| 2007-03-24 14:20:49 | |
| | |
| | ****** UNSAT 2ND REVIEW****** |
| | |
| | ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| | IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE |
| | ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY |
| | THE CITY OF WEST PALM BEACH. |
| | |
| | |
| | ** PLEASE KNOW THIS IS STILL UNDER "PLAN REVIEW" ONLY. |
| | NO APPLICATION FOR PERMIT HAS YET BEEN MADE TO DATE. |
| | PLEASE KNOW THAT EVEN ONCE PLANS ARE CODE COMPLIANT, |
| | REVIEWS WILL STILL REMAIN IN *FAILED* STATUES UNTIL |
| | PERMIT APPLICATION IS MADE AND REVIEW OF LICENSING, |
| | APPLIED VALUES ETC FOR COMPLETE SCOPE OF WORK CAN BE |
| | DONE. |
| | |
| | ** PLEASE SEE MANY ITEMS FROM PREVIOUS REVIEW NOTES |
| | WERE NOT DONE OR SUBMITTED. |
| | A COMPLETE REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE |
| | AT THIS TIME AS THESE ITEMS ARE NOT SHOWN OR |
| | SUBMITTED. |
| | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW NOT |
| | YET MADE. |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE THE PLANS, ELECTRICAL AND |
| | ARCHITECTURAL CONTAIN ALL THE REQUIRED CODES RELEVANT |
| | TO DESIGN. |
| | |
| | PLEASE KNOW THAT DEPENDING ON PERMIT APPLICATION IS |
| | FINALLY MADE, THIS WILL DETERMINE THE CODES IN WHICH |
| | THE PLANS ARE DESIGNED UNDER. |
| | PLEASE SEE THE ARCHITECTURAL PLANS INDICATE THE 2001 |
| | FBC???? |
| | PLEASE INCLUDE THE FOLLOWING AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS ( FOR ALL TRADES) |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72( IF APPLICABLE) |
| | 2002 NFPA-110 |
| | 2003 NFPA-30A |
| | 2002 NFPA-37 |
| | |
| | 2) NOTE: PLEASE SEE THE ARCHITECTURAL PLANS AND |
| | LANDSCAPE PLANS ARE MISSING ALL OF THE ELECTRICAL , |
| | MECHANICAL AND GENERATOR EQUIPMENT FROM PLANS SHOWING |
| | ALL SET BACKS AND DISTANCES FROM BUILDING, PROPERTY |
| | LINES ETC. |
| | PLEASE KNOW THAT BASED ON THE ELECTRICAL PLANS SHOWING |
| | SOME OF THIS AND COORDINATION WITH THE ONLY *SITE* |
| | LAYOUT PROVIDED ON THE LANDSCAPE PLANS, THE GENERATOR |
| | DOES NOT APPEAR IT CAN BE LOCATED IN THE REAR OF |
| | BUILDING. |
| | PLEASE ALSO SEE THE MINIMUM REQUIREMENTS FOR ZONING |
| | SETBACKS AND PERMITTED DISTANCES FROM BUILDING AND |
| | PROPERTY LINES. |
| | PLEASE SEE THE MINIMUM DISTANCES/CLEARANCES FOR THE |
| | GENERATOR FROM BUILDING AND PROPERTY LINE WILL PLACE |
| | THIS UNIT TOO CLOSE TO BUILDING AND PROPERTY. A NEW |
| | LOCATION MAY BE REQUIRED. |
| | PLEASE SEE THE MECHANICAL COMMENTS, BUILDING COMMENTS. |
| | |
| | MORE INFORMATION ON ALL WILL BE REQUIRED. PLEASE SEE |
| | COMMENTS FOR GENERATOR. |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE THE SEAL BEING USED BY THE |
| | LANDSCAPE ARCHITECT IS NOT OF SUFFICIENT SIZE. PLEASE |
| | SEE THE FAC 61G1-16.002 |
| | 61G1-16.002 DESCRIPTION OF SEAL. |
| | (1) THE SEAL SHALL CONTAIN THE NAME OF ONLY ONE |
| | ARCHITECT OR INTERIOR DESIGNER AND THE REGISTRATION |
| | NUMBER; THE SEAL OF THE ARCHITECT SHALL BE CIRCULAR, |
