| Date |
Text |
| 2006-12-17 10:24:04 | *** UNSAT 2ND REVIEW*** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH |
| | STILL NEEDS TO BE CLARIFIED OR ADDRESSED. |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE:NO, PLEASE SEE ALL CIRCUITING FOR NEW SHALL |
| | BE INDICATE ON PLANS AT A MINIMUM AND CORRELATE WITH A |
| | PANEL SCHEDULE TO BE SUBMITTED. PLEASE KNOW DUE TO THE |
| | NEW LOAD(S) BEING ADDED, A LOAD CALCULATIONS ON THE |
| | EXISTING FEEDERS/PANEL SHALL BE DONE AND SUBMITTED WITH |
| | THE PANEL SCHEDULE. |
| | PLEASE INDICATE ALL EXISTING WITH THE SYMBOL AS SHOWN |
| | ON SYMBOL LEGEND. THE E LOCATED NEXT TO THE EXIT LIGHTS |
| | ONLY INDICATES EXISTING DOORS. PLEASE INDICATE NEW OR |
| | EXISTING CIRCUITING FOR EM/EXT LTS PER 700.12E. |
| | PLEASE SEE THAT ALL RELOCATED DEVICES INDICATE "R" OR |
| | SOME INDICATION OF WHICH THESE ARE.. |
| | 106.1.2, 106.3.5.1.2 FBC ADMIN SECTION. 408.4, 310.16, |
| | ETC. |
| | |
| | |
| | **PREVIOUS REVIEW NOTE ** |
| | PLEASE CLARIFY IF THIS IS A BUILD OUT OF A NEW |
| | TENANT SPACE OR AN EXISTING TENANT AND OCCUPANT? PLEASE |
| | PROVIDE CIRCUITING ON PLANS FOR NEW ELECTRICAL AND |
| | CORRELATE WITH A PANEL SCHEDULE TO BE SUBMITTED. 240.4, |
| | 408.6, 310.16 |
| | FBC ADMIN SECT AS ADOPTED BY THE CITY OF WEST PALM |
| | BEACH 106.1.2, 106.3.5.1.2 |
| | |
| | 4) NOTE:NO, SEE NOTE #3 ABOVE. |
| | PLEASE SHOW NEW OR EXISTING LIGHTING. PLEASE INDICATE |
| | NEW OR EXISTING EXT/ EM LTS WHICH MEET LS 101, 7.8, |
| | 7.9, AND NEC 700.12 E. |
| | |
| | |
| | ** NEW NOTE ** |
| | |
| | 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | |
| | 2) NOTE: PLEASE ALSO SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE NEW WATER HEATER. PLANS SEEM TO INDICATE |
| | INSTA-HOT, YET ALSO SHOWS 6-GAL STORAGE TYPE. |
| | 110.3, 90.7, FBC ADMIN SECTION 106.1.2 |
| | |
| | NO REVIEW OF SOME ELECTRICAL ITEMS CAN BE DONE AT THIS |
| | TIME AS SOME INFORMATION WAS NOT SUBMITTED FOR REVIEW. |
| | PLEASE KNOW THERE MAY BE FURTHER COMMENTS DUE TO |
| | INFORMATION NOT YET SUBMITTED. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |