| 2009-05-29 13:52:26 | DENIED |
| | REFERENCE: |
| | FBC-2007 W/2009 SUPPLEMENTS |
| | FBC-2007 PLUMBING |
| | FBC-2007 FUEL GAS |
| | FBC-2007 BUILDING |
| | FBC-2007 CHAPTER 1 (ADMIN) |
| | FBC-2007 CHAPTER 11 |
| | |
| | |
| | 1. SHT SP-1 CODE REFERENCE SHALL INCLUDE THE 2009 |
| | SUPPLEMENTS. SECTION 106.1.1. |
| | |
| | 2. SHT A-2 THE FILTERS REFERENCED SHALL MEET THE |
| | REQUIREMENTS OF NSF-42. PLEASE SUBMIT MANUF. |
| | SPECIFICATIONS FOR THE FILTERS. SECTIONS 106.1.2 & |
| | 611.1. |
| | |
| | 3. SHT A-2 ROOM FINISH SCHEDULE FOR THE TOILET ROOM |
| | INDICATES PANTED WALLS. WALLS WITHIN 2 FEET OF THE |
| | WATER CLOSET SHALL HAVE A SMOOTH, HARD, NONABSORBENT |
| | SURFACE. PAINTED SURFACES DOES NOT MEET THE "HARD" |
| | REQUIREMENT. SECTION 1210.2. |
| | |
| | 4. SHT A-2 TOILET ROOM ELEVATIONS. PLEASE INCLUDE THE |
| | REQUIRMENT FOR SECTION 11-4.16.5 FLUSH CONTROLS. |
| | |
| | 5. SHT A-4 GUTTER FOR FLAT ROOF, (TOTAL AREA WITH |
| | VERTICAL WALL CONTRIBUTION 1102 FS), REQUIRES A 7INCH |
| | GUTTER AT .5 % SLOPE OR 6 INCH AT 1& SLOPE. TABLE |
| | 1106.6. PLEASE INDICATE SLOPE REQUIRED ON GUTTER OR |
| | INDICATE 7 INCH GUTTER. |
| | |
| | 6. SHT A-4 GUTTERS SHALL BE SIZED BY TABLE 1106.6. ROOF |
| | PLAN NOTES #5 INDICATES 1106.7. THIS IS FOR OVERFLOW |
| | SCUPPERS. PLEASE UPDATE TABLE REFERENCE FOR GUTTERS. |
| | |
| | 7. SHT P-2 SANITARY ISOMETRIC RISER DIAGRAM. MINIMUM 4" |
| | PIPE IS REQUIRED UPSTREAM OF THE 1ST HAND SINK, (BY THE |
| | KITCHEN). THE FIXTURE UNIT COUNT IS 41 FU AT THAT |
| | POINT. TABLE 710.1(1). |
| | |
| | 8 THE FOLLOWING INFORMATION IS REQUIRED FOR THE |
| | SEPARAGE GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2007 |
| | FUEL GAS CODE. -- THE SECTION FROM THE WALL TO THE |
| | METER IS NOT INDICATED. |
| | |
| | B. TYPE OF GAS, (LP OR NATURAL). -- NOT INDICATED ON |
| | PLANS. SITE PLANS SHOWS A 1000 GAL PROPANE TANK BUT |
| | NOTE ON SHT P-2 INDICATES TABLE 402.4(2) WHICH IS A |
| | NATURAL GAS TABLE. PLEASE CLARIFY. |
| | |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2007 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). -- TO BE VERIFIED WHEN |
| | COMMENT 8(A) IS ADDRESSED. |
| | |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2007 FUEL GAS CODE SEC 402.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |