2006-11-03 12:15:26*FOR PLAN REVIEW ONLY NOT FOR PERMIT*
 *** DENIED ***
 1) SHOW THE LOCATION OF THE TWO A/C CONDENSER UNITS AND
 THE ONE WALK IN COOLER CONDENSER UNIT ON THE MECHANICAL
 PLANS.
  
 2) NEED TO SHOW THE SIZES OF THE A/C AIR DUCTS, SUPPLY
 TRUNK LINE, RETURN TRUNK LINE, AND HALF THE SUPPLY
 BRANCH LINS, SEE HIGH LIGHTS ON MECH. PLANS.
  
 3) NEED THE SIZE OF THE RETURN AIR GRILLS.
  
 4) PROVIDE RETURN AIR TO THE OFFICE, PER 2004 FBC/M
 601.4.
  
 5) THE TWO AUXILIARY DRAIN LINES (EM) NEED TO DISCHARGE
 TO A CONSPICUOUS LOCATION, PER 2004 FBC/M 307.2.3,
 PLEASE CORRECT.
  
 6) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.1.1.
  
 7) PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004
 FBC 13-407.1.ABC.1 .
  
 8) NEED THE JOB ADDRESS ON EACH PLAN.
  
 9) NEED TO ALSO SHOW THE SENSIBLE BTU'S AND CFM'S FOR
 THE A/C SYSTEMS.
  