| | AND THE SEAL OF THE INTERIOR DESIGNER SHALL BE |
| | HEXAGONAL. BOTH SEALS SHALL BE AN IMPRESSION-TYPE METAL |
| | SEAL, APPROXIMATELY 2" IN DIAMETER WITH TWO CIRCULAR |
| | LINES BETWEEN WHICH LINES SHALL APPEAR, AT THE TOP, THE |
| | WORDS "STATE OF FLORIDA" AND AT THE BOTTOM THE WORDS |
| | "REGISTERED ARCHITECT" OR "LICENSED INTERIOR DESIGNER," |
| | WHICHEVER IS APPLICABLE. |
| | (2) ANY INDIVIDUAL WHO IS BOTH A REGISTERED ARCHITECT |
| | AND A LICENSED INTERIOR DESIGNER MUST USE A SEAL WHICH |
| | CONTAINS BOTH THE ARCHITECT AND INTERIOR DESIGN |
| | REGISTRATION NUMBERS, IN SUCH A MANNER: |
| | |
| | 4) NOTE: PLEASE SEE THE MISSING INFORMATION ON TITLE |
| | BLOCKS PER 61G1-16.004. PLEASE SEE MISSING THE PRINTED |
| | NAME, PRINTED LICENSE NUMBER AND MISSING FIRM LICENSE |
| | NUMBER. (ALSO KNOWN AS THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER. |
| | PLEASE SEE FS 481.219 |
| | |
| | 5) NOTE: PLEASE SEE MISSING LIGHTING POWER |
| | DENSITIES/CALCULATIONS AS REQUIRED PER 13-415.2. A NOTE |
| | ON PLANS WHICH MENTIONS THE DESIGN MEETS THIS SECTIONS |
| | DOES NOT ALLEVIATE THE REQUIRED INFORMATION TO BE SHOWN |
| | ON RECORD SETS OF PLANS AS REQUIRED PER THE SAME |
| | SECTION OF THE FBC CHAPTER 13. |
| | PLEASE SEE THAT NO ENERGY CALCULATIONS WERE SUBMITTED |
| | FOR REVIEW.? |
| | PLEASE SEE 13-415.1.AB.1.1 |
| | PLEASE SEE 13-103.1.1.1 AS THE DESIGNERS OF RECORD |
| | SHALL SIGN, DATE AND SEAL SAID ENERGY CALCULATIONS AND |
| | OTHER INFORMATION AS REQUIRED UNDER CHAPTER 13. PLEASE |
| | BE SURE TO SEE THE 2006 REVISIONS TO THE 2004 FBC AS |
| | CHANGES WERE MADE. |
| | |
| | 6) NOTE: PLEASE SHOW AND INCLUDE A LAYOUT ON PLANS |
| | SHOWING ALL CLASS AND DIVISION LOCATIONS AS REQUIRED |
| | PER NEC 511, 500 AND NFPA-30A. |
| | PLEASE PROVIDE A DETAIL FOR THE SHUNT/EM STOP DEVICE |
| | HOW THESE ARE BEING CONNECTED TO THE FEEDS. |
| | PLEASE SEE THE PANEL SCHEDULES WHICH DO NOT INDICATE |
| | SHUNT TRIPS REQUIRED? |
| | |
| | 7) NOTE: PLEASE SEE NFPA-96 AS THE ELECTRICAL UNDER |
| | HOODS SHALL ALSO CONTAIN SHUNT AND DETAIL TO BE SHOWN. |
| | PLEASE SEE COMMENTS FROM OTHER TRADES FOR MORE |
| | INFORMATION ON GAS AND HOODS. |
| | |
| | 8) NOTE: PLEASE SEE THE CODE SECTION REFERENCED FOR THE |
| | GFI PROTECTION OF THE KITCHEN OUTLETS SEEMS TO BE A |
| | MISPRINT. |
| | PLEASE SEE 210.8B3 |
| | PLEASE ALSO SHOW ALL OF THESE CIRCUITS WHICH WILL BE |
| | PROTECTED. PLEASE INDICATE ON PANEL SCHEDULE OR PLANS. |
| | STATING THE SECTION OF THE CODE IS ONLY PART OF WHAT IS |
| | NEEDED. |
| | FBC 106.1.2 |
| | |
| | 9) NOTE: PLEASE SEE HB 7121, HB 319, HB965 ETC THIS IS |
| | HOUSE BILL 7121 WHICH WAS JUST ADOPTED INTO LAW ON JULY |
| | 1ST, 2006. PLEASE SEE FS 252, 526.143ETC, WHICH NOW |
| | REQUIRES ALL FUEL STATIONS UPON BEING NEW OR |
| | SUBSTANTIAL REMODEL, ETC INSTALL A COMPLETE EMERGENCY |
| | BACK UP GENERATOR SYSTEM.PLEASE PROVIDE THE MINIMUM |
| | AMOUNT OF FUEL, FUEL CONSUMPTION FOR ALL LOADS. PLEASE |
| | SEE THAT UNDER THE FS 526.143 STATES THE MINIMUM AMOUNT |
