATE |
| | EXIT ENCLOSURES UNLESS THE EXCEPTIONS OF NFPA 101, |
| | 7.1.3.2.1. (6) ARE MET. |
| | 13. PLEASE PROVIDE PRESCRIPTIVE STRENGHT REQUIREMENTS |
| | FOR ALL NEW HANDRAILS AND GUARDRAILS (INCLUDING |
| | EMERGENCY OVERFLOW AREA). |
| | 14.INTERIOR WALL AND CEILING FINISH CLASSIFICATION |
| | SHALL BE CLASS A OR CLASS B IN GENERAL ASSEMBLY AREAS |
| | HAVING AN OCCUPANT LOAD OF MORE THAN 300 AND SHALL BE |
| | CLASS A, CLASS B, OR CLASS C IN ASSEMBLY AREAS HAVING |
| | OCCUPANTS OF 300 OR FEWER. |
| | 15.ELEVATORS TO COMPLY WITH ASME A17.1; WARNING SIGNS |
| | WILL BE REQUIRED IN ELEVATOR LOBBY.THE ELEVATORS (OR |
| | AT LEAST ONE ELEVATOR) SHOULD BE ACCESSIBLE FOR AN |
| | EMERGENCY MEDICAL STRETCHER OR GOURNEY. |
| | 16.DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE |
| | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.AMEND |
| | SHEET FA0.1, FIRE ALARM NOTE #17. |
| | 17.IF SO EQUIPPED WITH A COOKING HOOD, SEPARATE PLANS |
| | AND PERMIT WILL BE REQUIRED. |
| | 18.HOW WILL EMISSIONS FROM VEHICLES IN THE PARKING |
| | GARAGE BE CONTROLLED OR MANAGED AS TO NOT COMMUNICATE |
| | TO OTHER AREAS OF THE STRUCTURE? |
| | |
| | |
| | TO EXPEIDITE THE PLAN REVIEW PROCESS, INCLUDE A |
| | RESPONSE LETTER INDICATING HOW/WHERE EACH ITEM WAS |
| | ADDRESSED. |
| | |
| | |