| 2006-11-28 12:03:35 | BUILDING PLAN REVIEW |
| | PERMIT: 06110087 |
| | ADD: 3199 CUMBERLAND DR |
| | CONT: DCS ELECTRIC |
| | TEL: (561)7224690 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2 ) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 3) DCS ELECTRIC HAAS A EC STATE LICENSE, WHEN THE |
| | MAJORITY OF THE WORK IS NOT ELECTRIC, THE "PRIME PERMIT |
| | " HAS TO BE SIGNED BY EITHER A POLLUTANT STORAGE |
| | SYSTEMS CONTRACTOR OR IF GASOLINE A MECHANICAL |
| | CONTRACTOR. |
| | 489.105 |
| | I)"MECHANICAL CONTRACTOR" MEANS A CONTRACTOR WHOSE |
| | SERVICES ARE UNLIMITED IN THE EXECUTION OF CONTRACTS |
| | REQUIRING THE EXPERIENCE, KNOWLEDGE, AND SKILL TO |
| | INSTALL, MAINTAIN, REPAIR, FABRICATE, ALTER, EXTEND, OR |
| | DESIGN, WHEN NOT PROHIBITED BY LAW, CENTRAL |
| | AIR-CONDITIONING, REFRIGERATION, HEATING, AND |
| | VENTILATING SYSTEMS, INCLUDING DUCT WORK IN CONNECTION |
| | WITH A COMPLETE SYSTEM ONLY TO THE EXTENT SUCH DUCT |
| | WORK IS PERFORMED BY THE CONTRACTOR AS IS NECESSARY TO |
| | MAKE COMPLETE AN AIR-DISTRIBUTION SYSTEM, BOILER AND |
| | UNFIRED PRESSURE VESSEL SYSTEMS, LIFT STATION EQUIPMENT |
| | AND PIPING, AND ALL APPURTENANCES, APPARATUS, OR |
| | EQUIPMENT USED IN CONNECTION THEREWITH, AND ANY DUCT |
| | CLEANING AND EQUIPMENT SANITIZING WHICH REQUIRES AT |
| | LEAST A PARTIAL DISASSEMBLING OF THE SYSTEM; TO |
| | INSTALL, MAINTAIN, REPAIR, FABRICATE, ALTER, EXTEND, OR |
| | DESIGN, WHEN NOT PROHIBITED BY LAW, PIPING, INSULATION |
| | OF PIPES, VESSELS AND DUCTS, PRESSURE AND PROCESS |
| | PIPING, PNEUMATIC CONTROL PIPING, GASOLINE TANKS AND |
| | PUMP INSTALLATIONS AND PIPING FOR SAME, STANDPIPES, AIR |
| | PIPING, VACUUM LINE PIPING, OXYGEN LINES, NITROUS OXIDE |
| | PIPING, INK AND CHEMICAL LINES, FUEL TRANSMISSION |
| | LINES, LIQUEFIED PETROLEUM GAS LINES WITHIN BUILDINGS, |
| | AND NATURAL GAS FUEL LINES WITHIN BUILDINGS; TO |
| | REPLACE, DISCONNECT, OR RECONNECT POWER WIRING ON THE |
| | LOAD SIDE OF THE DEDICATED EXISTING ELECTRICAL |
| | DISCONNECT SWITCH; TO INSTALL, DISCONNECT, AND |
| | RECONNECT LOW VOLTAGE HEATING, VENTILATING, AND |
| | AIR-CONDITIONING CONTROL WIRING; AND TO INSTALL A |
| | CONDENSATE DRAIN FROM AN AIR-CONDITIONING UNIT TO AN |
| | EXISTING SAFE WASTE OR OTHER APPROVED DISPOSAL OTHER |
| | THAN A DIRECT CONNECTION TO A SANITARY SYSTEM. THE |
| | SCOPE OF WORK FOR SUCH CONTRACTOR SHALL ALSO INCLUDE |
| | ANY EXCAVATION WORK INCIDENTAL THERETO, BUT SHALL NOT |
| | INCLUDE ANY WORK SUCH AS POTABLE WATER LINES OR |
| | CONNECTIONS THERETO, SANITARY SEWER LINES, SWIMMING |
| | POOL PIPING AND FILTERS, OR ELECTRICAL POWER WIRING. |
| | |
| | P)"POLLUTANT STORAGE SYSTEMS CONTRACTOR" MEANS A |
| | CONTRACTOR WHOSE SERVICES ARE LIMITED TO, AND WHO HAS |
| | THE EXPERIENCE, KNOWLEDGE, AND SKILL TO INSTALL, |
| | MAINTAIN, REPAIR, ALTER, EXTEND, OR DESIGN, WHEN NOT |
| | PROHIBITED BY LAW, AND USE MATERIALS AND ITEMS USED IN |
| | THE INSTALLATION, MAINTENANCE, EXTENSION, AND |
| | ALTERATION OF, POLLUTANT STORAGE TANKS. ANY PERSON |
| | INSTALLING A POLLUTANT STORAGE TANK SHALL PERFORM SUCH |
| | INSTALLATION IN ACCORDANCE WITH THE STANDARDS ADOPTED |
| | PURSUANT TO S. 376.303. |
| | |
| | 4) PLEASE PROVIDE THE LOCATION OF THIS UNIT WITH THE |
| | LOCATION OF THE STRUCTURE, LOCATE ALL WINDOWS, DOORS , |
| | AND SOFFIT VENTS, PROVIDE THE DISTANCE AWAY FROM THE |
| | FUEL TANK TO THE STRUCTURE.ALSO INDICATE WHAT THIS IS A |
| | FUEL TANK TOO? |
| | |
| | 5) PROVIDE HOW THE FUEL TANK WILL BE BOLTED DOWN TO |
| | RESIST THE MOMENT OF OVERTURNING. |
| | 1609.1.3 ANCHORAGE AGAINST OVERTURNING , UPLIFT AND |
| | SLIDING. |
| | STRUCTURAL MEMBERS AND SYSTEMS AND COMPONENTS AND |
| | CLADDING IN A BUILDING OR STRUCTURE SHALL BE ANCHORED |
| | TO RESIST WIND-INDUCED OVERTURNING , UPLIFT AND SLIDING |
| | AND TO PROVIDE CONTINUOUS LOAD PATHS FOR THESE FORCES |
| | TO THE FOUNDATION. WHERE A PORTION OF THE RESISTANCE TO |
| | THESE FORCES IS PROVIDED BY DEAD LOAD, THE DEAD LOAD, |
| | INCLUDING THE WEIGHT OF SOILS AND FOUNDATIONS, SHALL BE |
| | TAKEN AS THE MINIMUM DEAD LOAD LIKELY TO BE IN PLACE |
| | DURING A DESIGN WIND EVENT. WHERE THE ALTERNATE BASIC |
| | LOAD COMBINATIONS OF SECTION 1605.3.2 ARE USED, ONLY |
| | TWO-THIRDS OF THE MINIMUM DEAD LOAD LIKELY TO BE IN |
| | PLACE DURING A DESIGN WIND EVENT SHALL BE USED. |
| | |
| | 6)NOTE, PROVISO: THE TANK IS ALSO LOCATED IN A A-8 |
| | FLOOD ZONE, |
| | THE FINISHED FLOOR LEVEL SHALL BE |
| | VERIFIED BY A SIGNED AND SEALED |
| | ELEVATION CERTIFICATE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |