2006-12-05 15:51:25*** DENIED ***
 1) DUCTS PASSING THROUGH RATED WALLS AND OVER RATED
 DOORS REQUIRE FIRE DAMPERS, SEE 2004 FBC/M 607.5.3.
  
 2) 14" FLEX DUCT MAY NOT PASS THROUGH A FIRE RATED WALL
 OR OVER A RATED DOOR, SEE 2004 FBC/M 607.7.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.