| | OF TIME REQUIRED FOR OPERATIONS OF GENERATOR WHICH IS |
| | 72HRS. |
| | PLEASE SUBMIT ALL REQUIRED LOCATIONS PER NEC 500. |
| | PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS FOR ALL |
| | EQUIPMENT, ATS, MTS, GEN, FUEL PRIME MOVER ETC. PLEASE |
| | INDICATE THE AMOUNT OF ONSITE FUEL. PLEASE SEE THE NEW |
| | FLORIDA STATUTES FOR THE REQUIRED TIMES AND AMOUNT OF |
| | ON SITE FUEL REQUIRED. PLEASE SEE HB AS NOTED. PLEASE |
| | SEE THE GENERATOR NOTE ON PLANS MENTIONS THE GENERATOR |
| | IS GOOD FOR 434 AMPS. PLEASE VERIFY HOW THIS IS |
| | POSSIBLE WITH A 125KW UNIT AT 3-PHASE, 120/208V? PLEASE |
| | ALSO SEE NOTE WHICH MENTIONS THAT THE GENERATOR |
| | MANUFACTURE IS TO PROVIDE CALCULATIONS WHICH WILL MEET |
| | THE INTENDED LOADS. PLEASE KNOW THAT THIS INFORMATION |
| | FOR THE MINIMUM DESIGN IS REQUIRED AT THIS TIME. PLEASE |
| | KNOW THIS IS AND WILL BE REQUIRED. 90.7, 110.3 ETC |
| | PLEASE KNOW THAT ONE THE SPECS ARE SUBMITTED THE REVIEW |
| | OF MANY ITEMS WILL BE ABLE TO BE DONE AT THAT TIME. ** |
| | PLEASE SEE THAT AS THIS IS LEGALLY REQUIRED SYSTEM |
| | PLEASE BE SURE TO SEE ALL OF THE REQUIREMENTS UNDER |
| | NFPA-110, AND NEC 701. |
| | |
| | 10) NOTE: PLEASE SE NOTE ON PLANS WHICH MENTIONS THAT |
| | THE CONTRACTOR IS REQUIRED TO THE TRANSFORMER WITH THE |
| | FPL SERVICE PLANNER FOR THE AVAILABLE FAULT CURRENT. |
| | PLEASE KNOW THAT THIS IS REQUIRED TO BE DONE AT THIS |
| | TIME. IT IS THE RESPONSIBILITY OF THE DESIGNER AND |
| | DESIGN TEAM. |
| | 110.9 |
| | |
| | 11) NOTE: PLEASE KNOW THAT UNTIL THE MANUFACTURES |
| | SPECS/CUT SHEETS ARE SUBMITTED FOR THE SERVICE ENTRANCE |
| | ATS, REVIEW FOR THE CODE COMPLIANCE FOR 225.31-225.39, |
| | 230.76, 230.79 CAN NOT BE DONE. |
| | 701, 110.27. |
| | |
| | 12) NOTE: PLEASE SEE RISER NOTES WHICH MENTIONS THE TWO |
| | DISCONNECTS ON THE LINE SIDE OF SUB PANELS AND ON THE |
| | LOAD SIDE OF THE GUTTER AS MAINS 1 OF 2 AND 2OF 2? HOW |
| | IS THIS POSSIBLE WHEN THE SERVICE MEANS OF DISCONNECTS |
| | ARE LOCATED IN THE ATS. |
| | OCP AT GENERATOR SHALL BE SHOWN. |
| | PLEASE SEE 445.13 WHICH MAY APPLY FOR THE MINIMUM |
| | SIZING OF THE CONDUCTORS. |
| | PLEASE SHOW ALL EQUIPMENT ON PLANS AT BUILDING |
| | INCLUDING BOTH MAINS. |
| | 110.26 |
| | FBC 106.1.2 |
| | |
| | 13) NOTE: PLEASE PROVIDE COMPLETED PLANS FOR THE SLAB |
| | DETAIL, ELEVATION OF THE UNIT AND SERVICE. EQUIPMENT IS |
| | PART OF A LEGALLY REQUIRED SYSTEM SEE LOCATIONS AND |
| | ELEVATIONS IN NFPA-110 CHAPTER 7 |
| | THE LOCATION, ENCLOSURE AND GENERATOR SHALL BE |
| | PROTECTED FROM VANDALISM, FLOODS, ETC. |
| | |
| | 14) NOTE: PLEASE SEE THAT FEES ARE OWED AS THE AMOUNT |
| | OF SHEETS SUBMITTED IS GREATER THAN THAT PLACED ON |
| | SUBMITTIAL SHEET. |
| | |
| | ** PLEASE KNOW AS THERE IS MUCH INFORMATION NOT YET |
| | SUBMITTED AND MANY CHANGES WHICH WILL BE REQUIRED ON |
| | PLANS, FURTHER COMMENTS MAY BE EXTENDED ON THE |
| | FOLLOWING REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-03-24 12:47:49 | IN ELEC FOR REVIEW |