| 2009-12-15 16:08:00 | REVISION REQUIRED THE FOLLOWING ITEMS HAVE BEEN DEEMED |
| | DEFICIENT OR WERE NOTED TO BE MISSING UPON REVIEW: |
| | |
| | 1) TRUSS DRAWINGS AND LAYOUT SIGNED SEALED AND DATED BY |
| | THE TRUSS ENGINEER AND REVIEWED BY THE DESIGNER OF |
| | RECORD OF THE STRUCTURE. MUST BE REVIEWED AND APPROVED |
| | PRIOR TO INSTALLATION. FBC 106.3.5 |
| | |
| | 2) TWO COPIES OF A KEY PLAN AND INSTALLATION SCHEDULE |
| | FOR THE ACCORDION SHUTTERS. SPECIFY THE OPENING |
| | LOCATIONS OF THE SHUTTERS, THE MOUNT TYPE, SPANS, |
| | FASTENERS, FASTENER SPACING, ETC. FBC 1609.1.2 NOTE: IF |
| | ALL OF THE REQUIRED INFORMATION IS SUBMITTED WITH THIS |
| | PERMIT THE SHUTTERS WILL BE INCLUDED WITH THIS PERMIT. |
| | IF NOT, A SEPARATE PERMIT AND FEES WILL BE REQUIRED AND |
| | THE C.O. WILL NOT BE ISSUED UNTIL THEY HAVE BEEN |
| | INSTALLED AND APPROVED. |
| | |
| | 3) TWO COPIES OF PRODUCT APPROVALS FOR THE BULLET |
| | RESISTANT WINDOWS AND PAYMENT DRAWER ASSEMBLIES, THE |
| | ROOFING MATERIALS AND THE WALL MOUNTED LOUVER VENTS FOR |
| | ATTIC VENTILATION. DCA RULE 9B-72 |
| | |
| | 4) THE GLASS TYPE, MULLION TYPE AND ANCHOR TYPE OF THE |
| | STOREFRONT WINDOWS. THIS INFORMATION DETERMINES THE |
| | DESIGN PRESSURES FOR THE ASSEMBLIES. FBC 1604.9 THIS |
| | INFORMATION CAN BE PROVIDED WITH THE SHOP DRAWINGS FROM |
| | THE WINDOW COMPANY. THEY WILL NEED TO BE SUBMITTED AND |
| | APPROVED PRIOR TO INSTALLATION. |
| | |
| | 5) THE HINGE OPTION AND IF THE STOREFRONT DOOR IS |
| | REINFORCED OR NOT. THIS INFORMATION DETERMINES DESIGN |
| | PRESSURES FOR THE ASSEMBLY. FBC 1604.9 THIS INFORMATION |
| | CAN BE PROVIDED WITH THE SHOP DRAWINGS. |
| | |
| | |
| | |
| 2009-12-15 14:49:05 | TEMPORARY FAILED STATUS WILL REMAIN UNTIL A CONTRACTOR |
| | IS DETERMINED. |