| Plan Review Notes For Permit 06101156 |
| Permit Number |
06101156 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-10-25 13:16:28 | ****DENIED***** | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | | | | 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE | | | PROPERTY OR VICINITY THEREOF. | | | | | | 4.THE NUMERICAL ADDRESS OF THE JOB SITE SHALL BE IN | | | THE TITLE BLOCK OF THE SUBMITTED PLAN SHEETS.NO | | | ADDRESS ON SHEET SP-1, LS-1, LS-2, LP-1, C2 & C3, AND | | | E-1 | | | | | | 8.SPECIFY ANY NEW WALL AND CEILING INTERIOR FINISH | | | CLASSIFICATION IN TERMS OFCLASS "A"CLASS "B", OR | | | CLASS "C". | | | | | | 9.PROVIDE A LIFE SAFETY PLAN SHEET TO INCLUDE ALL | | | COMMON PATHS OF TRAVEL TO THE EXIT(S) AND THE LOCATION | | | OF FIRE EXTINGUISHERS AT DISTANCES WHICH SATISFY THE | | | 75' TRAVEL DISTANCE REQUIREMENT. | | | | | | NEW COMMENT | | | | | | A.THE INSTALLATION OF THE STANDBY GENERATOR WILL | | | REQUIRE SEPARATE PLANS AND PERMIT, AND SHALL COMPLY | | | WITH NFPA 110. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|