Plan Review Notes
Plan Review Notes For Permit 06101156
Permit Number 06101156
Review Stop B
Sequence Number 2
Notes
Date Text
2007-03-28 14:24:55DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE CODE THAT IS CURRENTLY IN EFFECT IS THE 2004
 FLORIDA BUILDING CODE. PLEASE CORRECT GENERAL NOTE #1
 ON SHEET A-1.
  
 4) THE WRONG EDITION OF ASCE 7 IS SPECIFIED UNDER
 DESIGN PARAMETERS ON SHEETS A2 AND A7. THE EDITION
 REFERENCED BY THE 2004 FBC IS ASCE 7-02. PLEASE
 CORRECT.
  
 5) FBC SECTION 1606.1.7 THAT WAS SPECIFIED UNDER DESIGN
 PARAMETERS ON SHEETS A2 AND A7 IS NO LONGER IN THE
 CODE. PLEASE CORRECT.
  
 6) SPECIFY THE OCCUPANCY TYPE. SEE FBC 302.1.
  
 7) PROVIDESURVEY/SITE PLANS INDICATING THE LOCATION
 OF THE STRUCTURE, DISTANCE TO PROPERTY LINES, DISTANCES
 TO OTHER STRUCTURES ON THE PROPERTY FOR DETERMINING
 FIRE SEPARATION DISTANCES. SEE FBC 702, 704.8 AND TABLE
 602.
  
 8)SUBMIT ENERGY CALCULATIONS FOR THE STRUCTURE AS
 REQUIRED BY FBC 13-4.
  
 9)SUBMIT PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS,
 DOORS, STOREFRONTS, MULLIONS, ROOFING MATERIAL, IMPACT
 PROTECTION PRODUCTS, ETC.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 10)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 11) SPECIFY HOW IMPACT PROTECTION OF OPENINGS WILL BE
 PROVIDED AS REQUIRED BY FBC 1609.1.4.
  
 12) SUBMIT TRUSS DRAWINGS AND LAYOUT SIGNED, SEALED AND
 DATED BY THE TRUSS ENGINEER AND REVIEWED AND APPROVED
 BY THE DESIGNER OF RECORD OF THE STRUCTURE. FBC
 106.3.5* CITY AMENDMENTS. NOTE: THE UPLIFT AT HIP
 GIRDER TRUSSES MAY EXCEED 1500#.
  
 13) PROVIDE DIMENSIONS TO INDICATE THE LOCATIONS OF THE
 STEEL COLUMNS SHOWN IN DETAIL 2 ON A-3 ON THE
 FOUNDATION PLAN. SPECIFY THE ANCHOR TYPE, SIZE, EMBED
 DEPTH AND SIZE OF THE HOLES FOR THE ANCHORS FOR THE
 STEEL COLUMN BASE. SPECIFY THE WELD TYPE FOR THE COLUMN
 TO BASE ATTACHMENT. PROVIDE A DETAIL SPECIFYING THE
 COLUMN CAP FOR THE STEEL COLUMNS WITH FASTENERS, WELDS,
 ETC. INDICATED.
  
 14) SPECIFY THE LOCATION AND SIZE OF THE ATTIC ACCESS
 REQUIRED BY FBC 1209.2.
  
 15)WALL SECTION 1 ON A-4 SPECIFIES ASPHALT ROOF
 SHINGLES AND THE ELEVATIONS SHOW A METAL ROOF. PLEASE
 CORRECT.
  
 16) THE ROOF ZONE FIGURE FOR THE HIP ROOF ON A7 IS
 INCORRECT. THE OUTSIDE CORNER AREAS OF THE HIP ROOF ARE
 ZONE 3 . SEE FBC FIGURE 1609.6.2.2 (REVISED SHEETS).
  
