Plan Review Notes
Plan Review Notes For Permit 06101156
Permit Number 06101156
Review Stop E
Sequence Number 2
Notes
Date Text
2007-03-24 14:20:49 
  
 ****** UNSAT 2ND REVIEW******
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
  
 ** PLEASE KNOW THIS IS STILL UNDER "PLAN REVIEW" ONLY.
 NO APPLICATION FOR PERMIT HAS YET BEEN MADE TO DATE.
 PLEASE KNOW THAT EVEN ONCE PLANS ARE CODE COMPLIANT,
 REVIEWS WILL STILL REMAIN IN *FAILED* STATUES UNTIL
 PERMIT APPLICATION IS MADE AND REVIEW OF LICENSING,
 APPLIED VALUES ETC FOR COMPLETE SCOPE OF WORK CAN BE
 DONE.
  
 ** PLEASE SEE MANY ITEMS FROM PREVIOUS REVIEW NOTES
 WERE NOT DONE OR SUBMITTED.
 A COMPLETE REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE
 AT THIS TIME AS THESE ITEMS ARE NOT SHOWN OR
 SUBMITTED.
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW NOT
 YET MADE.
  
  
 1) NOTE: PLEASE BE SURE THE PLANS, ELECTRICAL AND
 ARCHITECTURAL CONTAIN ALL THE REQUIRED CODES RELEVANT
 TO DESIGN.
  
 PLEASE KNOW THAT DEPENDING ON PERMIT APPLICATION IS
 FINALLY MADE, THIS WILL DETERMINE THE CODES IN WHICH
 THE PLANS ARE DESIGNED UNDER.
 PLEASE SEE THE ARCHITECTURAL PLANS INDICATE THE 2001
 FBC????
 PLEASE INCLUDE THE FOLLOWING AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS ( FOR ALL TRADES)
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72( IF APPLICABLE)
 2002 NFPA-110
 2003 NFPA-30A
 2002 NFPA-37
  
 2) NOTE: PLEASE SEE THE ARCHITECTURAL PLANS AND
 LANDSCAPE PLANS ARE MISSING ALL OF THE ELECTRICAL ,
 MECHANICAL AND GENERATOR EQUIPMENT FROM PLANS SHOWING
 ALL SET BACKS AND DISTANCES FROM BUILDING, PROPERTY
 LINES ETC.
 PLEASE KNOW THAT BASED ON THE ELECTRICAL PLANS SHOWING
 SOME OF THIS AND COORDINATION WITH THE ONLY *SITE*
 LAYOUT PROVIDED ON THE LANDSCAPE PLANS, THE GENERATOR
 DOES NOT APPEAR IT CAN BE LOCATED IN THE REAR OF
 BUILDING.
 PLEASE ALSO SEE THE MINIMUM REQUIREMENTS FOR ZONING
 SETBACKS AND PERMITTED DISTANCES FROM BUILDING AND
 PROPERTY LINES.
 PLEASE SEE THE MINIMUM DISTANCES/CLEARANCES FOR THE
 GENERATOR FROM BUILDING AND PROPERTY LINE WILL PLACE
 THIS UNIT TOO CLOSE TO BUILDING AND PROPERTY. A NEW
 LOCATION MAY BE REQUIRED.
 PLEASE SEE THE MECHANICAL COMMENTS, BUILDING COMMENTS.
  
 MORE INFORMATION ON ALL WILL BE REQUIRED. PLEASE SEE
 COMMENTS FOR GENERATOR.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE THE SEAL BEING USED BY THE
 LANDSCAPE ARCHITECT IS NOT OF SUFFICIENT SIZE. PLEASE
 SEE THE FAC 61G1-16.002
 61G1-16.002 DESCRIPTION OF SEAL.
 (1) THE SEAL SHALL CONTAIN THE NAME OF ONLY ONE
 ARCHITECT OR INTERIOR DESIGNER AND THE REGISTRATION
 NUMBER; THE SEAL OF THE ARCHITECT SHALL BE CIRCULAR,
 AND THE SEAL OF THE INTERIOR DESIGNER SHALL BE
 HEXAGONAL. BOTH SEALS SHALL BE AN IMPRESSION-TYPE METAL
 SEAL, APPROXIMATELY 2" IN DIAMETER WITH TWO CIRCULAR
 LINES BETWEEN WHICH LINES SHALL APPEAR, AT THE TOP, THE
 WORDS "STATE OF FLORIDA" AND AT THE BOTTOM THE WORDS
 "REGISTERED ARCHITECT" OR "LICENSED INTERIOR DESIGNER,"
 WHICHEVER IS APPLICABLE.
 (2) ANY INDIVIDUAL WHO IS BOTH A REGISTERED ARCHITECT
 AND A LICENSED INTERIOR DESIGNER MUST USE A SEAL WHICH
 CONTAINS BOTH THE ARCHITECT AND INTERIOR DESIGN
 REGISTRATION NUMBERS, IN SUCH A MANNER:
  
