| Plan Review Notes For Permit 06110096 |
| Permit Number |
06110096 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-20 09:58:24 | ****UNSAT**** | | | | | | | | | | | | 1.IN THE TITLE BLOCK OF THE SUBMITTED PLANS, THE | | | ACTUAL LOCATION OF WHERE THE SCOPE OF WORK WILL BE | | | CONDUCTED SHOULD BE INCLUDED. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. | | | | | | 4.PLEASE PROVIDE EXISTING FLOOR PLAN THAT INCLUDES | | | EXIT LIGHTS, EMERGENCY LIGHTS, FIRE EXTINGUISHER(S), | | | ETC. FOR THIS TENANT SPACE.HOW WILL THEY BE AFFECTED | | | BY THE SCOPE OF THE WORK? | | | | | | 5.PLEASE DECLARE INTERIOR FINISH CLASSIFICATION FOR | | | WALLS AND CEILINGS. | | | | | | 6.IF THE FIRE ALARM AND SINCE THE SPRINKLER SYSTEM | | | ARE MODIFIED BY THE SCOPE OF THE WORK, SEPARATE PLANS | | | AND PERMIT ARE REQUIRED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | | INCLUDE A RESPONSE SHEET INDICATING HOW/WHERE EACH ITEM | | | WAS ADDRESSED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|