 17)SHOW HOW WALK-IN COOLER COMPLIES WITH 2603.4
 THERMAL BARRIER. PROVIDE MANUFACTURER'S SPECIFICATIONS
 AND DETAILS.
 EXCEPT AS PROVIDED FOR IN SECTIONS 2603.4.1 AND 2603.8
 , FOAM PLASTIC SHALL BE SEPARATED FROM THE INTERIOR OF
 A BUILDING BY AN APPROVED THERMAL BARRIER OF 0.5-INCH
 (12.7 MM) GYPSUM WALLBOARD OR EQUIVALENT THERMAL
 BARRIER MATERIAL THAT WILL LIMIT THE AVERAGE
 TEMPERATURE RISE OF THE UNEXPOSED SURFACE TO NOT MORE
 THAN 250 DEGREES F (120 DEGREES C) AFTER 15 MINUTES OF
 FIRE EXPOSURE, COMPLYING WITH THE STANDARD
 TIME-TEMPERATURE CURVE OF ASTM E 119. THE THERMAL
 BARRIER SHALL BE INSTALLED IN SUCH A MANNER THAT IT
 WILL REMAIN IN PLACE FOR 15 MINUTES BASED ON FM 4880,
 UL 1040, NFPA 286 OR UL 1715. COMBUSTIBLE CONCEALED
 SPACES SHALL COMPLY WITH SECTION 717 .
 2603.4.1 THERMAL BARRIER NOT REQUIRED.
 THE THERMAL BARRIER SPECIFIED IN SECTION 2603.4 IS NOT
 REQUIRED UNDER THE CONDITIONS SET FORTH IN SECTIONS
 2603.4.1.1 THROUGH 2603.4.1.13 .
 2603.4.1.2 COOLER AND FREEZER WALLS.
 FOAM PLASTIC INSTALLED IN A MAXIMUM THICKNESS OF 10
 INCHES (254 MM) IN COOLER AND FREEZER WALLS SHALL: 1.
 HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE
 TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS.
 2.HAVE FLASH IGNITION AND SELF-IGNITION
 TEMPERATURES OF NOT LESS THAN 600 DEGREES F AND 800
 DEGREES F (316 DEGREES C AND 427 DEGREES C),
 RESPECTIVELY.
 3.HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8
 MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT
 ANY POINT.
 4.BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM.
 WHERE THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH
 THE COOLER OR FREEZER AND THAT PART OF THE BUILDING IN
 WHICH IT IS LOCATED SHALL BE SPRINKLERED.
 WALK IN COOLERS
 2603.4.1.3 WALK -IN COOLERS .
 IN NONSPRINKLERED BUILDINGS, FOAM PLASTIC HAVING A
 THICKNESS THAT DOES NOT EXCEED 4 INCHES (102 MM) AND A
 MAXIMUM FLAME SPREAD INDEX OF 75 IS PERMITTED IN WALK
 -IN COOLERS OR FREEZER UNITS WHERE THE AGGREGATE FLOOR
 AREA DOES NOT EXCEED 400 SQUARE FEET (37 M 2 ) AND THE
 FOAM PLASTIC IS COVERED BY A METAL FACING NOT LESS THAN
 0.032-INCH-THICK (0.81 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL
 THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO
 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A
 THERMAL BARRIER.
 SHOW HOW WALK-IN COOLER COMPLIES. PROVIDE
 MANUFACTURER'S SPECIFICATIONS AND DETAILS.
  
 18) SUBMIT SITE PLANS SHOWING ACCESSIBLE PARKING,
 ACCESSIBLE ROUTE TO THE BUILDING ENTRANCE, RAMPS, CURB
 CUTS, ETC. AS REQUIRED BY FBC 11-4.1.3.
  
 19) ALL DOORS ON THE ACCESSIBLE ROUTESARE REQUIRED TO
 HAVE ADA COMPLIANT HARDWARE. SEE FBC 11-4.13.9.
  
 20)SHOW THE REQUIRED CLEAR FLOOR SPACE AT THE WATER
 CLOSET AND LAVATORY SPECIFY DIMENSIONS. SEE FBC
 11-4.16.2 AND 11-4.19.3.
  
 21) PROVIDE AN ACCESSIBLE COUNTER AS REQUIRED BY FBC
 11-7.2.
  
 22) DOOR 03DOES NOT HAVE THEMANEUVERING CLEARANCES
 REQUIRED BY FBC 11-4.13.6. A MINIMUM OF 18" IS REQUIRED
 ON THE PULL SIDE AT THE LATCH OF SIDE SWING DOORS.
  
 23) FBC 11-4.16.3 REQUIRES THE HEIGHT OF WATER CLOSETS
 TO BE 17" TO 19" MEASURED TO TOP OF THE TOILET SEAT.
 PLEASE CORRECT DETAIL 5 ON A-4.
  
 24) FBC 11-4.16.4 REQUIRES THE GRAB BAR BEHIND THE
 WATER CLOSET TO BE 36" MINIMUM.
  
 25) A SEPARATE PERMIT WILL BE REQUIRED FOR THE STAND
 ALONE CANOPY AT GAS PUMPS.
  
 26) THE FIRM'S LICENSE NUMBER IS REQUIRED TO BE IN THE
 TITLE BLOCK ON EACH SHEET OF THE PLANS. SEE FS 481 AND
 FAC 61G1-16.004.
  
 27) ADDITIONAL COMMENTS MAY RESULT WHEN THESE COMMENTS
 ARE ADDRESSED, DUE TO THE AMOUNT OF MISSING
 INFORMATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714