| Plan Review Notes For Permit 06110061 |
| Permit Number |
06110061 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-11-13 17:22:30 | BUILDING REVIEW 2ND CHECKLIST: | | | | | | 1- FLAT ROOF SYSTEM ON PAGE 25 OF NOA 02-1205.02 | | | DOESN'T WORK FOR THIS AREA BECAUSE THE DESIGN PRESSURES | | | ARE TOO LOW FOR PERIMETER AND CORNER AREAS. SEE TABLE | | | 1609.6B OF 2004 FBC FOR REQUIRED DESIGN PRESSURES. | | | SYSTEM IS LIMITED BY GENERAL LIMITATION #9 WHICH | | | DOESN'T ALLOW NAIL ENHANCING TO INCREASE THE DESIGN | | | PRESSURES OF THE SYSTEM. ONLY SYSTEMS THAT ARE LIMITED | | | BY GENERAL LIMITATION #7 MAY HAVE ENHANCED FASTENING AT | | | PERIMETER AND CORNER AREAS. SEE GENERAL LIMITATION #7 | | | ON LAST PAGE OF NOA. CALCULATIONS MUST BE DONE ONLY BY | | | ANY ONE OF THOSE LISTED IN GENERAL LIMITATION #7. | | | THEREFORE,SELECT A SYSTEM WITH LIMITATION #7 AND | | | PROVIDE THE RAS 117 CALCULATIONS PREPARED BY ANY ONE OF | | | THE LISTED PROFESSIONALS. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|