2006-11-06 11:15:25BUILDING REVIEW CHECKLIST:
  
 1- NEED TO INDICATE SPECIFIC APPROVED ASSEMBLY THAT IS
 GOING TO BE INSTALLED.SEE CITY POLICY FOR RE-ROOFING
 PERMITS AND PROVIDE ALL REQUIRED INFORMATION.
  
 2- INDICATE SPECIFIC FASTENING OPTION ON SELECTED
 APPROVED ASSEMBLY.
  
 3- IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #7, THEN PROVIDE RAS 117 CALCULATIONS FOR
 ENHANCED FASTENING AT PERIMETER AND CORNER AREAS. SEE
 GENERAL LIMITATION #7 ON LAST PAGE OF DADE COUNTY NOA
 #03-0501.02 SUBMITTED.
 ***NOTE: IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATAION #9, THEN IT MAY NOT BE USED BECAUSE THERE
 IS NOT NAIL ENHANCING ALLOWED. SEE GENERAL LIMITATION
 #9.
  