Plan Review Notes
Plan Review Notes For Permit 06101156
Permit Number 06101156
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-04-12 17:16:37****DENIED*****
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE
 PROPERTY OR VICINITY THEREOF.
  
 4.THE NUMERICAL ADDRESS OF THE JOB SITE SHALL BE IN
 THE TITLE BLOCK OF THE SUBMITTED PLAN SHEETS.
  
 5.IN ADDITION TO SHOWING WHERE THE NUMERICAL ADDRESS
 WILL BE LOCATED AS ON SHEET A-2, SHOW WHAT THOSE
 NUMBERS WILL BE.
  
 8.SPECIFY THE WALL AND CEILING INTERIOR FINISH
 CLASSIFICATION ASCLASS "A"CLASS "B", OR CLASS "C".
  
 9.PROVIDE A LIFE SAFETY PLAN SHEET TO INCLUDE ALL
 COMMON PATHS OF TRAVEL TO THE EXIT(S) AND THE LOCATION
 OF FIRE EXTINGUISHERS AT DISTANCES WHICH SATISFY THE
 75' TRAVEL DISTANCE REQUIREMENT.
  
 NEW COMMENT
  
 A.THE INSTALLATION OF THE STANDBY GENERATOR WILL
 REQUIRE SEPARATE PLANS AND PERMIT, AND SHALL COMPLY
 WITH NFPA 110.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722