| Date |
Text |
| 2006-11-15 13:43:43 | DENIED BY BUILDING |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT MUST |
| | BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) THE CODE THAT IS CURRENTLY IN EFFECT IS THE 2004 |
| | FLORIDA BUILDING CODE. PLEASE CORRECT GENERAL NOTE #1 |
| | ON SHEET A-1. |
| | |
| | 4) SPECIFY THE CONSTRUCTION TYPE BASED ON THE 2004 FBC |
| | DESIGNATIONS. SPECIFY A OR B. SEE FBC TABLE 601. |
| | |
| | 5) SPECIFY THE OCCUPANCY TYPE. SEE FBC 302.1. |
| | |
| | 6) PROVIDE SURVEY/SITE PLANS INDICATING THE LOCATION OF |
| | THE STRUCTURE, DISTANCE TO PROPERTY LINES, DISTANCES TO |
| | OTHER STRUCTURES ON THE PROPERTY FOR DETERMINING FIRE |
| | SEPARATION DISTANCES. SEE FBC 702, 704.8 AND TABLE 602. |
| | |
| | 7) PLEASE CLARIFY THE SCOPE OF WORK. THE APPLICATION |
| | INDICATES THAT THIS IS A REMODEL OF AN EXISTING |
| | BUILDING AND THE PLANS APPEAR TO BE FOR NEW |
| | CONSTRUCTION. |
| | |
| | 8) IF THIS IS A REMODEL, SUBMIT A DEMO PLAN FOR THE |
| | EXISTING STRUCTURE. |
| | |
| | 9) IF REMODEL, SPECIFY THE LEVEL OF ALTERATION FOR THE |
| | WORK AS SPECIFIED IN THE 2004 FBC EXISTING BUILDING |
| | CODE. |
| | |
| | 10) SUBMIT ENERGY CALCULATIONS FOR THE STRUCTURE AS |
| | REQUIRED BY FBC 13-4. |
| | |
| | 11) SPECIFY THE DESIGN DATA FOR THE STRUCTURE REQUIRED |
| | BY FBC 1603.1.4. |
| | |
| | 12) SUBMIT PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, |
| | DOORS, STOREFRONTS, MULLIONS, ROOFING MATERIAL, IMPACT |
| | PROTECTION PRODUCTS, ETC. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. |
| | |
| | 13) WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 14) SPECIFY HOW IMPACT PROTECTION OF OPENINGS WILL BE |
| | PROVIDED AS REQUIRED BY FBC 1609.1.4. |
| | |
| | 15) SUBMIT TRUSS DRAWINGS AND LAYOUT SIGNED, SEALED AND |
| | DATED BY THE TRUSS ENGINEER AND REVIEWED AND APPROVED |
| | BY THE DESIGNER OF RECORD OF THE STRUCTURE. FBC |
| | 106.3.5* CITY AMENDMENTS. NOTE: THE UPLIFT AT HIP |
| | GIRDER TRUSSES MAY EXCEED 1500#. |
| | |
| | 16) INDICATE WHERE ON THE FOUNDATION PLAN THE STEEL |
| | COLUMN IN DETAIL 2 ON A-3 IS LOCATED. |
| | |
| | 17) SPECIFY THE LOCATION AND SIZE OF THE ATTIC ACCESS |
| | REQUIRED BY FBC 1209.2. |
| | |
| | 18) WALL SECTION 1 ON A-4 SPECIFIES ASPHALT ROOF |
| | SHINGLES AND THE ELEVATIONS SHOW A METAL ROOF. PLEASE |
| | CORRECT. |
| | |
| | 19) 2603.4 THERMAL BARRIER. |
| | EXCEPT AS PROVIDED FOR IN SECTIONS 2603.4.1 AND 2603.8 |
| | , FOAM PLASTIC SHALL BE SEPARATED FROM THE INTERIOR OF |
| | A BUILDING BY AN APPROVED THERMAL BARRIER OF 0.5-INCH |
| | (12.7 MM) GYPSUM WALLBOARD OR EQUIVALENT THERMAL |
| | BARRIER MATERIAL THAT WILL LIMIT THE AVERAGE |
| | TEMPERATURE RISE OF THE UNEXPOSED SURFACE TO NOT MORE |
| | THAN 250?F (120?C) AFTER 15 MINUTES OF FIRE EXPOSURE, |
| | COMPLYING WITH THE STANDARD TIME-TEMPERATURE CURVE OF |
| | ASTM E 119. THE THERMAL BARRIER SHALL BE INSTALLED IN |
