Plan Review Notes
Plan Review Notes For Permit 06101156
Permit Number 06101156
Review Stop E
Sequence Number 1
Notes
Date Text
2006-11-04 19:45:09*** UNSAT ***
  
  
 ** PLEASE KNOW THIS IS STILL UNDER "PLAN REVIEW" ONLY.
 NO APPLICATION FOR PERMIT HAS YET BEEN MADE TO DATE.
 PLEASE KNOW A CODE CHANGE FOR NFPA-70 IS COMING AND IF
 PERMIT IS NOT APPLIED FOR BEFORE STATE ADOPTS NEW CODE,
 THEN THE PLANS WILL BE REQUIRED TO CHANGE AS NEEDED.
 THE TENTATIVE DATE IS DEC 1ST, 2006
  
 1) NOTE:PLEASE SEE PLANS SEEM TO INDICATE A NEW STORE
 BEING CONSTRUCTED, HOWEVER THE "PLAN REVIEW" SUBMITTAL
 SHEET INDICATES A REMODEL??? THE SCOPE OF WORK IS
 UNCLEAR BASED ON PLANS SUBMITTED IN EITHER CASE.
  
 2) NOTE: PLEASE SEE FS 471.003(2)(H)2A, AS PLANS ARE
 REQUIRED TO BE DONE BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER.
 PLEASE ALSO SEE FS 471.025(3).
 THE ELECTRICAL SCOPE AS SHOWN MAY NOT BE DONE BY AN
 ARCHITECTURAL FIRM/ARCHITECT.
  
 3) NOTE: PLEASE KNOW THE PLANS SUBMITTED ARE NOT
 COMPLETE FOR CODE COMPLIANCE. PLEASE SEE ONLY SOME CODE
 ARTICLES BELOW ARE BEING GIVEN. PLEASEKNOW THERE IS A
 SUBSTANTIALLY AMOUNT OF CODE RELATED ITEMS NOT
 SUBMITTED OR SHOWN.
  
 A) PLEASE INDICATE AND SHOW ALL CIRCUITING ON PLANS AND
 CORRELATE WITH PANEL SCHEDULES TO BE SUBMITTED.
 240.4,310.16, 408.4
 FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF
 WEST PALM BEACH. 106.1.2, 106.3.5.1.2 ETC.
 PLEASE ALSO SEE 2002 NFPA-70, 2003 NFPA-101, 2002
 NFPA-72, NFPA-30A ETC ETC.
 B) PLEASE SUBMIT LOAD CALCULATIONS.NEC 220.
 C) PLEASE SEE NEC 511
 D) PLEASE SEE LS 101 7.8, 7.9 FOR MISSING EM/ EXT LTS,
 PLEASE ALSO SEE 700.12E FOR CIRCUITING.
 E) PLEASE SEE 250.6, 250.24B
 F) PLEASE SEE 250.110, 250.110
 G) PLEASE SEE 250.50
 H) PLEASE SEE 600.5, 220.3(B)(6)
 I) PLEASE SEE 210.62, 220.12A
 J) PLEASE SEE 210.8B3
 K) PLEASE SEE FBC CHAPTER 13(ALL APPLICABLE SECTIONS,
 TOO MANY TO LIST AT THIS TIME.
 L) PLEASE SEE 110.9, 240.12 FOR SELECTIVE COORDINATION
 DETAILS TO BE SUBMITTED.
 ETC.
  
 4) NOTE: PLEASE SEE HB 7121, HB 319, HB965 ETC THIS IS
 HOUSE BILL 7121 WHICH WAS JUST ADOPTED INTO LAW ON JULY
 1ST, 2006. PLEASE SEE FS 252 ETC, WHICH NOW REQUIRES
 ALL FUEL STATIONS UPON BEING NEW OR SUBSTANTIAL
 REMODEL, ETC INSTALL A COMPLETE EMERGENCY BACK UP
 GENERATOR SYSTEM. THIS WILL SUBSTANTIALLY CHANGE THE
 PLANS SUBMITTED.
 PLEASE SUBMIT SITE PLANS, ALL REQUIRED LOCATIONS PER
 NEC 500. PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT
 SHEETS FOR ALL EQUIPMENT, ATS, MTS, GEN, FUEL PRIME
 MOVER ETC ETC.
 PLEASE KNOW THIS IS AND WILL BE REQUIRED. 90.7, 110.3
 ETC
  
  
 ** PLEASE KNOW AS PLANS ARE NOT COMPLETE AT THIS TIME
 FOR A SUFFICIENT REVIEW, AND WILL BE CHANGING, THERE
 MAY BE FURTHER COMMENTS UPON THE NEXT REVIEW.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]