| 2009-05-29 08:28:49 | **DENIED 4TH REVIEW ** |
| | |
| | |
| | |
| | ** THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION |
| | WHICH WAS ONLY MADE ON MAY 13, 2009 |
| | |
| | ** PLANS ARE ALSO UNDER A COMPLETELY NEW DESIGN TEAM. |
| | ** SOME COMMENTS FROM PREVIOUS REVIEWS ALONG NOW WITH |
| | SOME NEW COMMENTS BASED ON NEW PLANS AND DOCUMENTS |
| | SUBMITTED. |
| | PLEASE SEE NOTES BELOW. |
| | |
| | 1) NOTE: PLANS SUBMITTED AFTER MARCH 1ST, 2009 SHALL BE |
| | UNDER NEW CODES. PLANS STATE THE NEW 2007 FBC HOWEVER |
| | SOME REFERENCE 2008 GLITCHES AND SOME AREAS REFERENCE |
| | 20007 GLITCHES. BASED ON THE ADOPTED CODES AND GLITCHES |
| | AS OF MARCH 1ST, 2009 THE CODE IS AS FOLLOWS. |
| | 2007 FBC WITH 2009 GLITCHES. |
| | 2005 NFPA-70 (ALREADY DONE) |
| | 2006 NFPA-101 |
| | 2006 NFPA-1 |
| | |
| | 2) NOTE: PLEASE BE SURE THE SUBMITTED ENERGY |
| | CALCULATIONS COORDINATES WITH THE SUBMITTED PLANS. |
| | PREVIOUS REVIEWS STATED COMMENTS TO OTHER DESIGN TEAMS |
| | TO BE SURE THIS IS DONE. |
| | 13-415.AB.5 |
| | |
| | ** ONE EXAMPLE FOR METHOD *A* WHICH IS FOR *WHOLE* |
| | BUILDING COMPLIANCE IS THE EXTERIOR LIGHTING. THE INPUT |
| | DATA REPORT ONLY INCLUDES 7-32 WATT FIXTURES. HOW IS |
| | THIS POSSIBLE WHEN THE PLANS CLEARLY INDICATE OTHER |
| | FIXTURES SUCH AS CANOPY AND NEW SITE LIGHTING POLE |
| | LIGHTS WITH WATTAGES EXCEEDING 250W. |
| | PLEASE INCLUDE *ALL* FIXTURES ON PLANS AND LOCATION. |
| | |
| | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE BE |
| | SURE TO CALL AND GO OVER WITH THIS PLANS EXAMINER. |
| | |
| | 3) NOTE: PLEASE SEE 422.13 WAS STORAGE TYPE WATER |
| | HEATERS IN THE 2005 NEC ARE CONSIDERED CONTINUOUS LOADS |
| | WITH RESPECT TO LOAD CALCULATIONS FOR FEEDERS AND |
| | SERVICES. |
| | THIS WAS A REVISION FROM THE PREVIOUS 2002 CODE WHICH |
| | ONLY REQUIRED THE SIZING OF BRANCH CIRCUIT AND OCP TO |
| | BE SET AT 125%. |
| | PLEASE SEE COMMENTARY IN 2005 NEC HANDBOOK. |
| | ANY QUESTIONS PLEASE CALL. |
| | |
| | 4) NOTE: PLEASE INDICATE LOADS FOR SHOW WINDOW |
| | RECEPTACLES PER 220.14G FOR BRANCH CIRCUIT SIZING AND |
| | 220.43A FOR LOAD WHICH IS REQUIRED TO BE USED FOR |
| | SIZING SERVICE. |
| | |
| | 5) NOTE: PLEASE SEE 600.5 WHICH REQUIRES THE SIGN |
| | CIRCUIT TO BE DEDICATED. THIS CIRCUIT IS NOT PERMITTED |
| | TO HAVE ANY OTHER ITEMS SUCH AS SOFFITS LIGHTS ETC ON |
| | THE SAME CIRCUIT. |
| | THE MINIMUM VA TO BE FIGURED FOR SIZING OF THIS CIRCUIT |
| | SHALL BE 1200VA. PLEASE ADJUST PLANS AND CALCULATIONS. |
| | |
| | 6) NOTE: RISER SHOWS AN *EQUIPMENT GROUNDING CONDUCTOR* |
