| 2006-11-17 12:55:19 | **** UNSAT ***** |
| | |
| | 1) NOTE: PLEASE SEE AS THE MAJORITY OF THE INSTALLATION |
| | OF THE WORK INVOLVED IS NOT ELECTRICAL. PLEASE SEE |
| | SCOPE APPEARS TO BE OUT OF THAT OF AN ELECTRICAL |
| | CONTRACTOR. PLEASE KNOW A CONTRACTOR LICENSED TO |
| | INSTALL THIS SIZE FUEL TANK CAN BE THE PRIME |
| | CONTRACTOR, AND THE ELECTRICAL CAN BE THE SUB FOR THE |
| | ELECTRICAL HOOK UP. |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES WITH RESPECT |
| | TO WHO CAN INSTALL ETC. |
| | PLEASE SEE FS 489. |
| | |
| | 2) NOTE: PLEASE PROVIDE A COMPLETE LAYOUT FOR THE |
| | ENTIRE INSTALLATION OF THE ELECTRICAL SYSTEM INCLUDING |
| | ALL HAZARDOUS LOCATIONS, CLEARANCES HEIGHTS/ELEVATIONS |
| | ETC. |
| | PLEASE SEE FUEL DISPENSING IN THE NEC,514. |
| | PLEASE ALSO SEE COMMENTS FROM OTHER TRADES AS THIS IS A |
| | 750 GAL UNIT. PLEASE SEE MINIMUM CLEARANCES REQUIRED |
| | FROM BUILDINGS ETC WHICH WILL BE IN OTHER REVIEW |
| | COMMENTS. |
| | |
| | 3) NOTE: PLEASE KNOW, EVEN WHEN PLANS ARE NOT REQUIRED |
| | TO BE DONE BY ARCHITECT OR ENGINEER, THEY ARE REQUIRED |
| | TO CONTAIN A PRINTED NAME AND SIGNATURE FOR THE |
| | DESIGNS. |
| | PLEASE KNOW BASED ON SCOPE OF WORK AND REQUIREMENTS FOR |
| | WIND LOADS AND THE SPECIALIZED REQUIREMENTS SHOWN, |
| | PLANS WILL BE REQUIRED TO BE DONE BY AN ARCHITECT OR |
| | ENGINEER. |
| | FBC ADMIN SECTION 106.3.1.2(5). |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWER(S) AS THESE |
| | WILL GREATLY AFFECT THE PLANS SUBMITTED. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF |
| | THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE |
| | DO NOT HESITATEIN CONTACTING THIS REVIEWER. |
| | |
| | |
| | |
| | |