Plan Review Notes
Plan Review Notes For Permit 06101156
Permit Number 06101156
Review Stop P
Sequence Number 4
Notes
Date Text
2009-05-29 13:52:26DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 PLUMBING
 FBC-2007 FUEL GAS
 FBC-2007 BUILDING
 FBC-2007 CHAPTER 1 (ADMIN)
 FBC-2007 CHAPTER 11
  
  
 1. SHT SP-1 CODE REFERENCE SHALL INCLUDE THE 2009
 SUPPLEMENTS. SECTION 106.1.1.
  
 2. SHT A-2 THE FILTERS REFERENCED SHALL MEET THE
 REQUIREMENTS OF NSF-42. PLEASE SUBMIT MANUF.
 SPECIFICATIONS FOR THE FILTERS. SECTIONS 106.1.2 &
 611.1.
  
 3. SHT A-2 ROOM FINISH SCHEDULE FOR THE TOILET ROOM
 INDICATES PANTED WALLS. WALLS WITHIN 2 FEET OF THE
 WATER CLOSET SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE. PAINTED SURFACES DOES NOT MEET THE "HARD"
 REQUIREMENT. SECTION 1210.2.
  
 4. SHT A-2 TOILET ROOM ELEVATIONS. PLEASE INCLUDE THE
 REQUIRMENT FOR SECTION 11-4.16.5 FLUSH CONTROLS.
  
 5. SHT A-4 GUTTER FOR FLAT ROOF, (TOTAL AREA WITH
 VERTICAL WALL CONTRIBUTION 1102 FS), REQUIRES A 7INCH
 GUTTER AT .5 % SLOPE OR 6 INCH AT 1& SLOPE. TABLE
 1106.6. PLEASE INDICATE SLOPE REQUIRED ON GUTTER OR
 INDICATE 7 INCH GUTTER.
  
 6. SHT A-4 GUTTERS SHALL BE SIZED BY TABLE 1106.6. ROOF
 PLAN NOTES #5 INDICATES 1106.7. THIS IS FOR OVERFLOW
 SCUPPERS. PLEASE UPDATE TABLE REFERENCE FOR GUTTERS.
  
 7. SHT P-2 SANITARY ISOMETRIC RISER DIAGRAM. MINIMUM 4"
 PIPE IS REQUIRED UPSTREAM OF THE 1ST HAND SINK, (BY THE
 KITCHEN). THE FIXTURE UNIT COUNT IS 41 FU AT THAT
 POINT. TABLE 710.1(1).
  
 8 THE FOLLOWING INFORMATION IS REQUIRED FOR THE
 SEPARAGE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007
 FUEL GAS CODE. -- THE SECTION FROM THE WALL TO THE
 METER IS NOT INDICATED.
  
 B. TYPE OF GAS, (LP OR NATURAL). -- NOT INDICATED ON
 PLANS. SITE PLANS SHOWS A 1000 GAL PROPANE TANK BUT
 NOTE ON SHT P-2 INDICATES TABLE 402.4(2) WHICH IS A
 NATURAL GAS TABLE. PLEASE CLARIFY.
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). -- TO BE VERIFIED WHEN
 COMMENT 8(A) IS ADDRESSED.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  