2009-12-15 16:08:00REVISION REQUIRED THE FOLLOWING ITEMS HAVE BEEN DEEMED
 DEFICIENT OR WERE NOTED TO BE MISSING UPON REVIEW:
  
 1) TRUSS DRAWINGS AND LAYOUT SIGNED SEALED AND DATED BY
 THE TRUSS ENGINEER AND REVIEWED BY THE DESIGNER OF
 RECORD OF THE STRUCTURE. MUST BE REVIEWED AND APPROVED
 PRIOR TO INSTALLATION. FBC 106.3.5
  
 2) TWO COPIES OF A KEY PLAN AND INSTALLATION SCHEDULE
 FOR THE ACCORDION SHUTTERS. SPECIFY THE OPENING
 LOCATIONS OF THE SHUTTERS, THE MOUNT TYPE, SPANS,
 FASTENERS, FASTENER SPACING, ETC. FBC 1609.1.2 NOTE: IF
 ALL OF THE REQUIRED INFORMATION IS SUBMITTED WITH THIS
 PERMIT THE SHUTTERS WILL BE INCLUDED WITH THIS PERMIT.
 IF NOT, A SEPARATE PERMIT AND FEES WILL BE REQUIRED AND
 THE C.O. WILL NOT BE ISSUED UNTIL THEY HAVE BEEN
 INSTALLED AND APPROVED.
  
 3) TWO COPIES OF PRODUCT APPROVALS FOR THE BULLET
 RESISTANT WINDOWS AND PAYMENT DRAWER ASSEMBLIES, THE
 ROOFING MATERIALS AND THE WALL MOUNTED LOUVER VENTS FOR
 ATTIC VENTILATION. DCA RULE 9B-72
  
 4) THE GLASS TYPE, MULLION TYPE AND ANCHOR TYPE OF THE
 STOREFRONT WINDOWS. THIS INFORMATION DETERMINES THE
 DESIGN PRESSURES FOR THE ASSEMBLIES. FBC 1604.9 THIS
 INFORMATION CAN BE PROVIDED WITH THE SHOP DRAWINGS FROM
 THE WINDOW COMPANY. THEY WILL NEED TO BE SUBMITTED AND
 APPROVED PRIOR TO INSTALLATION.
  
 5) THE HINGE OPTION AND IF THE STOREFRONT DOOR IS
 REINFORCED OR NOT. THIS INFORMATION DETERMINES DESIGN
 PRESSURES FOR THE ASSEMBLY. FBC 1604.9 THIS INFORMATION
 CAN BE PROVIDED WITH THE SHOP DRAWINGS.
  
  
  
2009-12-15 14:49:05TEMPORARY FAILED STATUS WILL REMAIN UNTIL A CONTRACTOR
 IS DETERMINED.