2009-09-29 16:19:242007 FBC W/2009 REVISIONS
 CONVENIENCE STORE WITH FUEL DISPENSING
  
 DENIED BY BUILDING
  
 1) ON SHEET S-1 THE COMPONENT AND CLADDING PRESSURES
 ARE INCORRECT FOR EXPOSURE C WITH A 20' MEAN ROOF
 HEIGHT. THE ONES LISTED ARE EXPOSURE 'B' PRESSURES.
 PLEASE CORRECT. FBC 1609.4.1
  
 2) ON SHEET S-2 THE NOTES AT THE BOTTOM OF THE PAGE
 LIST THE MEAN ROOF HEIGHT AS 30' AND THE BASIC WIND
 PRESSURE AS 29.85 PSF. THESE ARE INCORRECT. THE MEAN
 ROOF HEIGHT IS SPECIFIED AS 20' AND THE BASIC WIND
 PRESSURE FOR EXPOSURE C AS 38.38 ON SHEET S-1. PLEASE
 CORRECT. FBC 1609
  
 3) SUBMIT TRUSS DRAWINGS AND LAYOUT SIGNED SEALED AND
 DATED BY THE TRUSS ENGINEER AND REVIEWED BY THE
 DESIGNER OF RECORD OF THE STRUCTURE. MUST BE REVIEWED
 AND APPROVED PRIOR TO INSTALLATION. FBC 106.3.5
  
 4) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE ACCORDION SHUTTERS. SPECIFY THE
 OPENING LOCATIONS OF THE SHUTTERS, THE MOUNT TYPE,
 SPANS, FASTENERS, FASTENER SPACING, ETC. FBC 1609.1.2
 NOTE: IF ALL OF THE REQUIRED INFORMATION IS SUBMITTED
 WITH THIS PERMIT THE SHUTTERS WILL BE INCLUDED WITH
 THIS PERMIT. IF NOT, A SEPARATE PERMIT AND FEES WILL BE
 REQUIRED AND THE C.O. WILL NOT BE ISSUED UNTIL THEY
 HAVE BEEN INSTALLED AND APPROVED.
  
 5) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 BULLET RESISTANT WINDOWS AND PAYMENT DRAWER ASSEMBLIES.
 DCA RULE 9B-72
  
 6) ON THE PRODUCT APPROVALS FOR THE STOREFRONT WINDOWS,
 SPECIFY THE GLASS TYPE, MULLION TYPE AND ANCHOR TYPE BY
 CIRCLING THE APPROPRIATE ITEMS IN THE TABLES. THIS
 INFORMATION DETERMINES THE DESIGN PRESSURES FOR THE
 ASSEMBLIES. FBC 1604.9 THIS INFORMATION CAN BE PROVIDED
 WITH THE SHOP DRAWINGS FROM THE WINDOW COMPANY. THEY
 WILL NEED TO BE SUBMITTED AND APPROVED PRIOR TO
 INSTALLATION.
  
 7) ON THE PRODUCT APPROVALS FOR THE STOREFRONT DOOR
 SPECIFY THE HINGE OPTION AND IF REINFORCED OR NOT. THIS
 INFORMATION DETERMINES DESIGN PRESSURES FOR THE
 ASSEMBLY. FBC 1604.9 THIS INFORMATION CAN ALSO BE
 PROVIDED WITH THE SHOP DRAWINGS.
  
 8) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 ROOFING MATERIALS AND THE WALL MOUNTED LOUVER VENTS FOR
 ATTIC VENTILATION. DCA RULE 9B-72
  
 9) PLEASE RESPOND TO COMMENTS IN WRITING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW