Plan Review Notes
Plan Review Notes For Permit 06101156
Permit Number 06101156
Review Stop P
Sequence Number 2
Notes
Date Text
2007-04-09 17:50:33DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 FROM PREVIOUS REVIEW:
  
 1. SHT C-1 INDICATES "NEW CONVENIENCE STORE/PROPOSED
 BUILDING", BUT NOTES ON SHT A-1 INDICATE AN EXISTING
 BUILDING. PLEASE CLARIFY. SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 2. SUBMIT A DETAIL FOR THE TOILET ROOM. SHOW COMPLIANCE
 WITH SECTIONS 11-4.16, 11-4.19, 11-4.22 AND ALL
 SUBSECTIONS.
 ****NO RESPONSE, NOT ADDRESSED.
 SHOW THE FOLLOWING:
 ____FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 ____FOR LAVS:
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
 B. 11-4.19.5 FAUCETS
  
 3. A GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE CONTACT
 LYNN MASSON, ENVIRONMENTAL COMPLIANCE MANAGER, PHONE
 NUMBER (561) 822-2271, FAX (561) 822-2279, OR E-MAIL
 [email protected]. WASTE ORD. 3434.
 ****NO RESPONSE, NOT ADDRESSED.
  
 4. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED.
 PLEASE INDICATE THE LOCATION ON THE FLOOR PLAN. SUBMIT
 A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.15 AND
 ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING. SHOW DRINKING FOUNTAIN ON THE SANT. AND WATER
 RISER DIAGRAMS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 5. SHT A-1 GENERAL NOTES #1. THE CODE ADOPTED IS
 FBC-2004 NOT FBC-2001 AS INDICATED. PLEASE UPDATE YOUR
 NOTES TO REFLECT THE CODE IN EFFECT.
 ****NO RESPONSE, NOT ADDRESSED.
  
 6. SHT P-1THE SANITARY PLUMBING RISER DOES NOT MEET
 CODE. HORIZONTAL DRY VENTS ARE NOT APPROVED. SECTION
 905.3. - THE 3" VENT UPSTREAM OF THE W/C IS NOT
 REQUIRED. THE 2" VENT AT THE LAV IS SUFFICIENT. ****NO
 RESPONSE, NOT ADDRESSED.
  
 7. SHT P-1 THE GREASE PLUMBING RISER DOES NOT MEET
 CODE. THE 3 COMPARTMENT SINK AND THE HAND SINK ARE NOT
 VENTED. (MISLABELED AS LAVS). ALSO EQUIPMENT AND
 FIXTURES UTILIZED FOR THE STORAGE, PREPARATION AND
 HANDLING OF FOOD SHALL DISCHARGE THROUGH AN INDIRECT
 PIPE BY MEANS OF AN AIR GAP. (A FLOOR SINK WOULD BE
 REQUIRED). SECTIONS 802.1.1 AND 901.2.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 8. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES,
 VALVES, AND REQUIRED WATER HAMMER ARRESTORS, (ICE
 MACHINE). SECTIONS 106.3.5.1.3 & 604.9.
 ****NO RESPONSE, NOT ADDRESSED.
  
 9. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO
 THE BUILDING. SECTION 608.13.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 10. SHT A-1 INDICATES GAS EQUIPMENT IN THE KITCHEN. A
 SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE FOLLOWING
 INFORMATION:
 ****NO RESPONSE, NOT ADDRESSED.
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****NO RESPONSE, NOT ADDRESSED.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ****NO RESPONSE, NOT ADDRESSED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
 ****NO RESPONSE, NOT ADDRESSED.
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 ****NO RESPONSE, NOT ADDRESSED.
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****NO RESPONSE, NOT ADDRESSED.
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ****NO RESPONSE, NOT ADDRESSED.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF 2 PSI SHOW THE
 LOCATION OF THE REGULATORS, SUBMIT MANUF.
 SPECIFICATIONS FOR THE REGULATORS AND IF THE REGULATORS
 ARE VENTED, INDICATE THE MATERIAL OF THE VENT AND SHOW
 THE PIPING LOCATION.
 ****NO RESPONSE, NOT ADDRESSED.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 ****NO RESPONSE, NOT ADDRESSED.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 ****NO RESPONSE, NOT ADDRESSED.
  
 L. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****NO RESPONSE, NOT ADDRESSED.
  
 **********NEW COMMENTS**********
  
 1B. PLEASE SEE ELECTRICAL COMMENTS #3 & #4 CONCERNING
 TITLE BLOCKS, SEALS, PRINTED NAMES REQUIRE BY THE
 FLORIDA ADMINISTRATIVE CODE AND THE FLORIDA STATUTES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved