Plan Review Notes For Permit 06110137
Permit Number 06110137
Review Stop P
Sequence Number 1
Notes
Date Text
2006-12-16 11:49:02 
 PAUL SCHMITZ
 [email protected] FBC 2004 PLUMBING
 CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 PLUMBING DENIED
  
 1) PLANS SHALL BE ROUTED TO DBPR
 BUSINESS AND HOTEL DIVISION FOR
 REVIEW. MINIMUM 2 SETS OF PLANS
 SHALL BE REVIEWED AND STAMPED
 AND THE TWO PAGE ?WORKSHEETS?
 ATTACHED TO EACH SET OF PLANS
 PRIOR TO RESUBMITTING TO CITY OF WEST PALM BEACH
 FOR REVIEW. PLEASE CONTACT DBPR
 AT (850) 487-1395.
  
 2) RE: GREASE WASTE SYSTEM
 CONTACT W P BEACHWATERPLANT LAB SUPERVISOR
 INDUSTRIAL COORDINATOR, LYNN MASSON
  
 OFFICE 561-822-2271E-MAIL [email protected]
  
 3) SHT 100,SEC 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010.
  
 4) SHT P100 SEC 606.1 LOCATION OF FULL-OPEN VALVES.
 FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 ON THE TOP OF EVERY WATER DOWN-FEED PIPE IN OCCUPANCIES
 OTHER THAN ONE- AND TWO-FAMILY RESIDENTIAL
 OCCUPANCIES.
  
 5) SEE OTHER PLAN REVIEW COMMENTS, THAT MAY EFFECT
 PLUMBING PLAN REVIEW.
  
 END OF COMMENTS, QUESTIONS 561-805-6692