| 2006-12-05 15:51:25 | *** DENIED *** | | | 1) DUCTS PASSING THROUGH RATED WALLS AND OVER RATED | | | DOORS REQUIRE FIRE DAMPERS, SEE 2004 FBC/M 607.5.3. | | | | | | 2) 14" FLEX DUCT MAY NOT PASS THROUGH A FIRE RATED WALL | | | OR OVER A RATED DOOR, SEE 2004 FBC/M 607.7. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|