Plan Review Notes
Plan Review Notes For Permit 06110143
Permit Number 06110143
Review Stop P
Sequence Number 1
Notes
Date Text
2006-12-06 14:31:33DENIED;
 1. BREAK SINK;GARBAGE DISPOSAL WILL NOT ALLOW A
 FRONTAL APPROACH UNDER SINK. SEE FBC-2004 BUILDING
 CHAPTER 11 SECTION 11-4.24.3 KNEECLEARANCE.
 2. PLEASE ADD NOTES TO INTERIOR ELEVATION DETAIL 01 ON
 PAGE A-3.01;
 DEPTH OF SINK 6 1/2 " DEEP MAX.
 SEC11-4.23.4
 RAP EXPOSED PIPES. SEC. 11-4.24.6
 SPECIFY TYPE OF HANDLES ON SINK FAUSET
 SEC. 11-4.24.7.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695