Plan Review Notes
Plan Review Notes For Permit 06101156
Permit Number 06101156
Review Stop E
Sequence Number 5
Notes
Date Text
2009-08-11 10:04:15 
 ** DENIED REVIEW **
  
 1) NOTE: PERMIT HAS NOT YET BEEN APPLIED FOR BY
 LICENSED CONTRACTOR.
  
 2) NOTE: THE SUBMITTED CALCULATIONS NEED TO INCLUDE ALL
 EXTERIOR LIGHTING PER 13-415.AB.5, 13-415.AB.2.2. THIS
 WAS A SPECIFIC NOTE ON THE PREVIOUS REVIEW YET THE SAME
 ITEMS NEED TO BE ADDRESSED.
  
 ** AS PERMIT HAS BEEN APPLIED UNDER PERMIT APPLICATION
 AS *TBD* TO BE DETERMINED*, IF CALCULATIONS ARE
 SUBMITTED BACK AGAIN WITH THE SAME ITEMS FS
 553.80(2)(B)
  
 3) NOTE: PLANS ARE STILL SHOWING SOME LOCATIONS IN
 WHICH THERE ARE NOTES FOR 2008 GLITCHES TO THE 2007
 FBC. THERE ARE ONLY 2009 SUPPLEMENTS TO THE 2007 FBC.
  
 4) NOTE: PLEASE SUBMIT THE SPECS/MANUFACTURES CUT
 SHEETS ON MANUAL TRANSFER SWITCH. COULD NOT LOCATE ON
 THE SPECS SUBMITTED FOR THE DOUBLE THROW SWITCH AS THIS
 BEING LISTED AS A MANUAL TRANSFER SWITCH? THIS IS
 LEGALLY REQUIRED TRANSFER SWITCH PER STATUTES. IF THIS
 EQUIPMENT IS LISTED AS SUCH PLEASE PROVIDE.
 110.3,90.7,701.7, FS 526.143
  
 ** PLANS ARE NO LONGER RELEASED PER BUILDING DIRECTOR.
 A TIME WILL NEED TO BE SET UP TO BRING IN NEW REVISIONS
 AND CHANGE OUT SHEETS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  