| Date |
Text |
| 2007-10-18 15:41:22 | *** DENIED 3RD REVIEW ***** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW NOTES ARE |
| | STILL IN NEED OF ADDRESSING. THERE ARE ALSO SOME NEW |
| | COMMENTS ON SHEETS OTHER THAN THE ELECTRICAL BASED ON |
| | CHANGES TO PLANS. |
| | |
| | 1) NOTE: PLEASE SEE AS STATED IN THE TWO PREVIOUS |
| | REVIEWS. THE PLANS ARE STILL ONLY SUBMITTED FOR *PLAN |
| | REVIEW *. |
| | |
| | ** PLEASE KNOW THIS IS STILL UNDER "PLAN REVIEW" ONLY. |
| | NO APPLICATION FOR PERMIT HAS YET BEEN MADE TO DATE. |
| | PLEASE KNOW THAT EVEN ONCE PLANS ARE CODE COMPLIANT, |
| | REVIEWS WILL STILL REMAIN IN *FAILED* STATUES UNTIL |
| | PERMIT APPLICATION IS MADE AND REVIEW OF LICENSING, |
| | APPLIED VALUES ETC FOR COMPLETE SCOPE OF WORK CAN BE |
| | DONE. |
| | |
| | 2) NOTE: PLEASE SEE THE ARCHITECTURAL PLANS AND |
| | LANDSCAPE PLANS, ETC STILL NEED COORDINATION WITH ALL |
| | OTHER SHEETS AND TRADES. |
| | PLEASE SEE FOR EXAMPLE THE ELECTRICAL LIGHTING WHICH IS |
| | SHOWN ON LP DOES NOT CORRELATE WITH SITE PLANS. |
| | PLEASE SEE FOR EXAMPLE THE DETAILS OF WALKS/ACCESS ETC |
| | ON SITE PLAN DETAILS DO NOT MATCH WITH THE SITE PLAN |
| | ITSELF. PLEASE SEE COMMENTS FROM OTHER TRADES SUCH AS |
| | ZONING AS ANY CHANGES ON THESE SHEETS WILL HAVE AN |
| | AFFECT ON ELECTRICAL PLANS ALSO. |
| | PLEASE CORRELATE ELECTRICAL PLANS WITH SITE/LANDSCAPE |
| | PLANS AS THERE ARE LIGHTING FIXTURES FOR SITE ETC SHOWN |
| | ON LP WHICH ARE NO WHERE ON ELECTRICAL SHEETS. |
| | NO WIND LOAD INFORMATION, NO CIRCUITING, NO LOADS, ETC |
| | PLEASE CORRELATE ALL AND COMPLETE. |
| | FBC 106.1, 106.1.2, 106.3.5.1.2 |
| | NEC 240, 310.16, 408.4 |
| | |
| | 3) NOTE: PLEASE SEE SEVERAL OF THE LANDSCAPE SHEETS ARE |
| | NOT SIGNED, DATED OR SEALED AS REQUIRED PER FS 481.321 |
| | PLEASE ALSO SEE MISSING INFORMATION ON TITLE BLOCKS FOR |
| | PRINTED NAME AND LICENSE NUMBER FOR SAID DESIGNER. |
| | |
| | 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT FOR |
| | THE ATS AND GENERATOR AS REQUESTED ON THE PREVIOUS TWO |
| | REVIEWS. |
| | THE SUB BASE FUEL TANK SPECS ARE ALSO REQUIRED AND WILL |
| | BE REVIEWED BY OTHER |
| | 110.3, 90.7. |
| | |
| | 5) NOTE: PLEASE SUBMIT THE FUEL CONSUMPTION ON THE |
| | GENERATOR AS PREVIOUSLY REQUESTED FOR HB 7121, HB 319, |
| | AND HB 965. CAN NOT LOCATE ANYWHERE ON PLANS THAT THE |
| | ON-SITE FUEL WILL SUPPLY THE REQUIRED 72HRS OF FUEL |
| | UNDER LOAD CONSUMPTION. |
| | |
| | 6) NOTE: ONCE AGAIN THE GENERATOR IS STILL BEING SHOWN |
| | FOR 434AMPS, YET THIS CAN NOT BE CONFIRMED. THIS IS |
| | 125KW AT 208V 3-PHASE. IF THIS IS 434AMPS, HOW IS IT |
| | THAT THE GENERATOR HAS A 400AMP BREAKER? |
| | PLEASE SEE COMMENT #4 ABOVE. |
| | |
| | 7) NOTE: PLEASE SEE MISSING LIGHTING POWER |
| | DENSITIES/CALCULATIONS AS REQUIRED PER 13-415.2. |
| | PLEASE SEE EXTERIOR LIGHTING CALCULATIONS COULD STILL |
| | NOT BE LOCATED ON PLAN/ENERGY CALCULATIONS ETC. |
| | 13-415.2.ABC.1.3 |
| | ** INTERIOR IS ON PLANS AND IS OK. |
| | PLEASE SEE THAT NO ENERGY CALCULATIONS WERE SUBMITTED |
| | FOR REVIEW.? |
| | PLEASE SEE 13-415.1.AB.1.1 |
| | PLEASE SEE 13-103.1.1.1 AS THE DESIGNERS OF RECORD |
| | SHALL SIGN, DATE AND SEAL SAID ENERGY CALCULATIONS AND |
| | OTHER INFORMATION AS REQUIRED UNDER CHAPTER 13. PLEASE |
| | BE SURE TO SEE THE 2006 REVISIONS TO THE 2004 FBC AS |
| | CHANGES WERE MADE. |
| | |
| | ** PLEASE KNOW AS THERE IS SOME INFORMATION STILL NOT |
| | YET SUBMITTED FOR REVIEW, COMPLETE REVIEW CAN NOT BE |
| | DONE. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |