| 2006-12-18 08:56:29 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB |
| | FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| | FBC2004 |
| | |
| | 1.)A002, CODE ANALYSIS, BUILDING TYPE, DECLARE A OR B |
| | FBC 601. |
| | |
| | 2.)A002, EXISTING BUILDING IS DECLARED AS R, NEW |
| | OCCUPANCY IS A-1 AND R-1, BUT THE PLANS SHOW THAT THIS |
| | IS A RENOVATION TO AN EXISTING KITCHEN.IS THIS A |
| | CHANGE OF OCCUPANCY? |
| | |
| | 3.)DECLARE GOVERNING CODE.INCLUDE FLORIDA BUILDING |
| | CODE 2004 EXISTING BUILDING CODE. |
| | |
| | 4.)DELCARE LEVEL OF ALTERATION FBC EB CHAPTER 3. |
| | |
| | 5.)IF THIS IS A CHANGE OF OCCUPANCY, THE RENOVATION |
| | IS TO COMPLY WITH FBC EB CHAPTER 8.PLEASE INDICATE ON |
| | THE PLAN AND SHOW COMPLIANCE. |
| | |
| | 6.)SHEET A002 REFERS TO FIRE RESISTANCE REQUIREMENTS, |
| | FBC TABLE 600.THIS IS FROM FBC2001.SEE FBC TABLE |
| | 601, FBC TABLE 602, FBC CHAPTER 7. |
| | |
| | 7.)CODE ANALYSIS, A002, FIRE RESISTANCE, INTERIOR |
| | NONBEARING PARTITIONS, CODE REFERENCES ARE FBC2001. |
| | PLEASE REVISE OR REMOVE. |
| | |
| | 8.)CODE ANALYSIS, FIRE RESISTANCE, A002, EXTERIOR |
| | BEARING WALLS, SHOWS A 4 HOUR WALL WITH NO LIMIT ON |
| | OPENINGS.PLEASE CLARIFY WHAT THIS MEANS OR HOW IT |
| | PERTAINS TO THIS PLAN. |
| | |
| | 9.)A0002, CODE ANALYSIS, FIRE RESISTANCE OF EXIT |
| | ACCESS CORRIDORS, OCCUPANCY R1, SHOULD BE 1 HOUR, 1/2 |
| | HOUR IS SHOWN.FBC TABLE 1016.1. |
| | |
| | 10.)EXIT REQUIREMENTS, FBC TABLE 1004, IS ALSO A |
| | REFERENCE FROM FBC2001.REVISE AND CHECK ALL CODE |
| | REFERENCES TO BE CONSISTENT WITH FBC2004. |
| | |
| | 11.)SHOW OCCUPANCY CLASSIFICATION FOR THE RENOVATED |
| | AREA AS WELL AS ADJACENT OCCUPANCY CLASSIFICATION. SHOW |
| | ANY REQUIRED FIRE RESISTANCE RATINGS ON THE FLOOR |
| | PLAN. |
| | |
| | 12.)INDICATE TRAVEL DISTANCE TO EXITS ON THE PLAN. |
| | |
| | 13.)WHERE SPRINKLERS ARE REQUIRED FOR CODE |
| | COMPLIANCE, FIRE SPRINKLER PLANS ARE TO BE A PART OF |
| | THE PERMIT PACKAGE.SEE ATTACHED LETTER FROM DCA. |
| | CALCULATIONS AND SHOPS ARE NOT REQUIRED AT THIS TIME; |
| | SUBMIT WITH SEPARATE PERMIT.A FIRE SPRINKLER LAYOUT |
| | IS REQUIRED IF THE SYSTEM IS TO BE MODIFIED. |
| | |