| | BEFORE THE FIRST MEANS OF DISCONNECT WHICH IS NOT |
| | PERMITTED. PLEASE SEE 250.6, 250.24. THE CODE REQUIRES |
| | THE NEUTRAL TO BE BONDED AT THE FIRST MEANS OF |
| | DISCONNECT. IF THERE IS AN EQUIPMENT GROUNDING |
| | CONDUCTOR INSTALLED FROM THE METER TO THIS FIRST MEANS |
| | OF DISCONNECT THEN THIS WOULD PARALLEL THE NEUTRAL THUS |
| | CREATING OBJECTIONABLE CURRENTS. |
| | |
| | 7) NOTE: PLEASE COMPLETE CIRCUITS ON PLANS. ONE EXAMPLE |
| | IS EQUIPMENT IDENTIFIED AS SOUP COUNTER. IS THIS |
| | EQUIPMENT? OR IS THE SOUP WARMER THE ONLY APPLIANCE? |
| | PLEASE ALSO SEE TOILET HAND DRYER WHICH INDICATES |
| | CIRCUITS *B 19-20*. THIS PLACES CONDUCTORS ON THE SAME |
| | PHASE WHICH WILL NOT WORK. |
| | PER THE PANEL SCHEDULE THIS SHOULD BE 19-21. |
| | PLEASE BE SURE TO COORDINATE ALL. |
| | 408.4, 310.16 ETC |
| | FBC 106.1.1, 106.5 |
| | |
| | 8) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE PROPOSED MANUAL TRANSFER SWITCH AS |
| | STATED ON PLANS. 701.7, 110.3, 90.7 |
| | |
| | 9) NOTE: PLEASE SEE 210.8B4 AS *ALL* OUTSIDE |
| | RECEPTACLES UNDER THE CHANGES IN THE 2005 NEC SHALL BE |
| | GFI PROTECTED. THIS INCLUDES ANY DEDICATED CIRCUITS FOR |
| | ITEMS SUCH AS ICE MACHINES ETC. |
| | |
| | 10) NOTE: PLEASE INDICATE THE TYPE OF TIME CLOCK TO |
| | MEET 13-415.AB.1.4. THIS MUST BE ASTRONOMICAL WITH A |
| | MINIMUM OF 10HR PROGRAMMING BACK UP. |
| | |
| | 11) NOTE: PLEASE SHOW ALL CLASS AND DIVISION LOCATIONS |
| | PER NEC 500,514.3.(B)(1) PLEASE ALSO SEE (2) UNDER SAME |
| | SECTION FOR ANY PROPOSED NG, OR LP. |
| | |
| | 12) NOTE: PLEASE SEE 514.11 (A)(B)(C) ETC. |
| | |
| | 13) NOTE: PLEASE INCLUDE ALL WIRING AND DETAILS FOR THE |
| | REST OF NEC 514. 514.4,514.7,514.9,514.16. |
| | |
| | 14) NOTE: PLEASE SEE 225.31- 225.39 FOR DISCONNECTING |
| | MEANS FOR SEPARATE STRUCTURES. |
| | |
| | |
| | 15) NOTE: PLEASE VERIFY SERVICE RISER. SERVICE IS SHOWN |
| | AS 600AMPS WITH A *600* AMP METER CAN. IS THIS NOT A CT |
| | TYPE OF INSTALLATION ? PLEASE CHECK WITH FPL AND |
| | MANUFACTURE. SEE FPL SERVICE STANDARDS. |
| | |
| | 16) NOTE: PLEASE COORDINATE PLANS. THE PLANS SHOW AND |
| | NOTE THE SERVICE TO BE AN OVERHEAD TYPE YET RISER SHOWS |
| | THIS AS UNDERGROUND. WHICH ONE WILL IT BE? |
| | REVIEW CAN NOT BE DONE ON AN OVERHEAD SERVICE AS IT IS |
| | NOT SHOWN ON RISER. |
| | 230,310.16 ETC |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION AND CLARITY OF |
| | PLANS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | * IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |