Plan Review Notes
Plan Review Notes For Permit 06110027
Permit Number 06110027
Review Stop E
Sequence Number 2
Notes
Date Text
2006-12-17 10:24:04*** UNSAT 2ND REVIEW***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH
 STILL NEEDS TO BE CLARIFIED OR ADDRESSED.
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE:NO, PLEASE SEE ALL CIRCUITING FOR NEW SHALL
 BE INDICATE ON PLANS AT A MINIMUM AND CORRELATE WITH A
 PANEL SCHEDULE TO BE SUBMITTED. PLEASE KNOW DUE TO THE
 NEW LOAD(S) BEING ADDED, A LOAD CALCULATIONS ON THE
 EXISTING FEEDERS/PANEL SHALL BE DONE AND SUBMITTED WITH
 THE PANEL SCHEDULE.
 PLEASE INDICATE ALL EXISTING WITH THE SYMBOL AS SHOWN
 ON SYMBOL LEGEND. THE E LOCATED NEXT TO THE EXIT LIGHTS
 ONLY INDICATES EXISTING DOORS. PLEASE INDICATE NEW OR
 EXISTING CIRCUITING FOR EM/EXT LTS PER 700.12E.
 PLEASE SEE THAT ALL RELOCATED DEVICES INDICATE "R" OR
 SOME INDICATION OF WHICH THESE ARE..
 106.1.2, 106.3.5.1.2 FBC ADMIN SECTION. 408.4, 310.16,
 ETC.
  
  
 **PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY IF THIS IS A BUILD OUT OF A NEW
 TENANT SPACE OR AN EXISTING TENANT AND OCCUPANT? PLEASE
 PROVIDE CIRCUITING ON PLANS FOR NEW ELECTRICAL AND
 CORRELATE WITH A PANEL SCHEDULE TO BE SUBMITTED. 240.4,
 408.6, 310.16
 FBC ADMIN SECT AS ADOPTED BY THE CITY OF WEST PALM
 BEACH 106.1.2, 106.3.5.1.2
  
 4) NOTE:NO, SEE NOTE #3 ABOVE.
 PLEASE SHOW NEW OR EXISTING LIGHTING. PLEASE INDICATE
 NEW OR EXISTING EXT/ EM LTS WHICH MEET LS 101, 7.8,
 7.9, AND NEC 700.12 E.
  
  
 ** NEW NOTE **
  
 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
  
 2) NOTE: PLEASE ALSO SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE NEW WATER HEATER. PLANS SEEM TO INDICATE
 INSTA-HOT, YET ALSO SHOWS 6-GAL STORAGE TYPE.
 110.3, 90.7, FBC ADMIN SECTION 106.1.2
  
 NO REVIEW OF SOME ELECTRICAL ITEMS CAN BE DONE AT THIS
 TIME AS SOME INFORMATION WAS NOT SUBMITTED FOR REVIEW.
 PLEASE KNOW THERE MAY BE FURTHER COMMENTS DUE TO
 INFORMATION NOT YET SUBMITTED.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]