Plan Review Notes
Plan Review Notes For Permit 06101156
Permit Number 06101156
Review Stop B
Sequence Number 3
Notes
Date Text
2007-11-14 11:46:582004 FBC
 CONSTRUCT NEW CONVENIENCE STORE (PLAN REVIEW)
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) FBC SECTION 1603.1.2 THAT WAS SPECIFIED UNDER DESIGN
 PARAMETERS ON SHEETS A2 AND A7 IS NOT THE APPROPRIATE
 SECTION. PLEASE CORRECT. SPECIFY CHAPTER 16.
  
 6) COMPLIED.
  
 7) PROVIDESURVEY/SITE PLANS INDICATING THE LOCATION
 OF THE STRUCTURE, DISTANCE TO PROPERTY LINES, DISTANCES
 TO OTHER STRUCTURES ON THE PROPERTY FOR DETERMINING
 FIRE SEPARATION DISTANCES. SEE FBC 702, 704.8 AND TABLE
 602. THE SURVEY THAT WAS SUBMITTED DOES NOT CORRESPOND
 WITH THE SITE PLANS. THE SITE PLAN IS NOT SIGNED AND
 SEALED.
  
 8)SUBMIT ENERGY CALCULATIONS FOR THE STRUCTURE AS
 REQUIRED BY FBC 13-4.
  
 9)SUBMIT PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS,
 DOORS, STOREFRONTS, MULLIONS, ROOFING MATERIAL, IMPACT
 PROTECTION PRODUCTS, ETC.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 10)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 11) SPECIFY HOW IMPACT PROTECTION OF OPENINGS WILL BE
 PROVIDED AS REQUIRED BY FBC 1609.1.4. IF STORM PANELS
 ARE TO BE USED, SUBMIT 2 COPIES OF PRODUCT APPROVALS, A
 KEY PLAN AND INSTALLATION SCHEDULE. SPECIFY THE MOUNT
 TYPE, ANCHORS, ANCHOR SPACING, ETC.
  
 12) SUBMIT TRUSS DRAWINGS AND LAYOUT SIGNED, SEALED AND
 DATED BY THE TRUSS ENGINEER AND REVIEWED AND APPROVED
 BY THE DESIGNER OF RECORD OF THE STRUCTURE. FBC
 106.3.5* CITY AMENDMENTS. NOTE: THE UPLIFT AT HIP
 GIRDER TRUSSES MAY EXCEED 1500#.
  
 13)SPECIFY THE ANCHOR TYPE, SIZE, EMBED DEPTH AND
 SIZE OF THE HOLES FOR THE ANCHORS FOR THE STEEL COLUMN
 BASE. SPECIFY THE WELD TYPE FOR THE COLUMN TO BASE
 ATTACHMENT. PROVIDE A DETAIL SPECIFYING THE COLUMN CAP
 FOR THE STEEL COLUMNS WITH FASTENERS, WELDS, ETC.
 INDICATED. THE STEEL COLUMN THICKNESS ON A-3 IS NOT
 LEGIBLE.
  
 14) COMPLIED.
  
 15)COMPLIED.
  
 16) THE ROOF ZONE FIGURE FOR THE HIP ROOF ON A7 IS
 INCORRECT. THE OUTSIDE CORNER AREAS OF THE HIP ROOF ARE
 ZONE 3 . SEE FBC FIGURE 1609.6.2.2 W/2006 REVISIONS
 (REVISED SHEETS).
  
 17)SHOW HOW WALK-IN COOLER COMPLIES WITH 2603.4
 THERMAL BARRIER. PROVIDE MANUFACTURER'S SPECIFICATIONS
 AND DETAILS.
 EXCEPT AS PROVIDED FOR IN SECTIONS 2603.4.1 AND 2603.8
 , FOAM PLASTIC SHALL BE SEPARATED FROM THE INTERIOR OF
 A BUILDING BY AN APPROVED THERMAL BARRIER OF 0.5-INCH
 (12.7 MM) GYPSUM WALLBOARD OR EQUIVALENT THERMAL
 BARRIER MATERIAL THAT WILL LIMIT THE AVERAGE
 TEMPERATURE RISE OF THE UNEXPOSED SURFACE TO NOT MORE
 THAN 250 DEGREES F (120 DEGREES C) AFTER 15 MINUTES OF
 FIRE EXPOSURE, COMPLYING WITH THE STANDARD
 TIME-TEMPERATURE CURVE OF ASTM E 119. THE THERMAL
 BARRIER SHALL BE INSTALLED IN SUCH A MANNER THAT IT
 WILL REMAIN IN PLACE FOR 15 MINUTES BASED ON FM 4880,
 UL 1040, NFPA 286 OR UL 1715. COMBUSTIBLE CONCEALED
 SPACES SHALL COMPLY WITH SECTION 717 .
 2603.4.1 THERMAL BARRIER NOT REQUIRED.
 THE THERMAL BARRIER SPECIFIED IN SECTION 2603.4 IS NOT
 REQUIRED UNDER THE CONDITIONS SET FORTH IN SECTIONS
 2603.4.1.1 THROUGH 2603.4.1.13 .
 2603.4.1.2 COOLER AND FREEZER WALLS.
 FOAM PLASTIC INSTALLED IN A MAXIMUM THICKNESS OF 10
 INCHES (254 MM) IN COOLER AND FREEZER WALLS SHALL: 1.
 HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE
 TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS.
 2.HAVE FLASH IGNITION AND SELF-IGNITION
 TEMPERATURES OF NOT LESS THAN 600 DEGREES F AND 800
 DEGREES F (316 DEGREES C AND 427 DEGREES C),
 RESPECTIVELY.
 3.HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8
 MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT
 ANY POINT.
 4.BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM.
 WHERE THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH
 THE COOLER OR FREEZER AND THAT PART OF THE BUILDING IN
 WHICH IT IS LOCATED SHALL BE SPRINKLERED.
 WALK IN COOLERS
 2603.4.1.3 WALK -IN COOLERS .
 IN NONSPRINKLERED BUILDINGS, FOAM PLASTIC HAVING A
 THICKNESS THAT DOES NOT EXCEED 4 INCHES (102 MM) AND A
 MAXIMUM FLAME SPREAD INDEX OF 75 IS PERMITTED IN WALK
 -IN COOLERS OR FREEZER UNITS WHERE THE AGGREGATE FLOOR
 AREA DOES NOT EXCEED 400 SQUARE FEET (37 M 2 ) AND THE
 FOAM PLASTIC IS COVERED BY A METAL FACING NOT LESS THAN
 0.032-INCH-THICK (0.81 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL
 THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO
 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A
 THERMAL BARRIER.
 SHOW HOW WALK-IN COOLER COMPLIES. PROVIDE
 MANUFACTURER'S SPECIFICATIONS AND DETAILS.
  
 18) SUBMIT SITE PLANS SHOWING ACCESSIBLE PARKING,
 ACCESSIBLE ROUTE TO THE BUILDING ENTRANCE, RAMPS, CURB
 CUTS, ETC. AS REQUIRED BY FBC 11-4.1.3. THE PLAN WITH
 THIS INFORMATION IS REQUIRED TO BE SIGNED AND SEALED BY
 A FLORIDA LICENSED ARCHITECT OR ENGINEER. SEE FS 471
 AND 481.
  
 19) COMPLIED.
  
 20)COMPLIED.
  
 21) COMPLIED.
  
 22) COMPLIED.
  
 23) COMPLIED.
  
 24) COMPLIED.
  
 25) A SEPARATE PERMIT WILL BE REQUIRED FOR THE STAND
 ALONE CANOPY AT GAS PUMPS.
  
 26) COMPLIED.
  
 27) ADDITIONAL COMMENTS MAY RESULT WHEN THESE COMMENTS
 ARE ADDRESSED, DUE TO THE AMOUNT OF MISSING
 INFORMATION.
  
 28) SPECIFY THE WIDTH OF THE STRUCTURE ON THE PLANS.
 FBC 106.1* CITY AMENDMENTS
  