Plan Review Notes For Permit 06101156
Permit Number 06101156
Review Stop G
Sequence Number 2
Notes
Date Text
2007-12-03 07:59:05DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT A-1 INDICATES GAS EQUIPMENT IN THE KITCHEN. A
 SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE FOLLOWING
 INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE CORRESPONDING LENGHTS OF
 EACH CUT SECTION HAVE NOT BEEN SUBMITTED, PLEASE
 CLARIFY THE MARKINGS ON THE RISER DIAGRAM.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ****NO RESPONSE, NOT ADDRESSED.
 ******NO RESPONSE, NOT INDICATED ON RISER DIAGRAM OR
 ADJOINING NOTES.
  
 C. OK - LP
 D. OK
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****NO RESPONSE, NOT ADDRESSED.
 ******NO RESPONSE, NOT ADDRESSED.
  
 F. OK
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF 2 PSI SHOW THE
 LOCATION OF THE REGULATORS, SUBMIT MANUF.
 SPECIFICATIONS FOR THE REGULATORS AND IF THE REGULATORS
 ARE VENTED, INDICATE THE MATERIAL OF THE VENT AND SHOW
 THE PIPING LOCATION.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS DO
 NOT SET THE DELIVERY PRESSURE. PLEASE ADDRESS COMMENT.
  
 H. OK
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT MANUF. SHEETS NOT SUBMITTED.
  
 J. OK
  
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE ISOMETRIC ON SHT P-1
 INDICATES AN ABOVE GROUND TANK, AND THE SITE PLAN AS
 WELL AS THE CIVIL SHEETS INDICATE AN UNDERGROUND TANK.
 PLEASE CORRELATE.
  
 L. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE UNION IS NOT SHOWN, AND
 MANUF. SPECIFICATION SHEETS ARE REQUIRED FOR THE ANSUL
 VALVE SHOWING THAT THE VALVE IS LISTED FOR OUTSIDE
 USE.