Plan Review Notes
Plan Review Notes For Permit 06110027
Permit Number 06110027
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-11-14 11:45:52*****UNSAT*****
  
  
  
 1.NFPA 101 - 2003 EDITIONAND FIRE PREVENTION CODE -
 2004 EDITION SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.INTERIOR RENOVATION OPERATIONS SHALL NOT INTERFERE
 OR HINDER EMERGENCY ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF (INCLUDING FIRE LANES).
  
 4.INDICATETHE LOCATION OF EXIT LIGHTS, EMERGENCY
 LIGHTS, FIRE EXTINGUISHERS AND ANY OTHER LIFE SAFETY
 SYSTEMS.HOW WILL THEY BE AFFECTED BY THE SCOPE OF THE
 WORK?
  
 5.IF THE INTERIOR BUILDOUT REQUIRES MODIFICATION OF
 THE FIRE SPRINKLER AND/OR FIRE ALARM SYSTEM, SEPARATE
 PERMIT AND PLANS WILL BE REQUIRED.
  
 6.INTERIOR FINISHING FOR WALLS AND CEILINGS IN EXITS
 AND EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS
 "B".
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW OR WHERE EACH
 ITEM WAS ADDRESSED.
  
  
  