Plan Review Notes
Plan Review Notes For Permit 06101156
Permit Number 06101156
Review Stop P
Sequence Number 3
Notes
Date Text
2007-12-03 07:42:39DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEWS.
  
 1.OK
  
 2. SUBMIT A DETAIL FOR THE TOILET ROOM. SHOW COMPLIANCE
 WITH SECTIONS 11-4.16, 11-4.19, 11-4.22 AND ALL
 SUBSECTIONS.
 ****NO RESPONSE, NOT ADDRESSED.
 SHOW THE FOLLOWING:
 ____FOR W/C'S:
 A. OK
 B. OK
 C. OK
 D. 11-4.16.5 FLUSH CONTROLS
 ******RESPONSE NOTED, NOT ADDRESSED
 E. OK
 ____FOR LAVS:
 A. OK
 B. 11-4.19.5 FAUCETS
 ******RESPONSE NOTED, NOT ADDRESSED
  
 3. OK
 4. OK
 5. OK
 6. OK
  
 7. SHT P-1 THE GREASE PLUMBING RISER DOES NOT MEET
 CODE. THE 3 COMPARTMENT SINK AND THE HAND SINK ARE NOT
 VENTED. (MISLABELED AS LAVS). ALSO EQUIPMENT AND
 FIXTURES UTILIZED FOR THE STORAGE, PREPARATION AND
 HANDLING OF FOOD SHALL DISCHARGE THROUGH AN INDIRECT
 PIPE BY MEANS OF AN AIR GAP. (A FLOOR SINK WOULD BE
 REQUIRED). SECTIONS 802.1.1 AND 901.2.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT A RUNNING TRAP IS NOT
 APPROVED AND A SEPARATE FLOOR SINK IS REQUIRED FOR THE
 3 COMPARTMENT SINK. (SEE RED LINE CORRECTION EXAMPLE
 SHOWN ON ONE SET OF PLANS). THE MOP SINK AND ICE MAKER
 DRAINAGE IS NOT SHOWN ON THE RISER DIAGRAM. FLOOR
 DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS. A
 FLOOR SINK OR HUB DRAIN IS REQUIRED PER SECTIONS 802.3
 & 802.3.2. FLOOR SINKS SHALL BE INSTALLED UNDER THE
 FIXTURE SO THEY WILL NOT BECOME A TRIPPING HAZARD.
  
 8. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES,
 VALVES, AND REQUIRED WATER HAMMER ARRESTORS, (ICE
 MACHINE). SECTIONS 106.3.5.1.3 & 604.9.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN,
 AND PLEASE CLARIFY MARKINGS ON THE RISER DIAGRAM.
  
 9. OK
  
 10. SHT A-1 INDICATES GAS EQUIPMENT IN THE KITCHEN. A
 SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE FOLLOWING
 INFORMATION:
 ****NO RESPONSE, NOT ADDRESSED.
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE CORRESPONDING LENGHTS OF
 EACH CUT SECTION HAVE NOT BEEN SUBMITTED, PLEASE
 CLARIFY THE MARKINGS ON THE RISER DIAGRAM.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ****NO RESPONSE, NOT ADDRESSED.
 ******NO RESPONSE, NOT INDICATED ON RISER DIAGRAM OR
 ADJOINING NOTES.
  
 C. OK - LP
 D. OK
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****NO RESPONSE, NOT ADDRESSED.
 ******NO RESPONSE, NOT ADDRESSED.
  
 F. OK
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF 2 PSI SHOW THE
 LOCATION OF THE REGULATORS, SUBMIT MANUF.
 SPECIFICATIONS FOR THE REGULATORS AND IF THE REGULATORS
 ARE VENTED, INDICATE THE MATERIAL OF THE VENT AND SHOW
 THE PIPING LOCATION.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS DO
 NOT SET THE DELIVERY PRESSURE. PLEASE ADDRESS COMMENT.
  
 H. OK
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT MANUF. SHEETS NOT SUBMITTED.
  
 J. OK
  
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE ISOMETRIC ON SHT P-1
 INDICATES AN ABOVE GROUND TANK, AND THE SITE PLAN AS
 WELL AS THE CIVIL SHEETS INDICATE AN UNDERGROUND TANK.
 PLEASE CORRELATE.
  
 L. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE UNION IS NOT SHOWN, AND
 MANUF. SPECIFICATION SHEETS ARE REQUIRED FOR THE ANSUL
 VALVE SHOWING THAT THE VALVE IS LISTED FOR OUTSIDE
 USE.
  
 **********NEW COMMENTS**********
  
 1B. PLEASE SEE ELECTRICAL COMMENTS #3 & #4 CONCERNING
 TITLE BLOCKS, SEALS, PRINTED NAMES REQUIRE BY THE
 FLORIDA ADMINISTRATIVE CODE AND THE FLORIDA STATUTES.
 ******NO RESPONSE, AND THE SP-1 SHEET IS NOT SIGNED,
 SEALED, OR DATED. SHT LS-1 SEAL IS NOT APPROVED. PER
 FAC 61G1-16.002 & FS 481.306. SHTS LS-1 & LS-2 ARE NOT
 SIGNED, SEALED OR DATED.
  
 *****NEW COMMENTS 3RD REVIEW*****
  
 1C. SHT P-1 SHOWS THE CLEANOUTS AT THE GREASE LINE &
 SANT. LINES NEAR THE GREASE INTERCEPTOR & THE BUILDING
 SEWER LOCATED UNDER AN A/C COMPRESSOR & IN A WALL.
 CLEANOUTS SHALL BE ACCESSIBLE PER TABLE 708.9. ALSO THE
 A/C UNITS ARE LOCATED OVER THE TOP OF THE GREASE
 INTERCEPTOR WHICH ALSO REQUIRES ACCESS TO SERVICE.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 2C. SHT P-1 WATER ISOMETRIC RISER DIAGRAM DOES NOT SHOW
 WATER SUPPLY TO THE MOP SINK NOR TO THE ICE MAKER,
 (WHICH REQUIRES A WATER HAMMER ARRESTOR). PLEASE
 CLARIFY. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved