| 2006-11-03 12:15:26 | *FOR PLAN REVIEW ONLY NOT FOR PERMIT* | | | *** DENIED *** | | | 1) SHOW THE LOCATION OF THE TWO A/C CONDENSER UNITS AND | | | THE ONE WALK IN COOLER CONDENSER UNIT ON THE MECHANICAL | | | PLANS. | | | | | | 2) NEED TO SHOW THE SIZES OF THE A/C AIR DUCTS, SUPPLY | | | TRUNK LINE, RETURN TRUNK LINE, AND HALF THE SUPPLY | | | BRANCH LINS, SEE HIGH LIGHTS ON MECH. PLANS. | | | | | | 3) NEED THE SIZE OF THE RETURN AIR GRILLS. | | | | | | 4) PROVIDE RETURN AIR TO THE OFFICE, PER 2004 FBC/M | | | 601.4. | | | | | | 5) THE TWO AUXILIARY DRAIN LINES (EM) NEED TO DISCHARGE | | | TO A CONSPICUOUS LOCATION, PER 2004 FBC/M 307.2.3, | | | PLEASE CORRECT. | | | | | | 6) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC | | | 13-101.1.1. | | | | | | 7) PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004 | | | FBC 13-407.1.ABC.1 . | | | | | | 8) NEED THE JOB ADDRESS ON EACH PLAN. | | | | | | 9) NEED TO ALSO SHOW THE SENSIBLE BTU'S AND CFM'S FOR | | | THE A/C SYSTEMS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|