| 2007-01-11 10:19:48 | BUILDING PLAN REVIEW |
| | PERMIT: 06110144 |
| | ADD: 500 AUSTRALIAN AVE SUITE# 910 |
| | CONT: KARL CORP CONSTRUCTION SERVICES |
| | TEL: (561)718-3799 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) NOT CAUGHT ON THE FIRST REVIEW SEE SHEET |
| | M-1 STAIR TOWER # 1. |
| | 1019.1.2 PENETRATIONS. |
| | PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT |
| | ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| | DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT |
| | PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, |
| | ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION |
| | AND ELECTRICAL RACEWAY SERVING THE EXIT ENCLOSURE AND |
| | TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE |
| | INCHES (0.010 M 2 ). SUCH PENETRATIONS SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 712 . THERE SHALL |
| | BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER |
| | PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES. |
| | |
| | 1019.1.3 VENTILATION. |
| | EQUIPMENT AND DUCTWORK FOR EXIT ENCLOSURE VENTILATION |
| | SHALL COMPLY WITH ONE OF THE FOLLOWING ITEMS: |
| | 1.SUCH EQUIPMENT AND DUCTWORK SHALL BE LOCATED |
| | EXTERIOR TO THE BUILDING AND SHALL BE DIRECTLY |
| | CONNECTED TO THE EXIT ENCLOSURE BY DUCTWORK ENCLOSED IN |
| | CONSTRUCTION AS REQUIRED FOR SHAFTS. |
| | 2.WHERE SUCH EQUIPMENT AND DUCTWORK IS LOCATED |
| | WITHIN THE EXIT ENCLOSURE, THE INTAKE AIR SHALL BE |
| | TAKEN DIRECTLY FROM THE OUTDOORS AND THE EXHAUST AIR |
| | SHALL BE DISCHARGED DIRECTLY TO THE OUTDOORS, OR SUCH |
| | AIR SHALL BE CONVEYED THROUGH DUCTS ENCLOSED IN |
| | CONSTRUCTION AS REQUIRED FOR SHAFTS. |
| | 3.WHERE LOCATED WITHIN THE BUILDING, SUCH |
| | EQUIPMENT AND DUCTWORK SHALL BE SEPARATED FROM THE |
| | REMAINDER OF THE BUILDING, INCLUDING OTHER MECHANICAL |
| | EQUIPMENT, WITH CONSTRUCTION AS REQUIRED FOR SHAFTS. |
| | IN EACH CASE, OPENINGS INTO THE FIRE-RESISTANCE-RATED |
| | CONSTRUCTION SHALL BE LIMITED TO THOSE NEEDED FOR |
| | MAINTENANCE AND OPERATION AND SHALL BE PROTECTED BY |
| | SELF-CLOSING FIRE-RESISTANCE-RATED DEVICES IN |
| | ACCORDANCE WITH CHAPTER 7 FOR ENCLOSURE WALL OPENING |
| | PROTECTIVES. |
| | EXIT ENCLOSURE VENTILATION SYSTEMS SHALL BE INDEPENDENT |
| | OF OTHER BUILDING VENTILATION SYSTEMS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |