Plan Review Notes
Plan Review Notes For Permit 06110096
Permit Number 06110096
Review Stop E
Sequence Number 2
Notes
Date Text
2006-12-21 11:45:49** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING. PLEASE SEE THE NOTES BELOW ARE
 TAKEN DIRECTLY FROM PREVIOUS REVIEW WITH A NOTATION OF
 OK OR NO IF COMMENT WAS OR WAS NOT ADDRESS FULLY.
 PLEASE SEE SOMETIMES A NO/OK IS PLACED AHEAD OF THE
 NOTE AS THE NOTE MAY HAVE ONLY BEEN PARTIALLY
 ADDRESSED.
  
 ** PLEASE ALSO SEE SOME NEW COMMENTS BASED ON PLANS
 SUBMITTED. THESE NEW COMMENTS ARE AT THE END OF THE
 FIRST REVIEW COMMENTS.
  
  
 1) NOTE:NO, PLEASE SEE NO ADDRESS FOR LOCATION AND
 SUITE IS YET ON THE TITLE BLOCKS FOR SAID PROJECT.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004,
 61G15-23.002
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY WORK LOCATION. PLANS MENTIONS WORK FOR
 CONTRACTOR/ENGINEERING OFFICE PERMIT APPLICATION
 MENTIONS UNIT #105? PLEASE INCLUDE SUITE OF THE SCOPE
 OF WORK BEING DONE.
  
 2) NOTE: NO/OK, PLEASE SEE THE SIZE OF THE EXISTING
 PANEL "AM" IS STILL IN QUESTION AND THE LOCATION ON
 PLANS APPEARS TO SHOW THIS IN A ROOM, HOWEVER NOT CLEAR
 IF THIS PANEL IS IN ANOTHER TENANT SPACE, SEPARATELY
 METERED ETC.
 PLEASE CLARIFY FURTHER AND SHOW.
 FBC 106.1.2
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY THE PANEL MENTIONED AS "AM" PLEASE
 CLARIFY WHERE THIS PANEL IS AND HOW THIS PANEL IF IN A
 SEPARATE SPACE FEEDS THIS SPACE.
 PLEASE ALSO SUBMIT LOAD CALCULATIONS FOR THIS EXISTING"
 AM" PANEL WITH NEW " LP" PANEL ADDED.
 THIS SCENARIO IS NOT CLEAR AT THIS TIME.
 220.3,220.10,220.11,220.13,CONTINUOUS LOADS PER
 215.3,230.42 ETC.
 FBC ADMINISTRATIVE SECTION 106.1.2, AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 3) NOTE: NO, PLEASE SEE THE CODE SECTIONS AS GIVEN
 BELOW IN PREVIOUS REVIEW. PLEASE SEE THE RESPONSE
 MENTIONS A TIME CLOCK BEING ADDED, HOWEVER NO DETAIL
 FOR THIS IS SHOWN. NO SCHEDULING, NO OVER RIDE CONTROLS
 IN SPACES AS REQUIRED AND NO TIMES ON OVER RIDES.
 PLEASE SEE THE DEVICES AND SYSTEM AS BEING SELECTED BY
 THE DESIGNER SHALL BE INDICATED ON PLANS AND CORRELATE
 WITH THE SYMBOL LEGEND.
 PLEASE SEE SECTIONS AS GIVEN FOR MISSING LIGHTING POWER
 DENSITIES?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THIS APPEAR AND IS BEING SHOWN AS A NEW
 TENANT BUILD OUT LOCATED IN A BUILDING GREATER THAN 5K
 SQ FT. PLEASE SEE FBC 2004, 13-415.1.ABC.1.1, .1.2 AND
 .1.3
 13-415.2.ABC.1
 ** NEW NOTE **
  
 1) NOTE: PLEASE BE SURE PLANS REFLECT THE FOLLOWING
 MINIMUM CODES AS REQUIRED. STATING THE LATEST EDITION
 MAY NOT APPLY AS DEPENDING ON PERMIT APPLICATION WAS
 MADE, THIS WILL DICTATE WHICH CODES THE PLANS ARE UNDER
 AND RELEVANT TO THE DESIGNS.
 THIS COMMENT WAS MISSED BY THIS REVIEWER ON PREVIOUS
 REVIEW, HOWEVER IS REQUIRED.
 PLEASE KNOW PERMIT APPLICATIONS BEFORE 12/8/06 WILL
 PLACE ELECTRICAL UNDER NFPA-70 2002 (NEC) , 2003
 NFPA-101, 2002 NFPA-72 AND REV #5 TO THE 2004 FBC.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]