Plan Review Notes
Plan Review Notes For Permit 06101156
Permit Number 06101156
Review Stop M
Sequence Number 2
Notes
Date Text
2007-04-02 08:16:22*FOR PLAN REVIEW ONLY NOT FOR PERMIT*
 *** DENIED ***
  
 1) ALL OF THE FOLLOWING CORRECTIONS WERE REQUESTED IN
 THE LAST REVIEW 11-3-06 AND STILL NEED TO BE
 CORRECTED.
  
 2) NEED TO SHOW THE SIZES OF THE A/C AIR DUCTS, SUPPLY
 TRUNK LINE, RETURN TRUNK LINE, AND HALF THE SUPPLY
 BRANCH LINES, SEE YELLOW HIGH LIGHTS ON MECH. PLANS.
  
 3) NEED THE SIZE OF THE RETURN AIR GRILLS.
  
 4) PROVIDE RETURN AIR TO THE OFFICE, PER 2004 FBC/M
 601.4.
  
 5) THE TWO AUXILIARY DRAIN LINES (EM) NEED TO DISCHARGE
 TO A CONSPICUOUS LOCATION, PER 2004 FBC/M 307.2.3,
 PLEASE CORRECT.
  
 6) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.1.1.
  
 7) PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004
 FBC 13-407.1.ABC.1 .
  
 8) NEED THE JOB ADDRESS ON EACH PLAN.
  
 9) NEED TO SHOW AN EQUIPMENT LISTING ON MECHANICAL
 PLANS WITH A/C EQUIPMENT MANUFACTURES NAME,MODEL
 NUMBERS, TOTAL AND SENSIBLE BTU'S, SEER, AND ALL OTHER
 PERTINENT INFORMATION FOR THE A/C SYSTEMS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.