| Plan Review Notes For Permit 06101156 |
| Permit Number |
06101156 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-04-02 08:16:22 | *FOR PLAN REVIEW ONLY NOT FOR PERMIT* | | | *** DENIED *** | | | | | | 1) ALL OF THE FOLLOWING CORRECTIONS WERE REQUESTED IN | | | THE LAST REVIEW 11-3-06 AND STILL NEED TO BE | | | CORRECTED. | | | | | | 2) NEED TO SHOW THE SIZES OF THE A/C AIR DUCTS, SUPPLY | | | TRUNK LINE, RETURN TRUNK LINE, AND HALF THE SUPPLY | | | BRANCH LINES, SEE YELLOW HIGH LIGHTS ON MECH. PLANS. | | | | | | 3) NEED THE SIZE OF THE RETURN AIR GRILLS. | | | | | | 4) PROVIDE RETURN AIR TO THE OFFICE, PER 2004 FBC/M | | | 601.4. | | | | | | 5) THE TWO AUXILIARY DRAIN LINES (EM) NEED TO DISCHARGE | | | TO A CONSPICUOUS LOCATION, PER 2004 FBC/M 307.2.3, | | | PLEASE CORRECT. | | | | | | 6) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC | | | 13-101.1.1. | | | | | | 7) PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004 | | | FBC 13-407.1.ABC.1 . | | | | | | 8) NEED THE JOB ADDRESS ON EACH PLAN. | | | | | | 9) NEED TO SHOW AN EQUIPMENT LISTING ON MECHANICAL | | | PLANS WITH A/C EQUIPMENT MANUFACTURES NAME,MODEL | | | NUMBERS, TOTAL AND SENSIBLE BTU'S, SEER, AND ALL OTHER | | | PERTINENT INFORMATION FOR THE A/C SYSTEMS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|