| Plan Review Notes For Permit 06110027 |
| Permit Number |
06110027 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-14 11:45:52 | *****UNSAT***** | | | | | | | | | | | | 1.NFPA 101 - 2003 EDITIONAND FIRE PREVENTION CODE - | | | 2004 EDITION SHALL BE REFERENCED. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.INTERIOR RENOVATION OPERATIONS SHALL NOT INTERFERE | | | OR HINDER EMERGENCY ACCESS TO THE SAID PROPERTY OR | | | VICINITY THEREOF (INCLUDING FIRE LANES). | | | | | | 4.INDICATETHE LOCATION OF EXIT LIGHTS, EMERGENCY | | | LIGHTS, FIRE EXTINGUISHERS AND ANY OTHER LIFE SAFETY | | | SYSTEMS.HOW WILL THEY BE AFFECTED BY THE SCOPE OF THE | | | WORK? | | | | | | 5.IF THE INTERIOR BUILDOUT REQUIRES MODIFICATION OF | | | THE FIRE SPRINKLER AND/OR FIRE ALARM SYSTEM, SEPARATE | | | PERMIT AND PLANS WILL BE REQUIRED. | | | | | | 6.INTERIOR FINISHING FOR WALLS AND CEILINGS IN EXITS | | | AND EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS | | | "B". | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | | INCLUDE A RESPONSE LETTER INDICATING HOW OR WHERE EACH | | | ITEM WAS ADDRESSED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | |
|