| 2006-11-28 07:52:39 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE BE PLANS REFLECT THE FOLLOWING CODES AT |
| | A MINIMUM. |
| | 2002 NFPA-70, 2003 NFPA-101, 2002 NFPA-72 AND THE |
| | ELECTRICAL PLANS SHOULD ALSO STATE THE 2004 FBC. |
| | |
| | 2) NOTE: PLEASE SEE FBC CHAPTER 13. PLEASE SEE |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE THERE ARE MANY AREAS WHICH INDICATE SOME |
| | SORT OF SYMBOL NEXT TO SWITCH, HOWEVER AS THIS SYMBOL |
| | IS NOT LOCATED ON THE SYMBOL SCHEDULE IT IS UNCLEAR |
| | WHAT THIS IS FOR REVIEW OF COMPLIANCE WITH ANY LIGHTING |
| | CONTROL REQUIREMENTS. |
| | PLEASE SEE MANY OTHER AREAS WHICH A SWITCH IS BEING |
| | SHOWN AND THE CIRCUIT IS NOT LABELED GOING THROUGH THE |
| | LIGHTING CONTROL PANEL. |
| | ** PLEASE KNOW THE LIGHTING CONTROL PANEL WILL BE NOTED |
| | AS "LCP" IN THE NOTES FORM HERE OUT. |
| | PLEASE SPECIFY THE SYSTEM WHICH IS BEING INSTALLED OR |
| | SPECIFIED FOR THE SCOPE OF WORK AND INTENDED |
| | CONTROL.110.3, 90.7 |
| | PLEASE SEE EACH SPACE SHALL CONTAIN A DEVICE WHICH OVER |
| | -RIDES A SYSTEM, OR PROVIDES CONTROLS MEANS AS OTHER |
| | METHODS LISTED IN 13-415.1.ABC.1.1, .1.2. |
| | PLEASE SEE THERE ARE SEVERAL ROOMS WHICH DO NOT |
| | INDICATE ANY KIND OF OVER RIDE DEVICE, OCCUPANT SENSOR |
| | ETC. |
| | PLEASE SEE THE OVER RIDE TYPE DEVICE IS ALSO REQUIRED |
| | TO BE LOCATED IN THE AREAS IN WHICH THE OCCUPANT CAN |
| | SEE THE LIGHTING BEING CONTROLLED. |
| | PLEASE SEE MISSING AUTO SHUT OFF OF PIT LIGHTS. PLEASE |
| | BE SURE THE LCP PANEL ONLY CONTROL LIGHTING WHICH |
| | SHOULD NOT BE TURNED OFF, :IE: PLEASE CIRCUIT WHICH ARE |
| | SHOWN BEING WIRED TO THE LCP'S , HOWEVER PLEASE SEE |
| | THERE ARE ALSO EMERGENCY LIGHTING ON THOSE SAME |
| | CIRCUITS. PLEASE PROVIDE DETAIL ON THE LCP |
| | RISER/DIAGRAM WHERE ALL EXIT AND EMERGENCY LIGHTING IS |
| | CIRCUITED AHEAD OF THE LOCAL LIGHTING CONTROL DEVICES. |
| | PLEASE SEE MISSING PERFORMANCE CALCULATIONS FOR ALL |
| | AREAS. PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO |
| | NOT INDICATE ANY EXTERIOR LIGHTING; HOWEVER THE PLANS |
| | INDICATE LIGHTING IN MANY LOCATIONS. |
| | PLEASE SEE ENERGY CALCULATIONS DO NOT INDICATE THE |
| | REQUIRED AUTOMATED CONTROLS WHERE LISTING TYPE OF |
| | CONTROL. |
| | PLEASE SEE 13-415.1.AB.1, 13-415.2, 13-415.2.ABC.1, |
| | 13-415.2.ABC.1.3. |
| | PLEASE SEE FBC CHAPTER 13, AS THERE ARE MANY AREAS AND |
| | ITEMS AS NOTED ABOVE WHICH NEEDS TO BE ADJUSTED. |
| | |
| | 3) NOTE: PLEASE CORRELATE THE SQ FT ON PERMIT |
| | APPLICATION WITH THAT OF THE PLANS. |
| | |
| | 4) NOTE: PLEASE SEE MISSING NORMAL AND EMERGENCY |
| | PHOTO-METRICS IN ALL EGRESS PATH AREAS. PLEASE SEE |
