| 2009-08-11 10:04:15 | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PERMIT HAS NOT YET BEEN APPLIED FOR BY |
| | LICENSED CONTRACTOR. |
| | |
| | 2) NOTE: THE SUBMITTED CALCULATIONS NEED TO INCLUDE ALL |
| | EXTERIOR LIGHTING PER 13-415.AB.5, 13-415.AB.2.2. THIS |
| | WAS A SPECIFIC NOTE ON THE PREVIOUS REVIEW YET THE SAME |
| | ITEMS NEED TO BE ADDRESSED. |
| | |
| | ** AS PERMIT HAS BEEN APPLIED UNDER PERMIT APPLICATION |
| | AS *TBD* TO BE DETERMINED*, IF CALCULATIONS ARE |
| | SUBMITTED BACK AGAIN WITH THE SAME ITEMS FS |
| | 553.80(2)(B) |
| | |
| | 3) NOTE: PLANS ARE STILL SHOWING SOME LOCATIONS IN |
| | WHICH THERE ARE NOTES FOR 2008 GLITCHES TO THE 2007 |
| | FBC. THERE ARE ONLY 2009 SUPPLEMENTS TO THE 2007 FBC. |
| | |
| | 4) NOTE: PLEASE SUBMIT THE SPECS/MANUFACTURES CUT |
| | SHEETS ON MANUAL TRANSFER SWITCH. COULD NOT LOCATE ON |
| | THE SPECS SUBMITTED FOR THE DOUBLE THROW SWITCH AS THIS |
| | BEING LISTED AS A MANUAL TRANSFER SWITCH? THIS IS |
| | LEGALLY REQUIRED TRANSFER SWITCH PER STATUTES. IF THIS |
| | EQUIPMENT IS LISTED AS SUCH PLEASE PROVIDE. |
| | 110.3,90.7,701.7, FS 526.143 |
| | |
| | ** PLANS ARE NO LONGER RELEASED PER BUILDING DIRECTOR. |
| | A TIME WILL NEED TO BE SET UP TO BRING IN NEW REVISIONS |
| | AND CHANGE OUT SHEETS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |