Plan Review Notes
Plan Review Notes For Permit 06110096
Permit Number 06110096
Review Stop P
Sequence Number 2
Notes
Date Text
2007-01-06 07:04:35DENIED;
 1. A PRIVATE TOILET ROOM IS FOR ONE PERSON NOT ALL 6
 EMPLOYEES. THIS IS A COMMON TOILET ROOM AND MUST COMPLY
 WITH FBC-2004 BUILDING CHAPTER 11. SEE SECTIONS
 11-4.1.3(11) AND 11-4.22.
 2. SINK IS NOT A WORK SINK. ELECTRICAL PLAN SHOWS AN
 OUTLET IN CABINET FOR A REF. AND GAR. DISP. SINK TO
 MEET HANDICAP REQUIREMENTS.
 3. SHOW CLEAR FRONTAL FLOORSPACEAT LACATORY AND
 SINK, AND TURNING RADIUS IN BATHROOM.
 4. SHOW DETAILS OF TOILET ROOM ,TOILET, LAVATORY AND
 SINK WITH ALL REQUIRED MEASUREMENTS.
 SEE THE FOLLOWING CODE SECTIONS FOR
 REFORANCE;
 TOILET:
 11-4.16.2 CLEAR FLOOR SPACE
 11-4.16.3 HEIGHT
 11-4.16.4 GRAB BAR
 11-4.16.5 FLUSH CONTROL
 11-4.16.6 DISPENSERS
 LAVATORY:
 11-4.19.2 HEIGHT AND CLEARANCE
 11-4.19.3 CLEAR FLOOR SPACE ( FRONTAL)
 11-4.19.4 EXPOSED PIPES
 11-4.19.5 FAUCET
 11-4.19.6 MIRROR
 SINK:
 11-4.24.2 HEIGHT
 11-4.24.3 KNEE CLEARANCE
 11-4.24.4 DEPTH OF SINK
 11-4.24.5 CLEAR FLOOR SPACE
 11-4.24.6 EXPOSED PIPES
 11-4.24.7 FAUCET
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695