| | MISSING STAIR WAYS. PLEASE SEE NFPA-101 2003, 7.8.1.3, |
| | AND 7.9.2.2. |
| | A) STAIRS REQUIRE A MINIMUM OF 10FT CANDLES UNDER |
| | NORMAL AND 1FT CANDLE UNDER EMERGENCY. |
| | B) PLEASE SEE THIS IS FOR ALL EXIT STAIRS TO THE PUBLIC |
| | RIGHT OF WAY FOR EGRESS PATHS. |
| | |
| | 5) NOTE: PLEASE SEE NFPA-101 7.8, 7.9, WHICH REQUIRES |
| | LIGHTING AND EMERGENCY LIGHTING TO THE PUBLIC RIGHT OF |
| | WAY. PLEASE SEE ALL EXTERIOR STAIRS INCLUDING LARGE AND |
| | SMALLER STAIRS AREAS WILL REQUIRE SOME SORT OF BATTERY |
| | BACK UP FIXTURES WHICH WILL PROVIDE THE MINIMUM FT |
| | CANDLES TO THE PUBLIC RIGHT OF WAY, OUT AND AWAY FROM |
| | THE BUILDING. |
| | PLEASE SEE THIS INCLUDES RAMP AREAS. |
| | |
| | 5) NOTE: PLEASE SEE ELEVATOR EQUIPMENT ROOMS WHICH WILL |
| | REQUIRE A CHANGE IN FIXTURE TYPE OR AN ADDITIONAL |
| | FIXTURE. PLEASE SEE 700.16. |
| | |
| | 6) NOTE: PLEASE SEE 110.26, 408.7, AND 240.24D WHICH DO |
| | NOT PERMIT ELECTRICAL PANELS TO BE LOCATED IN STORAGE |
| | ROOMS OR CLOSETS. PLEASE ADJUST LOCATIONS OF EQUIPMENT |
| | OR CREATE DEDICATED ELECTRICAL ROOMS/CLOSETS AS DONE IN |
| | SOME OTHER LOCATIONS ON PLANS. |
| | *** PLEASE SEE ACCESS TO ELECTRICAL EQUIPMENT SHOULD |
| | ALSO NOT BE THROUGH STORAGE ROOMS. EQUIPMENT SHOULD BE |
| | LOCATED IN A MANNER WHICH READY ACCESS CAN BE GRANTED |
| | AND QUITE OFTEN STORAGE ROOMS BECOME A LOCATION WHERE |
| | THINGS IMPEDE ACCESS AS NEEDED. |
| | |
| | 7) NOTE: PLEASE SEE POSSIBLE BUILDING OR FIRE REVIEW |
| | COMMENTS WITH RESPECT TO STAIRWAY #4.IT IS UNCLEAR AS |
| | THIS SEEMS TO EXIT OCCUPANTS BACK INTO THE BUILDING. |
| | THERE ARE SOME INSTANCES WHERE THIS IS PERMITTED; |
| | HOWEVER DEPENDING ON POSSIBLE COMMENTS THIS WILL AFFECT |
| | THE ELECTRICAL PLANS AND LAYOUT IF ANY CHANGES ARE |
| | NEEDED. THIS IS ONLY A NOTE AT THIS TIME. |
| | |
| | 8) NOTE: PLEASE BE SURE ALL FIXTURES ARE IDENTIFIED BY |
| | THEIR FIXTURE DESIGNATIONS. PLEASE SEE SOME FIXTURES |
| | ARE MISSING THIS. |
| | PLEASE SEE OTHER FIXTURES WHICH ARE INDICATED AS "UT", |
| | HOWEVER THIS FIXTURE IS NOT LOCATED ON FIXTURE |
| | SCHEDULED AND THE SYMBOL AROUND THE FIXTURE IS NOT |
| | SIMILAR AND COULD NOT BE LOCATE ANY OTHER DESIGNATION |
| | OR REFERENCE ON PLANS. PLEASE CLARIFY THIS? |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 9) NOTE: PLEASE SEE THERE ARE SEVERAL CIRCUITS ON PLANS |
| | WHICH DO NOT SEEM TO BE SHOWN GOING THROUGH ANY OF THE |
| | LCP'S? |
| | PLEASE PROVIDE A COMPLETE LCP SCHEDULE FOR ALL |
| | CIRCUITS. |
| | 13-415.1.ABC.1.1, .1.2, AND .1.3. |
| | |
| | 10) NOTE: PLEASE PROVIDE MORE INFORMATION ON MAIN 1 OF |
| | 2. PLEASE INDICATE SIZE, VOLTAGEETC. |
