| Plan Review Notes For Permit 06101156 |
| Permit Number |
06101156 |
|
| Review Stop |
ENG |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-03-30 14:26:29 | YOUR PLANS WERE REVIEWED IN REV 1 ON 11/17/06.YOU | | | PROVIDED SEAL & SIGNED PLANS, NOW, FOR REV 2. YOU DID | | | NOT PROVIDE EXPLANATIONS OF ITEMS WE LISTED IN REV 1, | | | DATED 11/17/06 | | | PLEASE PROVIDE EXPLANATIONS & INFO ON THE DRAWINGS FOR | | | EACH OF THE ITEMS WE ASKED FOR IN REV 1 DATED | | | 11/17/06. | | | ALSO, PLEASE PROVIDE DETAIL CALCULATIONS FOR WATER | | | QUALITY FOR BOTH CRITERIA EITHER 1" OR 2.5" CRITERIA | | | FOR WATER QUALITY?? WE LIKE TO SEE BOTH CRITERIA | | | CALCULATIONS, AND TAKE THE WORST CRITERIAFOR THE | | | LENGTH OF DESIGNINGEXFILTRATIONS TRENCH. IN OTHER | | | WORDS, DETAILEDCAL FORLENGTH OF EXFILTRATION TRENCH | | | ETC. | | | | | | PLEASE RESPOND EACH |
|