| Date |
Text |
| 2006-11-04 17:51:38 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE THAT THE FOLLOWING CODES AT A |
| | MINIMUM SHALL BE STATED ON PLANS. |
| | 2002 NFPA-70(NEC), 2003 NFPA-101, 2002 NFPA-72 |
| | ** PLEASE SEE PLANS ON FRONT COVER SHEET REFLECT A NFPA |
| | 2004. |
| | PLEASE SEE WRONG LIFE SAFETY CODE IS ALSO REFLECTED. |
| | (2004). |
| | (PLEASE KNOW THE NEXT ADOPTED EDITION OF THE NFPA-70 |
| | WILL BE THE 2005.) |
| | |
| | 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON |
| | TITLE BLOCKS FOR ENGINEERING FIRM AND ENGINEER OF |
| | RECORD PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002. |
| | PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER |
| | OF ENGINEER AND MISSING THE PLANS ARE NOT SEALED, AS |
| | REQUIRED PER FS 471.025. |
| | |
| | THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S). |
| | PLEASE ALSO SEE FRONT COVER SHEET. |
| | |
| | 3) NOTE:PLEASE CLARIFY IF THIS IS A BUILD OUT OF A |
| | NEW TENANT SPACE OE AN EXISTING TENANT AND OCCUPANT? |
| | PLEASE PROVIDE CIRCUITING ON PLANS FOR NEW ELECTRICAL |
| | AND CORRELATE WITH A PANEL SCHEDULE TO BE SUBMITTED. |
| | 240.4, 408.6, 310.16 |
| | FBC ADMIN SECT AS ADOPTED BY THE CITY OF WEST PALM |
| | BEACH 106.1.2, 106.3.5.1.2 |
| | |
| | 4) NOTE: PLEASE SHOW NEW OR EXISTING LIGHTING. PLEASE |
| | INDICATE NEW OR EXISTING EXT/ EM LTS WHICH MEET LS 101, |
| | 7.8, 7.9, AND NEC 700.12 E. |
| | |
| | NO REVIEW OF SOME ELECTRICAL ITEMS CAN BE DONE AT THIS |
| | TIME AS SOME INFORMATION WAS NOT SUBMITTED FOR REVIEW. |
| | PLEASE KNOW THERE MAY BE FURTHER COMMENTS DUE TO |
| | INFORMATION NOT YET SUBMITTED. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2006-11-04 17:38:24 | REMOVED FROM INCOMING. |