Plan Review Notes
Plan Review Notes For Permit 06110137
Permit Number 06110137
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-12-12 11:47:04*****DENIED*****
  
  
  
 1.THE ADDRESS ON THE SUBMITTED PLANS DO NOT MATCH THE
 ADDRESS ON THE PERMIT APPLICATION OR IN THE CITY'S
 PERMITTING SYSTEM.THE CORRECT ADDRESS SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.NFPA 101 (2003 EDITION), FLORIDA FIRE PREVENTION
 CODE (2004 EDITION), NFPA 13 (2002 EDITION), AND NFPA
 72 (2002 EDITION) SHALL BE REFERENCED FOR FIRE AND LIFE
 SAFETY CONCERNS.AMEND SHEET A002, GENERAL NOTE #1.
  
 3.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.ADD TO DEMO NOTES.
  
 4.COMBUSTIBLE WASTE, DUST, AND DEBRIS SHALL BE
 REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR MORE
 FREQUENTLY AS NECESSARY FOR SAFE OPERATION.ADD TO
 DEMO NOTES.
  
 5.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER ACCESS TO OR EGRESS FROM OTHER
 AREAS OF THE BUILDING.ADD TO DEMO NOTES
  
 6.IF THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM IS
 MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE PLANS AND
 PERMIT ARE REQUIRED.
  
 7.SEPARATE MECHANICAL PERMITS WILL BE REQUIRED FOR
 THE HOOD/FIRE SUPPRESSION SYSTEM.
  
 8.PROVIDE INTERIOR FINISH CLASSIFICATION INFORMATION
 FOR WALLS AND CEILINGS TO BE INSTALLED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW