| 2007-11-14 11:46:58 | 2004 FBC |
| | CONSTRUCT NEW CONVENIENCE STORE (PLAN REVIEW) |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) COMPLIED. |
| | |
| | 4) COMPLIED. |
| | |
| | 5) FBC SECTION 1603.1.2 THAT WAS SPECIFIED UNDER DESIGN |
| | PARAMETERS ON SHEETS A2 AND A7 IS NOT THE APPROPRIATE |
| | SECTION. PLEASE CORRECT. SPECIFY CHAPTER 16. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) PROVIDESURVEY/SITE PLANS INDICATING THE LOCATION |
| | OF THE STRUCTURE, DISTANCE TO PROPERTY LINES, DISTANCES |
| | TO OTHER STRUCTURES ON THE PROPERTY FOR DETERMINING |
| | FIRE SEPARATION DISTANCES. SEE FBC 702, 704.8 AND TABLE |
| | 602. THE SURVEY THAT WAS SUBMITTED DOES NOT CORRESPOND |
| | WITH THE SITE PLANS. THE SITE PLAN IS NOT SIGNED AND |
| | SEALED. |
| | |
| | 8)SUBMIT ENERGY CALCULATIONS FOR THE STRUCTURE AS |
| | REQUIRED BY FBC 13-4. |
| | |
| | 9)SUBMIT PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, |
| | DOORS, STOREFRONTS, MULLIONS, ROOFING MATERIAL, IMPACT |
| | PROTECTION PRODUCTS, ETC. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. |
| | |
| | 10)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 11) SPECIFY HOW IMPACT PROTECTION OF OPENINGS WILL BE |
| | PROVIDED AS REQUIRED BY FBC 1609.1.4. IF STORM PANELS |
| | ARE TO BE USED, SUBMIT 2 COPIES OF PRODUCT APPROVALS, A |
| | KEY PLAN AND INSTALLATION SCHEDULE. SPECIFY THE MOUNT |
| | TYPE, ANCHORS, ANCHOR SPACING, ETC. |
| | |
| | 12) SUBMIT TRUSS DRAWINGS AND LAYOUT SIGNED, SEALED AND |
| | DATED BY THE TRUSS ENGINEER AND REVIEWED AND APPROVED |
| | BY THE DESIGNER OF RECORD OF THE STRUCTURE. FBC |
| | 106.3.5* CITY AMENDMENTS. NOTE: THE UPLIFT AT HIP |
| | GIRDER TRUSSES MAY EXCEED 1500#. |
| | |
| | 13)SPECIFY THE ANCHOR TYPE, SIZE, EMBED DEPTH AND |
| | SIZE OF THE HOLES FOR THE ANCHORS FOR THE STEEL COLUMN |
| | BASE. SPECIFY THE WELD TYPE FOR THE COLUMN TO BASE |
| | ATTACHMENT. PROVIDE A DETAIL SPECIFYING THE COLUMN CAP |
| | FOR THE STEEL COLUMNS WITH FASTENERS, WELDS, ETC. |
| | INDICATED. THE STEEL COLUMN THICKNESS ON A-3 IS NOT |
| | LEGIBLE. |
| | |
| | 14) COMPLIED. |
| | |
| | 15)COMPLIED. |
| | |
| | 16) THE ROOF ZONE FIGURE FOR THE HIP ROOF ON A7 IS |
| | INCORRECT. THE OUTSIDE CORNER AREAS OF THE HIP ROOF ARE |
| | ZONE 3 . SEE FBC FIGURE 1609.6.2.2 W/2006 REVISIONS |
| | (REVISED SHEETS). |
| | |
| | 17)SHOW HOW WALK-IN COOLER COMPLIES WITH 2603.4 |
| | THERMAL BARRIER. PROVIDE MANUFACTURER'S SPECIFICATIONS |
| | AND DETAILS. |
| | EXCEPT AS PROVIDED FOR IN SECTIONS 2603.4.1 AND 2603.8 |
| | , FOAM PLASTIC SHALL BE SEPARATED FROM THE INTERIOR OF |
| | A BUILDING BY AN APPROVED THERMAL BARRIER OF 0.5-INCH |
| | (12.7 MM) GYPSUM WALLBOARD OR EQUIVALENT THERMAL |
| | BARRIER MATERIAL THAT WILL LIMIT THE AVERAGE |
| | TEMPERATURE RISE OF THE UNEXPOSED SURFACE TO NOT MORE |
| | THAN 250 DEGREES F (120 DEGREES C) AFTER 15 MINUTES OF |
| | FIRE EXPOSURE, COMPLYING WITH THE STANDARD |
| | TIME-TEMPERATURE CURVE OF ASTM E 119. THE THERMAL |
| | BARRIER SHALL BE INSTALLED IN SUCH A MANNER THAT IT |
| | WILL REMAIN IN PLACE FOR 15 MINUTES BASED ON FM 4880, |
| | UL 1040, NFPA 286 OR UL 1715. COMBUSTIBLE CONCEALED |
| | SPACES SHALL COMPLY WITH SECTION 717 . |
| | 2603.4.1 THERMAL BARRIER NOT REQUIRED. |
| | THE THERMAL BARRIER SPECIFIED IN SECTION 2603.4 IS NOT |
| | REQUIRED UNDER THE CONDITIONS SET FORTH IN SECTIONS |
| | 2603.4.1.1 THROUGH 2603.4.1.13 . |
| | 2603.4.1.2 COOLER AND FREEZER WALLS. |
| | FOAM PLASTIC INSTALLED IN A MAXIMUM THICKNESS OF 10 |
| | INCHES (254 MM) IN COOLER AND FREEZER WALLS SHALL: 1. |
| | HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE |
| | TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS. |
| | 2.HAVE FLASH IGNITION AND SELF-IGNITION |
| | TEMPERATURES OF NOT LESS THAN 600 DEGREES F AND 800 |
| | DEGREES F (316 DEGREES C AND 427 DEGREES C), |
| | RESPECTIVELY. |
| | 3.HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8 |
| | MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE |
| | METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT |
| | ANY POINT. |
| | 4.BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. |
| | WHERE THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH |
| | THE COOLER OR FREEZER AND THAT PART OF THE BUILDING IN |
| | WHICH IT IS LOCATED SHALL BE SPRINKLERED. |
| | WALK IN COOLERS |
| | 2603.4.1.3 WALK -IN COOLERS . |
| | IN NONSPRINKLERED BUILDINGS, FOAM PLASTIC HAVING A |
| | THICKNESS THAT DOES NOT EXCEED 4 INCHES (102 MM) AND A |
| | MAXIMUM FLAME SPREAD INDEX OF 75 IS PERMITTED IN WALK |
| | -IN COOLERS OR FREEZER UNITS WHERE THE AGGREGATE FLOOR |
| | AREA DOES NOT EXCEED 400 SQUARE FEET (37 M 2 ) AND THE |
| | FOAM PLASTIC IS COVERED BY A METAL FACING NOT LESS THAN |
| | 0.032-INCH-THICK (0.81 MM) ALUMINUM OR |
| | CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL |
| | THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO |
| | 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A |
| | THERMAL BARRIER. |
| | SHOW HOW WALK-IN COOLER COMPLIES. PROVIDE |
| | MANUFACTURER'S SPECIFICATIONS AND DETAILS. |
| | |
| | 18) SUBMIT SITE PLANS SHOWING ACCESSIBLE PARKING, |
| | ACCESSIBLE ROUTE TO THE BUILDING ENTRANCE, RAMPS, CURB |
| | CUTS, ETC. AS REQUIRED BY FBC 11-4.1.3. THE PLAN WITH |
| | THIS INFORMATION IS REQUIRED TO BE SIGNED AND SEALED BY |
| | A FLORIDA LICENSED ARCHITECT OR ENGINEER. SEE FS 471 |
| | AND 481. |
| | |
| | 19) COMPLIED. |
| | |
| | 20)COMPLIED. |
| | |
| | 21) COMPLIED. |
| | |
| | 22) COMPLIED. |
| | |
| | 23) COMPLIED. |
| | |
| | 24) COMPLIED. |
| | |
| | 25) A SEPARATE PERMIT WILL BE REQUIRED FOR THE STAND |
| | ALONE CANOPY AT GAS PUMPS. |
| | |
| | 26) COMPLIED. |
| | |
| | 27) ADDITIONAL COMMENTS MAY RESULT WHEN THESE COMMENTS |
| | ARE ADDRESSED, DUE TO THE AMOUNT OF MISSING |
| | INFORMATION. |
| | |
| | 28) SPECIFY THE WIDTH OF THE STRUCTURE ON THE PLANS. |