2009-05-29 08:28:49**DENIED 4TH REVIEW **
  
  
  
 ** THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION
 WHICH WAS ONLY MADE ON MAY 13, 2009
  
 ** PLANS ARE ALSO UNDER A COMPLETELY NEW DESIGN TEAM.
 ** SOME COMMENTS FROM PREVIOUS REVIEWS ALONG NOW WITH
 SOME NEW COMMENTS BASED ON NEW PLANS AND DOCUMENTS
 SUBMITTED.
 PLEASE SEE NOTES BELOW.
  
 1) NOTE: PLANS SUBMITTED AFTER MARCH 1ST, 2009 SHALL BE
 UNDER NEW CODES. PLANS STATE THE NEW 2007 FBC HOWEVER
 SOME REFERENCE 2008 GLITCHES AND SOME AREAS REFERENCE
 20007 GLITCHES. BASED ON THE ADOPTED CODES AND GLITCHES
 AS OF MARCH 1ST, 2009 THE CODE IS AS FOLLOWS.
 2007 FBC WITH 2009 GLITCHES.
 2005 NFPA-70 (ALREADY DONE)
 2006 NFPA-101
 2006 NFPA-1
  
 2) NOTE: PLEASE BE SURE THE SUBMITTED ENERGY
 CALCULATIONS COORDINATES WITH THE SUBMITTED PLANS.
 PREVIOUS REVIEWS STATED COMMENTS TO OTHER DESIGN TEAMS
 TO BE SURE THIS IS DONE.
 13-415.AB.5
  
 ** ONE EXAMPLE FOR METHOD *A* WHICH IS FOR *WHOLE*
 BUILDING COMPLIANCE IS THE EXTERIOR LIGHTING. THE INPUT
 DATA REPORT ONLY INCLUDES 7-32 WATT FIXTURES. HOW IS
 THIS POSSIBLE WHEN THE PLANS CLEARLY INDICATE OTHER
 FIXTURES SUCH AS CANOPY AND NEW SITE LIGHTING POLE
 LIGHTS WITH WATTAGES EXCEEDING 250W.
 PLEASE INCLUDE *ALL* FIXTURES ON PLANS AND LOCATION.
  
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE BE
 SURE TO CALL AND GO OVER WITH THIS PLANS EXAMINER.
  
 3) NOTE: PLEASE SEE 422.13 WAS STORAGE TYPE WATER
 HEATERS IN THE 2005 NEC ARE CONSIDERED CONTINUOUS LOADS
 WITH RESPECT TO LOAD CALCULATIONS FOR FEEDERS AND
 SERVICES.
 THIS WAS A REVISION FROM THE PREVIOUS 2002 CODE WHICH
 ONLY REQUIRED THE SIZING OF BRANCH CIRCUIT AND OCP TO
 BE SET AT 125%.
 PLEASE SEE COMMENTARY IN 2005 NEC HANDBOOK.
 ANY QUESTIONS PLEASE CALL.
  
 4) NOTE: PLEASE INDICATE LOADS FOR SHOW WINDOW
 RECEPTACLES PER 220.14G FOR BRANCH CIRCUIT SIZING AND
 220.43A FOR LOAD WHICH IS REQUIRED TO BE USED FOR
 SIZING SERVICE.
  
 5) NOTE: PLEASE SEE 600.5 WHICH REQUIRES THE SIGN
 CIRCUIT TO BE DEDICATED. THIS CIRCUIT IS NOT PERMITTED
 TO HAVE ANY OTHER ITEMS SUCH AS SOFFITS LIGHTS ETC ON
 THE SAME CIRCUIT.
 THE MINIMUM VA TO BE FIGURED FOR SIZING OF THIS CIRCUIT
 SHALL BE 1200VA. PLEASE ADJUST PLANS AND CALCULATIONS.
  
 6) NOTE: RISER SHOWS AN *EQUIPMENT GROUNDING CONDUCTOR*
 BEFORE THE FIRST MEANS OF DISCONNECT WHICH IS NOT
 PERMITTED. PLEASE SEE 250.6, 250.24. THE CODE REQUIRES
 THE NEUTRAL TO BE BONDED AT THE FIRST MEANS OF
 DISCONNECT. IF THERE IS AN EQUIPMENT GROUNDING
 CONDUCTOR INSTALLED FROM THE METER TO THIS FIRST MEANS
 OF DISCONNECT THEN THIS WOULD PARALLEL THE NEUTRAL THUS
 CREATING OBJECTIONABLE CURRENTS.
  
 7) NOTE: PLEASE COMPLETE CIRCUITS ON PLANS. ONE EXAMPLE
 IS EQUIPMENT IDENTIFIED AS SOUP COUNTER. IS THIS
 EQUIPMENT? OR IS THE SOUP WARMER THE ONLY APPLIANCE?
 PLEASE ALSO SEE TOILET HAND DRYER WHICH INDICATES
 CIRCUITS *B 19-20*. THIS PLACES CONDUCTORS ON THE SAME
 PHASE WHICH WILL NOT WORK.
 PER THE PANEL SCHEDULE THIS SHOULD BE 19-21.
 PLEASE BE SURE TO COORDINATE ALL.
 408.4, 310.16 ETC
 FBC 106.1.1, 106.5
  
 8) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE PROPOSED MANUAL TRANSFER SWITCH AS
 STATED ON PLANS. 701.7, 110.3, 90.7
  
 9) NOTE: PLEASE SEE 210.8B4 AS *ALL* OUTSIDE
 RECEPTACLES UNDER THE CHANGES IN THE 2005 NEC SHALL BE
 GFI PROTECTED. THIS INCLUDES ANY DEDICATED CIRCUITS FOR
 ITEMS SUCH AS ICE MACHINES ETC.
  
 10) NOTE: PLEASE INDICATE THE TYPE OF TIME CLOCK TO
 MEET 13-415.AB.1.4. THIS MUST BE ASTRONOMICAL WITH A
 MINIMUM OF 10HR PROGRAMMING BACK UP.
  
 11) NOTE: PLEASE SHOW ALL CLASS AND DIVISION LOCATIONS
 PER NEC 500,514.3.(B)(1) PLEASE ALSO SEE (2) UNDER SAME
 SECTION FOR ANY PROPOSED NG, OR LP.
  
 12) NOTE: PLEASE SEE 514.11 (A)(B)(C) ETC.
  
 13) NOTE: PLEASE INCLUDE ALL WIRING AND DETAILS FOR THE
 REST OF NEC 514. 514.4,514.7,514.9,514.16.
  
 14) NOTE: PLEASE SEE 225.31- 225.39 FOR DISCONNECTING
 MEANS FOR SEPARATE STRUCTURES.
  
  
 15) NOTE: PLEASE VERIFY SERVICE RISER. SERVICE IS SHOWN
 AS 600AMPS WITH A *600* AMP METER CAN. IS THIS NOT A CT
 TYPE OF INSTALLATION ? PLEASE CHECK WITH FPL AND
 MANUFACTURE. SEE FPL SERVICE STANDARDS.
  
 16) NOTE: PLEASE COORDINATE PLANS. THE PLANS SHOW AND
 NOTE THE SERVICE TO BE AN OVERHEAD TYPE YET RISER SHOWS
 THIS AS UNDERGROUND. WHICH ONE WILL IT BE?
 REVIEW CAN NOT BE DONE ON AN OVERHEAD SERVICE AS IT IS
 NOT SHOWN ON RISER.
 230,310.16 ETC
 FBC 106.1.2 FOR ADDITIONAL INFORMATION AND CLARITY OF
 PLANS.
  
  
  
  
  
  
 * IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  