| Date |
Text |
| 2006-11-04 19:45:09 | *** UNSAT *** |
| | |
| | |
| | ** PLEASE KNOW THIS IS STILL UNDER "PLAN REVIEW" ONLY. |
| | NO APPLICATION FOR PERMIT HAS YET BEEN MADE TO DATE. |
| | PLEASE KNOW A CODE CHANGE FOR NFPA-70 IS COMING AND IF |
| | PERMIT IS NOT APPLIED FOR BEFORE STATE ADOPTS NEW CODE, |
| | THEN THE PLANS WILL BE REQUIRED TO CHANGE AS NEEDED. |
| | THE TENTATIVE DATE IS DEC 1ST, 2006 |
| | |
| | 1) NOTE:PLEASE SEE PLANS SEEM TO INDICATE A NEW STORE |
| | BEING CONSTRUCTED, HOWEVER THE "PLAN REVIEW" SUBMITTAL |
| | SHEET INDICATES A REMODEL??? THE SCOPE OF WORK IS |
| | UNCLEAR BASED ON PLANS SUBMITTED IN EITHER CASE. |
| | |
| | 2) NOTE: PLEASE SEE FS 471.003(2)(H)2A, AS PLANS ARE |
| | REQUIRED TO BE DONE BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER. |
| | PLEASE ALSO SEE FS 471.025(3). |
| | THE ELECTRICAL SCOPE AS SHOWN MAY NOT BE DONE BY AN |
| | ARCHITECTURAL FIRM/ARCHITECT. |
| | |
| | 3) NOTE: PLEASE KNOW THE PLANS SUBMITTED ARE NOT |
| | COMPLETE FOR CODE COMPLIANCE. PLEASE SEE ONLY SOME CODE |
| | ARTICLES BELOW ARE BEING GIVEN. PLEASEKNOW THERE IS A |
| | SUBSTANTIALLY AMOUNT OF CODE RELATED ITEMS NOT |
| | SUBMITTED OR SHOWN. |
| | |
| | A) PLEASE INDICATE AND SHOW ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH PANEL SCHEDULES TO BE SUBMITTED. |
| | 240.4,310.16, 408.4 |
| | FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF |
| | WEST PALM BEACH. 106.1.2, 106.3.5.1.2 ETC. |
| | PLEASE ALSO SEE 2002 NFPA-70, 2003 NFPA-101, 2002 |
| | NFPA-72, NFPA-30A ETC ETC. |
| | B) PLEASE SUBMIT LOAD CALCULATIONS.NEC 220. |
| | C) PLEASE SEE NEC 511 |
| | D) PLEASE SEE LS 101 7.8, 7.9 FOR MISSING EM/ EXT LTS, |
| | PLEASE ALSO SEE 700.12E FOR CIRCUITING. |
| | E) PLEASE SEE 250.6, 250.24B |
| | F) PLEASE SEE 250.110, 250.110 |
| | G) PLEASE SEE 250.50 |
| | H) PLEASE SEE 600.5, 220.3(B)(6) |
| | I) PLEASE SEE 210.62, 220.12A |
| | J) PLEASE SEE 210.8B3 |
| | K) PLEASE SEE FBC CHAPTER 13(ALL APPLICABLE SECTIONS, |
| | TOO MANY TO LIST AT THIS TIME. |
| | L) PLEASE SEE 110.9, 240.12 FOR SELECTIVE COORDINATION |
| | DETAILS TO BE SUBMITTED. |
| | ETC. |
| | |
| | 4) NOTE: PLEASE SEE HB 7121, HB 319, HB965 ETC THIS IS |
| | HOUSE BILL 7121 WHICH WAS JUST ADOPTED INTO LAW ON JULY |
| | 1ST, 2006. PLEASE SEE FS 252 ETC, WHICH NOW REQUIRES |
| | ALL FUEL STATIONS UPON BEING NEW OR SUBSTANTIAL |
| | REMODEL, ETC INSTALL A COMPLETE EMERGENCY BACK UP |
| | GENERATOR SYSTEM. THIS WILL SUBSTANTIALLY CHANGE THE |
| | PLANS SUBMITTED. |
| | PLEASE SUBMIT SITE PLANS, ALL REQUIRED LOCATIONS PER |
| | NEC 500. PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT |
| | SHEETS FOR ALL EQUIPMENT, ATS, MTS, GEN, FUEL PRIME |
| | MOVER ETC ETC. |
| | PLEASE KNOW THIS IS AND WILL BE REQUIRED. 90.7, 110.3 |
| | ETC |
| | |
| | |
| | ** PLEASE KNOW AS PLANS ARE NOT COMPLETE AT THIS TIME |
| | FOR A SUFFICIENT REVIEW, AND WILL BE CHANGING, THERE |
| | MAY BE FURTHER COMMENTS UPON THE NEXT REVIEW. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |