Plan Review Notes
Plan Review Notes For Permit 06110137
Permit Number 06110137
Review Stop B
Sequence Number 1
Notes
Date Text
2006-12-18 08:56:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)A002, CODE ANALYSIS, BUILDING TYPE, DECLARE A OR B
 FBC 601.
  
 2.)A002, EXISTING BUILDING IS DECLARED AS R, NEW
 OCCUPANCY IS A-1 AND R-1, BUT THE PLANS SHOW THAT THIS
 IS A RENOVATION TO AN EXISTING KITCHEN.IS THIS A
 CHANGE OF OCCUPANCY?
  
 3.)DECLARE GOVERNING CODE.INCLUDE FLORIDA BUILDING
 CODE 2004 EXISTING BUILDING CODE.
  
 4.)DELCARE LEVEL OF ALTERATION FBC EB CHAPTER 3.
  
 5.)IF THIS IS A CHANGE OF OCCUPANCY, THE RENOVATION
 IS TO COMPLY WITH FBC EB CHAPTER 8.PLEASE INDICATE ON
 THE PLAN AND SHOW COMPLIANCE.
  
 6.)SHEET A002 REFERS TO FIRE RESISTANCE REQUIREMENTS,
 FBC TABLE 600.THIS IS FROM FBC2001.SEE FBC TABLE
 601, FBC TABLE 602, FBC CHAPTER 7.
  
 7.)CODE ANALYSIS, A002, FIRE RESISTANCE, INTERIOR
 NONBEARING PARTITIONS, CODE REFERENCES ARE FBC2001.
 PLEASE REVISE OR REMOVE.
  
 8.)CODE ANALYSIS, FIRE RESISTANCE, A002, EXTERIOR
 BEARING WALLS, SHOWS A 4 HOUR WALL WITH NO LIMIT ON
 OPENINGS.PLEASE CLARIFY WHAT THIS MEANS OR HOW IT
 PERTAINS TO THIS PLAN.
  
 9.)A0002, CODE ANALYSIS, FIRE RESISTANCE OF EXIT
 ACCESS CORRIDORS, OCCUPANCY R1, SHOULD BE 1 HOUR, 1/2
 HOUR IS SHOWN.FBC TABLE 1016.1.
  
 10.)EXIT REQUIREMENTS, FBC TABLE 1004, IS ALSO A
 REFERENCE FROM FBC2001.REVISE AND CHECK ALL CODE
 REFERENCES TO BE CONSISTENT WITH FBC2004.
  
 11.)SHOW OCCUPANCY CLASSIFICATION FOR THE RENOVATED
 AREA AS WELL AS ADJACENT OCCUPANCY CLASSIFICATION. SHOW
 ANY REQUIRED FIRE RESISTANCE RATINGS ON THE FLOOR
 PLAN.
  
 12.)INDICATE TRAVEL DISTANCE TO EXITS ON THE PLAN.
  
 13.)WHERE SPRINKLERS ARE REQUIRED FOR CODE
 COMPLIANCE, FIRE SPRINKLER PLANS ARE TO BE A PART OF
 THE PERMIT PACKAGE.SEE ATTACHED LETTER FROM DCA.
 CALCULATIONS AND SHOPS ARE NOT REQUIRED AT THIS TIME;
 SUBMIT WITH SEPARATE PERMIT.A FIRE SPRINKLER LAYOUT
 IS REQUIRED IF THE SYSTEM IS TO BE MODIFIED.
  