2006-11-13 17:22:30BUILDING REVIEW 2ND CHECKLIST:
  
 1- FLAT ROOF SYSTEM ON PAGE 25 OF NOA 02-1205.02
 DOESN'T WORK FOR THIS AREA BECAUSE THE DESIGN PRESSURES
 ARE TOO LOW FOR PERIMETER AND CORNER AREAS. SEE TABLE
 1609.6B OF 2004 FBC FOR REQUIRED DESIGN PRESSURES.
 SYSTEM IS LIMITED BY GENERAL LIMITATION #9 WHICH
 DOESN'T ALLOW NAIL ENHANCING TO INCREASE THE DESIGN
 PRESSURES OF THE SYSTEM. ONLY SYSTEMS THAT ARE LIMITED
 BY GENERAL LIMITATION #7 MAY HAVE ENHANCED FASTENING AT
 PERIMETER AND CORNER AREAS. SEE GENERAL LIMITATION #7
 ON LAST PAGE OF NOA. CALCULATIONS MUST BE DONE ONLY BY
 ANY ONE OF THOSE LISTED IN GENERAL LIMITATION #7.
 THEREFORE,SELECT A SYSTEM WITH LIMITATION #7 AND
 PROVIDE THE RAS 117 CALCULATIONS PREPARED BY ANY ONE OF
 THE LISTED PROFESSIONALS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712