| 2007-01-05 11:09:43 | PERMIT: 06110096 |
| | ADD: 2247 PALM BEACH LAKES BLVD,SUITE 105 |
| | CONT: AMODIE ENGINEERING & CONSTRUCTION |
| | TEL: (561)685-7500 |
| | |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | 2) 2ND REQUEST, 110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) COMPLIED. |
| | B) COMPLIED. |
| | |
| | C) THE TYPE OF CONSTRUCTION"FOR THE BUILDING" |
| | AS DEFINED IN CHAPTER 6, TABLE 503. |
| | THIS WILL DEFINE WHAT MATERIALS WILL OR WILL |
| | NOT BE ALLOWED IN THIS STRUCTURE. |
| | THE RESPONCE INDICATED A TYPE V BUILDING NOT INDICATING |
| | A OR B, |
| | AND TO THE ANSWER TO QUESTION "E" SPRINKLERS NOT |
| | REQUIRED. |
| | THIS BUILDING IS APPROX 12,500 SQ FT IN FOOTPRINT, |
| | TABLE 503ONLY ALLOWS 9.000SF |
| | FOR A TYPE V-B BUILDING. EITHER THIS IS A TYPE V-A OR |
| | TYPE V-B WITH AREA INCREASES |
| | OR THE AREA INCREASES FOR FIRE SPRINKLERS. |
| | |
| | D) COMPLIED. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | G) COMPLIED. |
| | H) LEVEL OF ALTERATIONS? 2004 EXISTING BUILDING CODE, |
| | SEE LEVEL 2, CHAPTER II. |
| | |
| | 3) COMPLIED. |
| | |
| | 4) COMPLIED.PRIVATE RESTROOMS ARE TO BE |
| | ADAPTABLE.11-4.1.3(11) |
| | ( REQUIRES BACKING IN WALLS.) |
| | |
| | 5) 2ND REQUEST, YOUR RESPONCE TO A BREAK ROOM SINK |
| | VS A WORK SINK, WHAT TYPE OF WORK WILL BE ACCOMPLISHED |
| | THAT WILL TRANSFORM THISFROM A BREAK ROOM SINK TO A |
| | WORK SINK? |
| | WHEN THE E SHEETS SHOW THERE TO BE AN UNDER COUNTER |
| | REFRIGARATOR AND A GARBAGE DISPOSAL |
| | IT APPEARS THIS IS TRUELY A BREAK ROOM SINK. |
| | PLEASE SEE,11-4.24.2 SINKS, HEIGHT. SINKS SHALL |
| | BE MOUNTED WITH THE COUNTER NO HIGHER |
| | THAN 34" ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT |
| | LEAST 27" HIGH 30" WIDE, AND 19" DEEP |
| | SHALL BE PROVIDED UNDERNEATH SINKS. |
| | |
| | |
| | 6) COMPLIED. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |