Plan Review Notes
Plan Review Notes For Permit 06110022
Permit Number 06110022
Review Stop G
Sequence Number 1
Notes
Date Text
2006-11-07 16:56:47UNSAT
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC AND
 DOES NOT SHOW ALL CUT SECTIONS OF PIPE AND DOES NOT
 INDICATE THE CORRESPONDING LENGTHS OF THE ABOVE GROUND
 PIPING. PLEASE REFERENCE THE EXAMPLE ISOMETRIC OF THE
 SUBMITTED DRAWING WITH THE PROVIDED INFORMATION MINUS
 THE MISSING ABOVE GROUND INFORMATION.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: THE ABOVE GROUND PIPING MATERIAL AND SIZES ARE
 NOT INDICATED ON THE DRAWING.
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: PLEASE INDICATE ON THE DRAWING THE MP REGULATOR
 MAKE AND MODEL NUMBER AND SUBMITMANUFACTURER CUT SHEETS
 OF THE MP REGULATORS.
  
 4. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 5. NOTE: THE APPROVED POOL HEATER FOR SAID RESIDENCE
 ON POOL PERMIT #06061247 IS A 399,000 BTU HEATER THIS
 IS DIFFERENT FROM THE BTU LOAD ON THE SUBMITTED GAS
 DRAWING OF 199,000.PLEASE CLARIFY THIS DIFFERENCE ON
 THE RESUBMITTAL.
  
 6. PROVIDE A NOTICE OF COMMENCEMENT RECORDED WITH THE
 CLERK OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
 NOTE: FOR FUTURE PERMIT APPLICATIONSPLEASE REFERENCE
 THE ENCLOSED "CITY OF WEST PALM BEACH, GAS PERMIT
 APPLICATION REQUIREMENTS"
  
 END OF COMMENTS:
  