Plan Review Notes
Plan Review Notes For Permit 06101156
Permit Number 06101156
Review Stop B
Sequence Number 4
Notes
Date Text
2009-06-02 14:54:262007 FBC W/2009 REVISIONS
 CONVENIENCE STORE WITH FUEL DISPENSING
  
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) THE CODE THAT IS CURRENTLY IN EFFECT IS THE 2007
 FLORIDA BUILDING CODE WITH 2009 SUPPLEMENT. PLEASE
 CORRECT CODE NOTE ON SHEET SP-1.
  
 3) SPECIFY THE REQUIRED SOIL BEARING CAPACITY ON THE
 PLANS. FBC 1804.1
  
 4) PLEASE UPDATE THE STANDARDS SPECIFIED ON SHEETS S-1
 AND S-2 TO THE EDITIONS SPECIFIED IN CHAPTER 35 OF THE
 2007 FBC. ASCE 7-05, ACI 318-05, ACI 315-05, TMS 402-05
 AND TMS 602-05.
  
 5) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 EXTERIOR WINDOWS, DOORS, STOREFRONTS, MULLIONS, ROOFING
 MATERIAL, TRUSS CONNECTORS, IMPACT PROTECTION PRODUCTS,
 ETC. AS REQUIRED BY FAC RULE 9B-72.
  
 6) SUBMIT TRUSS DRAWINGS AND LAYOUT SIGNED, SEALED AND
 DATED BY THE TRUSS ENGINEER AND REVIEWED AND APPROVED
 BY THE DESIGNER OF RECORD FOR THE STRUCTURE. FBC
 106.3.5* CITY AMENDMENTS. NOTE: THE UPLIFT AT HIP
 GIRDER TRUSSES MAY EXCEED 1500#.
  
 7) SPECIFY THE REQUIRED SOIL BEARING CAPACITY ON THE
 PLANS. FBC 1804.1.
  
 8) THE ROOF VENTILATION NOTE ON A-4 SITES EXCEPTION #2
 TO FBC 1203.2. THIS EXCEPTION APPLIES TO UN-VENTED
 ATTICS SUCH AS THOSE USING SPRAY FOAM INSULATION
 APPLIED TO THE UNDERSIDE OF THE ROOF DECK. THE PLANS DO
 NOT INDICATE THIS TYPE OF ATTIC. SHOW COMPLIANCE WITH
 FBC 1203.2.
  
 9) 2603.4.1.3 WALK -IN COOLERS .
 IN NONSPRINKLERED BUILDINGS, FOAM PLASTIC HAVING A
 THICKNESS THAT DOES NOT EXCEED 4 INCHES (102 MM) AND A
 MAXIMUM FLAME SPREAD INDEX OF 75 IS PERMITTED IN WALK
 -IN COOLERS OR FREEZER UNITS WHERE THE AGGREGATE FLOOR
 AREA DOES NOT EXCEED 400 SQUARE FEET (37 M 2 ) AND THE
 FOAM PLASTIC IS COVERED BY A METAL FACING NOT LESS THAN
 0.032-INCH-THICK (0.81 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL
 THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO
 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A
 THERMAL BARRIER. THE WALK-IN COOLER SHOWN ON THE PLANS
 APPEARS TO BE LARGER THAN THE 400 SQFT ALLOWED. SHOW
 HOW WALK-IN COOLER COMPLIES. PROVIDE MANUFACTURER'S
 SPECIFICATIONS AND DETAILS.
  
 10) DOOR #S 3 AND 5 DO NOT HAVE THE MANEUVERING
 CLEARANCES REQUIRED BY FBC 11-4.13.6. A MINIMUM OF 18"
 IS REQUIRED ON THE PULL SIDE AT THE LATCH OF SIDE SWING
 DOORS.
  
 11) AS NOTED ON THE PLAN A SEPARATE PERMIT WILL BE
 REQUIRED FOR THE STAND ALONE CANOPY AT GAS PUMPS.
  
 12) THE LIFE SAFETY PLAN DOES NOT INDICATE THE TRAVEL
 DISTANCE FROM INSIDE THE WALK-IN COOLER TO THE ONE
 EXIT. THIS APPEARS TO BE A TRAVEL DISTANCE IN EXCESS OF
 75 FT, WHICH WOULD REQUIRE TWO EXITS. FBC 1019.2 AND
 1015.1
  
 13) ON LS-1, THE OCCUPANT LOAD FOR THE WALK-IN COOLER
 SHOULD BE INCLUDED IN THE TABLE AS A STORAGE OCCUPANCY.
 FBC TABLE 1004.1.1 AND TABLE 508.3
  
 14) THE WEST EXTERIOR WALL THAT IS LOCATED AT 6 FT FROM
 THE PROPERTY LINE IS REQUIRED TO HAVE A ONE HOUR FIRE
 RATING PER FBC TABLE 602. THE MAXIMUM AREA OF EXTERIOR
 WALL OPENINGS IS 10 PERCENT PER TABLE 704.8. PLEASE
 NOTE THIS ON PLANS.
  
 NOTE: FOR THE NORTH OR REAR WALL WHICH IS LOCATED ON AN
 ALLEY, THE FIRE SEPARATION DISTANCE IS MEASURED FROM
 THE FACE OF THE BUILDING TO THE CENTERLINE OF THE
 ALLEY, WHICH IS 16 FEET BASED ON THE SITE PLAN. THIS
 WALL IS NOT REQUIRED TO BE FIRE RATED BY TABLE 602 AND
 FOOTNOTE I OF TABLE 704.8 ALLOWS UNLIMITED UNPROTECTED
 OPENINGS.
  
 NOTE: ADDITIONAL COMMENTS MAY RESULT WHEN THESE
 COMMENTS ARE ADDRESSED, DUE TO THE AMOUNT OF MISSING
 INFORMATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714