| 2007-12-03 07:59:05 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | 1. SHT A-1 INDICATES GAS EQUIPMENT IN THE KITCHEN. A |
| | SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE FOLLOWING |
| | INFORMATION: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE CORRESPONDING LENGHTS OF |
| | EACH CUT SECTION HAVE NOT BEEN SUBMITTED, PLEASE |
| | CLARIFY THE MARKINGS ON THE RISER DIAGRAM. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******NO RESPONSE, NOT INDICATED ON RISER DIAGRAM OR |
| | ADJOINING NOTES. |
| | |
| | C. OK - LP |
| | D. OK |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******NO RESPONSE, NOT ADDRESSED. |
| | |
| | F. OK |
| | |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF 2 PSI SHOW THE |
| | LOCATION OF THE REGULATORS, SUBMIT MANUF. |
| | SPECIFICATIONS FOR THE REGULATORS AND IF THE REGULATORS |
| | ARE VENTED, INDICATE THE MATERIAL OF THE VENT AND SHOW |
| | THE PIPING LOCATION. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS DO |
| | NOT SET THE DELIVERY PRESSURE. PLEASE ADDRESS COMMENT. |
| | |
| | H. OK |
| | |
| | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT MANUF. SHEETS NOT SUBMITTED. |
| | |
| | J. OK |
| | |
| | K. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE ISOMETRIC ON SHT P-1 |
| | INDICATES AN ABOVE GROUND TANK, AND THE SITE PLAN AS |
| | WELL AS THE CIVIL SHEETS INDICATE AN UNDERGROUND TANK. |
| | PLEASE CORRELATE. |
| | |
| | L. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE UNION IS NOT SHOWN, AND |
| | MANUF. SPECIFICATION SHEETS ARE REQUIRED FOR THE ANSUL |
| | VALVE SHOWING THAT THE VALVE IS LISTED FOR OUTSIDE |
| | USE. |