| Date |
Text |
| 2007-12-03 07:42:39 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | FROM PREVIOUS REVIEW: |
| | ******FROM PREVIOUS REVIEWS. |
| | |
| | 1.OK |
| | |
| | 2. SUBMIT A DETAIL FOR THE TOILET ROOM. SHOW COMPLIANCE |
| | WITH SECTIONS 11-4.16, 11-4.19, 11-4.22 AND ALL |
| | SUBSECTIONS. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | SHOW THE FOLLOWING: |
| | ____FOR W/C'S: |
| | A. OK |
| | B. OK |
| | C. OK |
| | D. 11-4.16.5 FLUSH CONTROLS |
| | ******RESPONSE NOTED, NOT ADDRESSED |
| | E. OK |
| | ____FOR LAVS: |
| | A. OK |
| | B. 11-4.19.5 FAUCETS |
| | ******RESPONSE NOTED, NOT ADDRESSED |
| | |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | |
| | 7. SHT P-1 THE GREASE PLUMBING RISER DOES NOT MEET |
| | CODE. THE 3 COMPARTMENT SINK AND THE HAND SINK ARE NOT |
| | VENTED. (MISLABELED AS LAVS). ALSO EQUIPMENT AND |
| | FIXTURES UTILIZED FOR THE STORAGE, PREPARATION AND |
| | HANDLING OF FOOD SHALL DISCHARGE THROUGH AN INDIRECT |
| | PIPE BY MEANS OF AN AIR GAP. (A FLOOR SINK WOULD BE |
| | REQUIRED). SECTIONS 802.1.1 AND 901.2.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT A RUNNING TRAP IS NOT |
| | APPROVED AND A SEPARATE FLOOR SINK IS REQUIRED FOR THE |
| | 3 COMPARTMENT SINK. (SEE RED LINE CORRECTION EXAMPLE |
| | SHOWN ON ONE SET OF PLANS). THE MOP SINK AND ICE MAKER |
| | DRAINAGE IS NOT SHOWN ON THE RISER DIAGRAM. FLOOR |
| | DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS. A |
| | FLOOR SINK OR HUB DRAIN IS REQUIRED PER SECTIONS 802.3 |
| | & 802.3.2. FLOOR SINKS SHALL BE INSTALLED UNDER THE |
| | FIXTURE SO THEY WILL NOT BECOME A TRIPPING HAZARD. |
| | |
| | 8. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES, |
| | VALVES, AND REQUIRED WATER HAMMER ARRESTORS, (ICE |
| | MACHINE). SECTIONS 106.3.5.1.3 & 604.9. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, |
| | AND PLEASE CLARIFY MARKINGS ON THE RISER DIAGRAM. |
| | |
| | 9. OK |
| | |
| | 10. SHT A-1 INDICATES GAS EQUIPMENT IN THE KITCHEN. A |
| | SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE FOLLOWING |
| | INFORMATION: |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE CORRESPONDING LENGHTS OF |
| | EACH CUT SECTION HAVE NOT BEEN SUBMITTED, PLEASE |
| | CLARIFY THE MARKINGS ON THE RISER DIAGRAM. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******NO RESPONSE, NOT INDICATED ON RISER DIAGRAM OR |
| | ADJOINING NOTES. |
| | |
| | C. OK - LP |
| | D. OK |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******NO RESPONSE, NOT ADDRESSED. |
| | |
| | F. OK |
| | |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF 2 PSI SHOW THE |
| | LOCATION OF THE REGULATORS, SUBMIT MANUF. |
| | SPECIFICATIONS FOR THE REGULATORS AND IF THE REGULATORS |
| | ARE VENTED, INDICATE THE MATERIAL OF THE VENT AND SHOW |
| | THE PIPING LOCATION. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS DO |
| | NOT SET THE DELIVERY PRESSURE. PLEASE ADDRESS COMMENT. |
| | |
| | H. OK |
| | |
| | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT MANUF. SHEETS NOT SUBMITTED. |
| | |
| | J. OK |
| | |
| | K. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE ISOMETRIC ON SHT P-1 |
| | INDICATES AN ABOVE GROUND TANK, AND THE SITE PLAN AS |
| | WELL AS THE CIVIL SHEETS INDICATE AN UNDERGROUND TANK. |
| | PLEASE CORRELATE. |
| | |
| | L. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE UNION IS NOT SHOWN, AND |
| | MANUF. SPECIFICATION SHEETS ARE REQUIRED FOR THE ANSUL |
| | VALVE SHOWING THAT THE VALVE IS LISTED FOR OUTSIDE |
| | USE. |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. PLEASE SEE ELECTRICAL COMMENTS #3 & #4 CONCERNING |
| | TITLE BLOCKS, SEALS, PRINTED NAMES REQUIRE BY THE |
| | FLORIDA ADMINISTRATIVE CODE AND THE FLORIDA STATUTES. |
| | ******NO RESPONSE, AND THE SP-1 SHEET IS NOT SIGNED, |
| | SEALED, OR DATED. SHT LS-1 SEAL IS NOT APPROVED. PER |
| | FAC 61G1-16.002 & FS 481.306. SHTS LS-1 & LS-2 ARE NOT |
| | SIGNED, SEALED OR DATED. |
| | |
| | *****NEW COMMENTS 3RD REVIEW***** |
| | |
| | 1C. SHT P-1 SHOWS THE CLEANOUTS AT THE GREASE LINE & |
| | SANT. LINES NEAR THE GREASE INTERCEPTOR & THE BUILDING |
| | SEWER LOCATED UNDER AN A/C COMPRESSOR & IN A WALL. |
| | CLEANOUTS SHALL BE ACCESSIBLE PER TABLE 708.9. ALSO THE |
| | A/C UNITS ARE LOCATED OVER THE TOP OF THE GREASE |
| | INTERCEPTOR WHICH ALSO REQUIRES ACCESS TO SERVICE. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 2C. SHT P-1 WATER ISOMETRIC RISER DIAGRAM DOES NOT SHOW |
| | WATER SUPPLY TO THE MOP SINK NOR TO THE ICE MAKER, |
| | (WHICH REQUIRES A WATER HAMMER ARRESTOR). PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |