| Plan Review Notes For Permit 06110027 |
| Permit Number |
06110027 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-09 08:26:41 | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) SPECIFY THE TYPE OF CONSTRUCTION BASED ON 2004 FBC | | | DESIGNATIONS. SPECIFY A OR B. SEE FBC TABLE 601. | | | | | | 3) CLARIFY THE SCOPE OF WORK FOR THIS PERMIT. IS THIS A | | | TENANT BUILD OUT, A CHANGE OF OCCUPANCY OR ALTERATIONS | | | TO AN EXISTING TENANT SPACE. | | | | | | 4) SPECIFY THE LEVEL OF ALTERATION PER 2004 FBC | | | EXISTING BUILDING CODE CHAPTER 3. | | | | | | 5) THE DOOR SCHEDULE SPECIFIES A NEW 3-0 DOOR #1. WHERE | | | IS THIS DOOR LOCATED ON THE FLOOR PLAN? | | | | | | 6) PLANS HAVE NOT BEEN SEALED WITH THE EMBOSSED SEAL OF | | | THE ARCHITECT AS REQUIRED BY FAC 61G1-16.003. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | | | | |
|