| 2006-12-12 16:42:09 | BUILDING PLAN REVIEW |
| | PERMIT: 06110142 |
| | ADD: 500 S AUSTRALIAN AV9TH FLOOR COMMON |
| | CORRIDOR |
| | CONT: KARL CORP CONSTRUCTION |
| | TEL: (561)718-3799 |
| | |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) 110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | *** 2004 EXISTING BUILDING CODE |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | PLANS INDICATEA TYPE II BUILDING, TYPE "A OR B" |
| | DE)IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | |
| | 3)PLEASE PROVIDE WALL AND CEILING CLASSIFICATION. |
| | TABLE 803.5 REQUIRED BY OCCUPANCY |
| | GENERAL. |
| | INTERIOR WALL AND CEILING FINISHES SHALL BE CLASSIFIED |
| | IN ACCORDANCE WITH ASTM E 84. SUCH INTERIOR FINISH |
| | MATERIALS SHALL BE GROUPED IN THE FOLLOWING CLASSES IN |
| | ACCORDANCE WITH THEIR FLAME SPREAD AND SMOKE-DEVELOPED |
| | INDEX. |
| | CLASS A: |
| | FLAME SPREAD INDEX 0-25; SMOKE-DEVELOPED INDEX 0-450. |
| | CLASS B: |
| | FLAME SPREAD INDEX 26-75; SMOKE-DEVELOPED INDEX 0-450. |
| | |
| | CLASS C: |
| | FLAME SPREAD INDEX 76-200; SMOKE-DEVELOPED INDEX 0-450. |
| | |
| | |