Plan Review Notes
Plan Review Notes For Permit 06110070
Permit Number 06110070
Review Stop B
Sequence Number 2
Notes
Date Text
2006-12-01 10:23:58BUILDING REVIEW 2ND CHECKLIST:
  
 1- A) ENGINEER LETTER FOR ENHANCED FASTENING AT
 PERIMETER AND CORNER AREAS PREPARED BY DON ARPIN IS
 WRONG. ENGINEER'S DESIGN PRESSURES ( PG 16.20 EXP. B:
 -30.4, -51 AND -76.8) ARE FOR BASIC WIND SPEED OF
 130MPH-3 SECOND GUST.THE CITY OF WEST PALM BEACH
 ADOPTED THE 140MPH-3 SECOND GUST BASIC WIND SPEED. NEED
 TO REVISE DESIGN PRESSURES AS REQUIRED.
  
 B) ENGINEER TO IDENTIFY SPECIFIC APPROVED ASSEMBLY
 FROM NOA SUBMITTED. SPECIFY PAGE FROM THE NOA OR
 COMPLETELY IDENTIFY APPROVED SYSTEM FROM NOA.
  
 2- ENGINEER TO PROVIDE COMPLETE RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 OF LAST PAGE OF NOA
 06-0626.02. ENGINEER TO READ GENERAL LIMITATION #7 AND
 PROVIDE ALL REQUIRED INFORMATION.
  
 3- NEED FIELD WITHDRAWAL RESISTANCE TESTING AS REQUIRED
 BY GENERAL LIMITATION #7.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.