| Notes |
| Date |
Text |
| 2007-01-17 14:39:14 | DENIED; | | | 1.BREAK SINK CABINET DOORS CANNOT SWING INTO THE CLEAR | | | FLOOR SPACE. SHOW DETAIL HOW GARBAGE DISPOSAL SHALL BE | | | INSTALLED AND STILL ALLOW THE 19" REQUIRED UNDER SINK. | | | 2.WATER HAMMER ARRESTOR REQUIRED FOR ICE MAKER. SEE | | | PLUMBING SECTION 604.9. SHOW ON WATER RISER DIAGRAM AND | | | LIST MANUFACTURE AND TYPE ON PLANS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|