 4) NOTE: PLEASE SEE THE MISSING INFORMATION ON TITLE
 BLOCKS PER 61G1-16.004. PLEASE SEE MISSING THE PRINTED
 NAME, PRINTED LICENSE NUMBER AND MISSING FIRM LICENSE
 NUMBER. (ALSO KNOWN AS THE CERTIFICATE OF AUTHORIZATION
 NUMBER.
 PLEASE SEE FS 481.219
  
 5) NOTE: PLEASE SEE MISSING LIGHTING POWER
 DENSITIES/CALCULATIONS AS REQUIRED PER 13-415.2. A NOTE
 ON PLANS WHICH MENTIONS THE DESIGN MEETS THIS SECTIONS
 DOES NOT ALLEVIATE THE REQUIRED INFORMATION TO BE SHOWN
 ON RECORD SETS OF PLANS AS REQUIRED PER THE SAME
 SECTION OF THE FBC CHAPTER 13.
 PLEASE SEE THAT NO ENERGY CALCULATIONS WERE SUBMITTED
 FOR REVIEW.?
 PLEASE SEE 13-415.1.AB.1.1
 PLEASE SEE 13-103.1.1.1 AS THE DESIGNERS OF RECORD
 SHALL SIGN, DATE AND SEAL SAID ENERGY CALCULATIONS AND
 OTHER INFORMATION AS REQUIRED UNDER CHAPTER 13. PLEASE
 BE SURE TO SEE THE 2006 REVISIONS TO THE 2004 FBC AS
 CHANGES WERE MADE.
  
 6) NOTE: PLEASE SHOW AND INCLUDE A LAYOUT ON PLANS
 SHOWING ALL CLASS AND DIVISION LOCATIONS AS REQUIRED
 PER NEC 511, 500 AND NFPA-30A.
 PLEASE PROVIDE A DETAIL FOR THE SHUNT/EM STOP DEVICE
 HOW THESE ARE BEING CONNECTED TO THE FEEDS.
 PLEASE SEE THE PANEL SCHEDULES WHICH DO NOT INDICATE
 SHUNT TRIPS REQUIRED?
  
 7) NOTE: PLEASE SEE NFPA-96 AS THE ELECTRICAL UNDER
 HOODS SHALL ALSO CONTAIN SHUNT AND DETAIL TO BE SHOWN.
 PLEASE SEE COMMENTS FROM OTHER TRADES FOR MORE
 INFORMATION ON GAS AND HOODS.
  
 8) NOTE: PLEASE SEE THE CODE SECTION REFERENCED FOR THE
 GFI PROTECTION OF THE KITCHEN OUTLETS SEEMS TO BE A
 MISPRINT.
 PLEASE SEE 210.8B3
 PLEASE ALSO SHOW ALL OF THESE CIRCUITS WHICH WILL BE
 PROTECTED. PLEASE INDICATE ON PANEL SCHEDULE OR PLANS.
 STATING THE SECTION OF THE CODE IS ONLY PART OF WHAT IS
 NEEDED.
 FBC 106.1.2
  
 9) NOTE: PLEASE SEE HB 7121, HB 319, HB965 ETC THIS IS
 HOUSE BILL 7121 WHICH WAS JUST ADOPTED INTO LAW ON JULY
 1ST, 2006. PLEASE SEE FS 252, 526.143ETC, WHICH NOW
 REQUIRES ALL FUEL STATIONS UPON BEING NEW OR
 SUBSTANTIAL REMODEL, ETC INSTALL A COMPLETE EMERGENCY
 BACK UP GENERATOR SYSTEM.PLEASE PROVIDE THE MINIMUM
 AMOUNT OF FUEL, FUEL CONSUMPTION FOR ALL LOADS. PLEASE
 SEE THAT UNDER THE FS 526.143 STATES THE MINIMUM AMOUNT
 OF TIME REQUIRED FOR OPERATIONS OF GENERATOR WHICH IS
 72HRS.
 PLEASE SUBMIT ALL REQUIRED LOCATIONS PER NEC 500.
 PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS FOR ALL
 EQUIPMENT, ATS, MTS, GEN, FUEL PRIME MOVER ETC. PLEASE
 INDICATE THE AMOUNT OF ONSITE FUEL. PLEASE SEE THE NEW
 FLORIDA STATUTES FOR THE REQUIRED TIMES AND AMOUNT OF
 ON SITE FUEL REQUIRED. PLEASE SEE HB AS NOTED. PLEASE
 SEE THE GENERATOR NOTE ON PLANS MENTIONS THE GENERATOR
 IS GOOD FOR 434 AMPS. PLEASE VERIFY HOW THIS IS
 POSSIBLE WITH A 125KW UNIT AT 3-PHASE, 120/208V? PLEASE
 ALSO SEE NOTE WHICH MENTIONS THAT THE GENERATOR
 MANUFACTURE IS TO PROVIDE CALCULATIONS WHICH WILL MEET
 THE INTENDED LOADS. PLEASE KNOW THAT THIS INFORMATION
 FOR THE MINIMUM DESIGN IS REQUIRED AT THIS TIME. PLEASE
 KNOW THIS IS AND WILL BE REQUIRED. 90.7, 110.3 ETC
 PLEASE KNOW THAT ONE THE SPECS ARE SUBMITTED THE REVIEW
 OF MANY ITEMS WILL BE ABLE TO BE DONE AT THAT TIME. **
 PLEASE SEE THAT AS THIS IS LEGALLY REQUIRED SYSTEM
 PLEASE BE SURE TO SEE ALL OF THE REQUIREMENTS UNDER
 NFPA-110, AND NEC 701.
  
 10) NOTE: PLEASE SE NOTE ON PLANS WHICH MENTIONS THAT
 THE CONTRACTOR IS REQUIRED TO THE TRANSFORMER WITH THE
 FPL SERVICE PLANNER FOR THE AVAILABLE FAULT CURRENT.
 PLEASE KNOW THAT THIS IS REQUIRED TO BE DONE AT THIS
 TIME. IT IS THE RESPONSIBILITY OF THE DESIGNER AND
 DESIGN TEAM.
 110.9
  
 11) NOTE: PLEASE KNOW THAT UNTIL THE MANUFACTURES
 SPECS/CUT SHEETS ARE SUBMITTED FOR THE SERVICE ENTRANCE
 ATS, REVIEW FOR THE CODE COMPLIANCE FOR 225.31-225.39,
 230.76, 230.79 CAN NOT BE DONE.
 701, 110.27.
  
 12) NOTE: PLEASE SEE RISER NOTES WHICH MENTIONS THE TWO
 DISCONNECTS ON THE LINE SIDE OF SUB PANELS AND ON THE
 LOAD SIDE OF THE GUTTER AS MAINS 1 OF 2 AND 2OF 2? HOW
 IS THIS POSSIBLE WHEN THE SERVICE MEANS OF DISCONNECTS
 ARE LOCATED IN THE ATS.
 OCP AT GENERATOR SHALL BE SHOWN.
 PLEASE SEE 445.13 WHICH MAY APPLY FOR THE MINIMUM
 SIZING OF THE CONDUCTORS.
 PLEASE SHOW ALL EQUIPMENT ON PLANS AT BUILDING
 INCLUDING BOTH MAINS.
 110.26
 FBC 106.1.2
  
 13) NOTE: PLEASE PROVIDE COMPLETED PLANS FOR THE SLAB
 DETAIL, ELEVATION OF THE UNIT AND SERVICE. EQUIPMENT IS
 PART OF A LEGALLY REQUIRED SYSTEM SEE LOCATIONS AND
 ELEVATIONS IN NFPA-110 CHAPTER 7
 THE LOCATION, ENCLOSURE AND GENERATOR SHALL BE
 PROTECTED FROM VANDALISM, FLOODS, ETC.
  
 14) NOTE: PLEASE SEE THAT FEES ARE OWED AS THE AMOUNT
 OF SHEETS SUBMITTED IS GREATER THAN THAT PLACED ON
 SUBMITTIAL SHEET.
  
 ** PLEASE KNOW AS THERE IS MUCH INFORMATION NOT YET
 SUBMITTED AND MANY CHANGES WHICH WILL BE REQUIRED ON
 PLANS, FURTHER COMMENTS MAY BE EXTENDED ON THE
 FOLLOWING REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-24 12:47:49IN ELEC FOR REVIEW