| 2006-12-12 16:58:53 | BUILDING PLAN REVIEW |
| | PERMIT: 06110143 |
| | ADD: 500 S AUSTRALIAN SUITE# 930 |
| | CONT: KARL CORP CONST |
| | TEL: (561)718-3799 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) SHEET A-0 PROJECT INFORMATION |
| | PROVIDE BUILDING TYPE II "A OR B" |
| | |
| | 3) 110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | ALSO THE 2004 EXISTING BUILDING CODE. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | |
| | 4) THE SAME CONDITION WILL EXIST AT THE ENTRY DOOR |
| | AND THE DOOR AT THE RECEPTIONIST IN BOTH CASES THE |
| | REQUIRED 18" ON THE LATCH, PULL SIDE OF THE DOOR IS |
| | REQUIRED.11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARANCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARANCES SHALL BE |
| | CLEAR & LEVEL. |
| | 1003.3.3 HORIZONTAL PROJECTIONS. |
| | ELEMENTS CANNOT PROJECT OVER A WALKING SURFACE MORE |
| | THAN 4 INCHES (102 MM) WHEN THEY ARE LOCATED BETWEEN 27 |
| | AND 80 INCHES (686 AND 2032 MM) ABOVE THE FLOOR. |
| | HANDRAILS CAN PROJECT UP TO 4? INCHES (114 MM) FROM THE |
| | WALL. |
| | 11-4.4.1 GENERAL. |
| | OBJECTS PROJECTING FROM WALLS (FOR EXAMPLE, TELEPHONES) |
| | WITH THEIR LEADING EDGES BETWEEN 27 INCHES AND 80 |
| | INCHES (685 MM AND 2030 MM) ABOVE THE FINISHED FLOOR |
| | SHALL PROTRUDE NO MORE THAN 4 INCHES (102 MM) INTO |
| | WALKS, HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES [SEE |
| | FIGURE 11-8 (A)]. OBJECTS MOUNTED WITH THEIR LEADING |
| | EDGES AT OR BELOW 27 INCHES (685 MM) ABOVE THE FINISHED |
| | FLOOR MAY PROTRUDE ANY AMOUNT [SEE FIGURE 11-8 (A) AND |
| | FIGURE 11-8 (B)]. FREE-STANDING OBJECTS MOUNTED ON |
| | POSTS OR PYLONS MAY OVERHANG 12 INCHES (305 MM) MAXIMUM |
| | FROM 27 INCHES TO 80 INCHES (685 MM TO 2030 MM) ABOVE |
| | THE GROUND OR FINISHED FLOOR [SEE FIGURE 11-8 (C) AND |
| | FIGURE 11-8 (D)]. PROTRUDING OBJECTS SHALL NOT REDUCE |
| | THE CLEAR WIDTH OF AN ACCESSIBLE ROUTE OR MANEUVERING |
| | SPACE [SEE FIGURE 11-8 (E)]. |
| | |