Plan Review Notes
Plan Review Notes For Permit 06101156
Permit Number 06101156
Review Stop M
Sequence Number 3
Notes
Date Text
2007-10-23 11:50:32PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *FOR PLAN REVIEW ONLY NOT FOR PERMIT*
 *** DENIED ***
  
 1) AS NOTED IN LAST TWO REVIEWS 11-3-06 AND 4-2-07 NOTE
 #5. THE TWO AUXILIARY DRAIN LINES (EM) NEED TO
 DISCHARGE TO A CONSPICUOUS LOCATION, PER 2004 FBC/M
 307.2.3, PLEASE CORRECT. (THE BACK OF THE BUILDING IS
 NOT A CONSPICUOUS LOCATION).
  
 2) AS NOTED IN LAST TWO REVIEWS 11-3-06 AND 4-2-07 NOTE
 #6. PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.1.1. (BE ADVISED A COMPLETE REVIEW CAN NOT BE
 DONE WITHOUT THIS).
  
 3) AS NOTED IN LAST TWO REVIEWS 11-3-06 AND 4-2-07 NOTE
 #7. PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004
 FBC 13-407.1.ABC.1. (BE ADVISED A COMPLETE REVIEW CAN
 NOT BE DONE WITHOUT THIS).
  
 4) PLEASE SIZE THE RETURN AIR DUCT TO OFFICE, SEE W.P.B
 AMEND. 106.3.5.4 (10).
  
 5) PLEASE SIZE THE TWO FRESH AIR DUCTS TO THE AHU'S,
 SEE W.P.B. AMEND. 106.3.5.4 (10).
  
 6) THE A/C EQUIPMENT LISTING IS SHOWING THE TWO SAME
 SYSTEMS, BUT WITH DIFFERENT SENSIBLE, LATENT, AND TOTAL
 BTU,S PLEASE CORRECT OR EXPLAIN, SEE W.P.B. AMEND.
 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]