| 2006-12-14 12:11:15 | *****DENIED***** |
| | |
| | |
| | |
| | 1.NFPA 101 (2003 EDITION) THE FLORIDA FIRE PREVENTION |
| | CODE (2004 EDITION) SHALL BE REFERENCED. |
| | |
| | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT |
| | HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE |
| | PROPERTY OR VICINITY THEREOF. |
| | |
| | 4.THE NUMERICAL ADDRESS OF THE JOB SITE SHALL BE IN |
| | THE TITLE BLOCK OF THE SUBMITTED PLAN SHEETS. |
| | |
| | 5.IN ADDITION TO SHOWING WHERE THE NUMERICAL ADDRESS |
| | WILL BE LOCATED AS ON SHEET A-2, SHOW WHAT THOSE |
| | NUMBERS WILL BE. |
| | |
| | 6.EXIT AND EMERGENCY LIGHTS TO BE INSTALLED AND |
| | ARRANGED AS PER NFPA 101, 7.9 AND 7.10 |
| | |
| | 7.PROVIDE THE THE FOLLOWING BUILDING INFORMATION: A) |
| | CONSTRUCTION TYPEB) OCCUPANCY TYPEC) FIRE |
| | PROTECTION SYSTEM I.E. FIRE ALARM AND/ORFIRE |
| | SPRINKLERD) INTERIOR FINISH CLASSIFICATION |
| | |
| | 8.IF THE BUILDING IS UNSPRINKLERED, INTERIOR FINISH |
| | SHALL BE CLASS "A" OR CLASS "B". |
| | |
| | 9.PROVIDE A LIFE SAFETY PLAN SHEET TO INCLUDE ALL |
| | COMMON PATHS OF TRAVEL TO THE EXIT(S) AND THE LOCATION |
| | OF FIRE EXTINGUISHERS AT DISTANCES WHICH SATISFY THE |
| | 75' TRAVEL DISTANCE REQUIREMENT. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |