| 2006-12-04 13:24:28 | DENIED 2ND TIME |
| | REFERENCE: FBC-2004 FUEL GAS AND FBC-2004 CHAPTER 1 |
| | |
| | THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR GAS |
| | PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. (OK) |
| | 2. (OK) |
| | 3. (OK) |
| | 4. (OK) |
| | |
| | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | NOTE: MANUFACTURE CUT SHEETS OF THE MP REGULATORS ARE |
| | STILL REQUIRED, PLEASE SUBMIT ON THE RESUBMITTAL. |
| | |
| | 6. PER FBC-2004, CHAPTER 1, SECTION |
| | 108.3, BUILDING PERMIT VALUATION: IF IN |
| | THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF THE BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED. FOR |
| | PERMITTING PURPOSES, VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, NORMAL SITE WORK (EXCAVATION AND |
| | BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| | AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| | VALUE. VALUATION REFERENCES MAY INCLUDE |
| | THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| | MEANS ECT.) WITH |
| | REGIONAL ADJUSTMENTS FOR LOCATION AS |
| | PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. |
| | NOTE: THE INDICATED VALUE OF $495.00 STILL SEEMS WAY TO |
| | LOW. THE INDICATED APPLIANCES (WATER HEATER AND BBQ) ON |
| | THE DRAWING COST MORE THAN $495.00. AGAIN PLEASE ADJUST |
| | THE VALUE ON THE RESUBMITTAL OR AN ACCESSED VALUE WILL |
| | BE DONE ON THE RESUBMITTAL AND FEES MIGHT NEED TO BE |
| | PAID BEFORE A PERMIT IS ISSUED. |
| | |
| | ******************************************************* |
| | ******************************************************* |
| | ******************************************************* |
| | ******************************************************* |
| | |
| | THE FOLLOWING ARE NEW COMMENTS OF CORRECTIONS THAT ARE |
| | REQUIRED FOR GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 7. PER FBC-2004, CHAPTER 1, SECTION 106.1: TWO (2) |
| | COMPLETE SETS OF DRAWINGS ARE REQUIRED FOR PLAN REVIEW, |
| | ONLY ONE (1) WAS RESUBMITTED. |
| | |
| | 8. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | |
| | END OF COMMENTS: |
| | |