| 2009-07-24 12:22:54 | 2007 FBC W/2009 REVISIONS |
| | CONVENIENCE STORE WITH FUEL DISPENSING |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) ON SHEET S-1 AND THE TOP OF SHEET S-2 THE EXPOSURE |
| | CATEGORY IS CORRECTLY SPECIFIED AS 'C'. HOWEVER, AT THE |
| | BOTTOM OF SHEET S-2 THE EXPOSURE 'B' IS SPECIFIED ON |
| | THE ROOF ZONE DETAIL. PLEASE CORRECT. FBC 1609.4.1 |
| | |
| | 2) THE COMPONENT AND CLADDING PRESSURES ON SHEET A-5 DO |
| | NOT CORRESPOND WITH THOSE ON SHEET S-1. THE PRESSURES |
| | ON A-5 ARE FOR EXPOSURE CATEGORY 'B'. PLEASE CORRECT. |
| | FBC 1609 |
| | |
| | 3) SUBMIT TRUSS DRAWINGS AND LAYOUT SIGNED SEALED AND |
| | DATED BY THE TRUSS ENGINEER AND REVIEWED BY THE |
| | DESIGNER OF RECORD OF THE STRUCTURE. MUST BE REVIEWED |
| | AND APPROVED PRIOR TO INSTALLATION. FBC 106.3.5 |
| | |
| | 4) SHEET A-1 AND S-2 OF THE PLANS SPECIFY IMPACT |
| | WINDOWS AND NO SHUTTERS. HOWEVER, THE PRODUCT APPROVALS |
| | THAT WERE SUBMITTED FOR THE STOREFRONTS ARE NOT IMPACT |
| | RATED AND PRODUCT APPROVALS FOR ACCORDION SHUTTERS WERE |
| | SUBMITTED. PLEASE CLARIFY. FBC 1609.1.2 |
| | |
| | 5) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE ACCORDION SHUTTERS. SPECIFY THE |
| | OPENING LOCATIONS OF THE SHUTTERS, THE MOUNT TYPE, |
| | SPANS, FASTENERS, FASTENER SPACING, ETC. FBC 1609.1.2 |
| | |
| | 6) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | BULLET RESISTANT WINDOWS AND PAYMENT DRAWER ASSEMBLIES. |
| | DCA RULE 9B-72 |
| | |
| | 7) ON THE PRODUCT APPROVALS FOR THE STOREFRONT WINDOWS, |
| | SPECIFY THE GLASS TYPE, MULLION TYPE AND ANCHOR TYPE BY |
| | CIRCLING THE APPROPRIATE ITEMS IN THE TABLES. THIS |
| | INFORMATION DETERMINES THE DESIGN PRESSURES FOR THE |
| | ASSEMBLIES. FBC 1604.9 |
| | |
| | 8) ON THE PRODUCT APPROVALS FOR THE STOREFRONT DOOR |
| | SPECIFY THE HINGE OPTION AND IF REINFORCED OR NOT. THIS |
| | INFORMATION DETERMINES DESIGN PRESSURES FOR THE |
| | ASSEMBLY. FBC 1604.9 |
| | |
| | 9) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | ROOFING MATERIALS AND THE WALL MOUNTED LOUVER VENTS FOR |
| | ATTIC VENTILATION. DCA RULE 9B-72 |
| | |