| | 230, 240, 110.3, 90.7 |
| | FBC 106.1.2 |
| | |
| | 11) NOTE: PLEASE SEE MISSING AN EQUIPMENT GROUNDING |
| | CONDUCTOR FROM THIS MAIN 1 OF 2 TO THE EXISTING MDP |
| | PANEL. |
| | IT IS NOTED THAT THE SYSTEM SHALL SEPARATE ALL NEUTRAL |
| | AND GROUND CONNECTIONS AT THE EXISTING MDP. 250.24B, |
| | 250.110, 250.122 |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 12) NOTE: PLEASE SEE AN "EQUIPMENT GROUNDING CONDUCTOR" |
| | IS BEING SHOWN FROM THE FPL TRANSFORMER TO THE NEW MAIN |
| | 2 OF 2? PLEASE SEE 250.6, AND 250.24 AS EQUIPMENT |
| | GROUNDING CONDUCTORS ARE ONLY INSTALLED AFTER THE FIRST |
| | MEANS OF DISCONNECT. |
| | |
| | 13) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AND THE |
| | LARGEST MOTOR LOADS ON EACH PANEL AND SERVICE AT 125%. |
| | PLEASE SEE NO LOAD CALCULATIONS OR LOAD SUMMARY COULD |
| | BE LOCATED. |
| | 220.3, 220.10, 220.11, 220.13, 215.3 AND 230.42 ETC. |
| | FBC ADMIN SECTION 106.3.5.1.2 |
| | |
| | 14) NOTE: PLEASE SEE PANEL "L2 AA" IS BEING SHOWN FED |
| | FROM MULTIPLE PANELS. PLEASE SEE THIS PANEL IS SHOWN |
| | FED FROM BOTH "DP2A" AND "DP2B". PLEASE CORRELATE AND |
| | ADJUST. |
| | PLEASE SEE RISER AS THE RISER SHOWS THIS PANEL ONLY |
| | BEING FED FROM DP2A. |
| | FBC 106.1.2. |
| | |
| | 15) NOTE: PLEASE SEE PANEL "DP1B" WHICH INDICATES A |
| | FEED TO A PANEL "L1BB" , YET NO PANEL SCHEDULE COULD BE |
| | LOCATED ON THE PLANS SUBMITTED. |
| | FBC 106.1.2 |
| | |
| | 16) NOTE: PLEASE SEE A PANEL SCHEDULE FOR "L3AB" WAS |
| | SUBMITTED ON PANEL SCHEDULES, HOWEVER COULD NOT LOCATED |
| | ON ANY OTHER OF THE PANEL SCHEDULE WHERE THIS IS FED |
| | FROM OR COULD NOT LOCATED THIS ON THE ELECTRICAL RISER |
| | DIAGRAM EITHER.PLEASE CLARIFY. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 17) NOTE: PLEASE BE SURE TO GO THROUGH PLANS AND |
| | CORRELATE ALL PANELS SHOWN ON PLANS WITH THE RISER |
| | DIAGRAM AND PANEL SCHEDULES SUBMITTED. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 18) NOTE: PLEASE SEE INDICATE ANY FIRE SPRINKLER WATER |
| | LINE AS PART OF THE GROUNDING ELECTRODE SYSTEM. |
| | 250.106 |
| | |
| | 19) NOTE: PLEASE SEE FBC 2004 11-4.28.2 AND |
| | 11-4.28.3(4) FOR ALL AUDIBLE AND VISUAL DEVICES. PLEASE |
| | SEE 11-4.28.1 FOR LOCATION REQUIREMENTS. PLEASE BE SURE |
| | FA PLANS INDICATE ALL THE MINIMUM LEVELS PER ADA AND |
| | PLACES NOTES ALSO FOR FBC SECTIONS AS GIVEN. |
| | |
| | ** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SHOWN OR |
| | MISSING, THERE MAY BE COMMENTS ON THE FOLLOWING |
| | REVIEW. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2006-11-27 07:00:34 | REVIEW IN PROGRESS |
| 2006-11-26 15:03:26 | ONE ROLL INELECTRICALFOR REVIEW. |