Plan Review Notes
Plan Review Notes For Permit 06110021
Permit Number 06110021
Review Stop G
Sequence Number 2
Notes
Date Text
2006-12-04 13:24:28DENIED 2ND TIME
 REFERENCE: FBC-2004 FUEL GAS AND FBC-2004 CHAPTER 1
  
 THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR GAS
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. (OK)
 2. (OK)
 3. (OK)
 4. (OK)
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: MANUFACTURE CUT SHEETS OF THE MP REGULATORS ARE
 STILL REQUIRED, PLEASE SUBMIT ON THE RESUBMITTAL.
  
 6. PER FBC-2004, CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
 NOTE: THE INDICATED VALUE OF $495.00 STILL SEEMS WAY TO
 LOW. THE INDICATED APPLIANCES (WATER HEATER AND BBQ) ON
 THE DRAWING COST MORE THAN $495.00. AGAIN PLEASE ADJUST
 THE VALUE ON THE RESUBMITTAL OR AN ACCESSED VALUE WILL
 BE DONE ON THE RESUBMITTAL AND FEES MIGHT NEED TO BE
 PAID BEFORE A PERMIT IS ISSUED.
  
 *******************************************************
 *******************************************************
 *******************************************************
 *******************************************************
  
 THE FOLLOWING ARE NEW COMMENTS OF CORRECTIONS THAT ARE
 REQUIRED FOR GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 7. PER FBC-2004, CHAPTER 1, SECTION 106.1: TWO (2)
 COMPLETE SETS OF DRAWINGS ARE REQUIRED FOR PLAN REVIEW,
 ONLY ONE (1) WAS RESUBMITTED.
  
 8. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  