| | SUCH A MANNER THAT IT WILL REMAIN IN PLACE FOR 15 |
| | MINUTES BASED ON FM 4880, UL 1040, NFPA 286 OR UL 1715. |
| | COMBUSTIBLE CONCEALED SPACES SHALL COMPLY WITH SECTION |
| | 717 . |
| | 2603.4.1 THERMAL BARRIER NOT REQUIRED. |
| | THE THERMAL BARRIER SPECIFIED IN SECTION 2603.4 IS NOT |
| | REQUIRED UNDER THE CONDITIONS SET FORTH IN SECTIONS |
| | 2603.4.1.1 THROUGH 2603.4.1.13 . |
| | 2603.4.1.2 COOLER AND FREEZER WALLS. |
| | FOAM PLASTIC INSTALLED IN A MAXIMUM THICKNESS OF 10 |
| | INCHES (254 MM) IN COOLER AND FREEZER WALLS SHALL: 1. |
| | HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE |
| | TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS. |
| | 2. HAVE FLASH IGNITION AND SELF-IGNITION TEMPERATURES |
| | OF NOT LESS THAN 600?F AND 800?F (316?C AND 427?C), |
| | RESPECTIVELY. |
| | 3. HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8 MM) |
| | ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE |
| | METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT |
| | ANY POINT. |
| | 4. BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. WHERE |
| | THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH THE |
| | COOLER OR FREEZER AND THAT PART OF THE BUILDING IN |
| | WHICH IT IS LOCATED SHALL BE SPRINKLERED. |
| | WALK IN COOLERS |
| | 2603.4.1.3 WALK -IN COOLERS . |
| | IN NONSPRINKLERED BUILDINGS, FOAM PLASTIC HAVING A |
| | THICKNESS THAT DOES NOT EXCEED 4 INCHES (102 MM) AND A |
| | MAXIMUM FLAME SPREAD INDEX OF 75 IS PERMITTED IN WALK |
| | -IN COOLERS OR FREEZER UNITS WHERE THE AGGREGATE FLOOR |
| | AREA DOES NOT EXCEED 400 SQUARE FEET (37 M 2 ) AND THE |
| | FOAM PLASTIC IS COVERED BY A METAL FACING NOT LESS THAN |
| | 0.032-INCH-THICK (0.81 MM) ALUMINUM OR |
| | CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL |
| | THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO |
| | 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A |
| | THERMAL BARRIER. |
| | SHOW HOW WALK-IN COOLER COMPLIES. PROVIDE |
| | MANUFACTURER'S SPECIFICATIONS AND DETAILS. |
| | |
| | 20) SUBMIT SITE PLANS SHOWING ACCESSIBLE PARKING, |
| | ACCESSIBLE ROUTE TO THE BUILDING ENTRANCE, RAMPS, CURB |
| | CUTS, ETC. AS REQUIRED BY FBC 11-4.1.3. |
| | |
| | 21) ALL DOORS ON THE ACCESSIBLE ROUTES ARE REQUIRED TO |
| | HAVE ADA COMPLIANT HARDWARE. SEE FBC 11-4.13.9. |
| | |
| | 22) SHOW THE REQUIRED CLEAR FLOOR SPACE AT THE WATER |
| | CLOSET AND LAVATORY SPECIFY DIMENSIONS. SEE FBC |
| | 11-4.16.2 AND 11-4.19.3. |
| | |
| | 23) PROVIDE AN ACCESSIBLE COUNTER AS REQUIRED BY FBC |
| | 11-7.2. |
| | |
| | 24) DOORS 03 AND 04 DO NOT HAVE THE MANEUVERING |
| | CLEARANCES REQUIRED BY FBC 11-4.13.6. A MINIMUM OF 18" |
| | IS REQUIRED ON THE PULL SIDE AT THE LATCH OF SIDE SWING |
| | DOORS. |
| | |
| | 25) FBC 11-4.16.3 REQUIRES THE HEIGHT OF WATER CLOSETS |
| | TO BE 17" TO 19" MEASURED TO TOP OF THE TOILET SEAT. |
| | PLEASE CORRECT DETAIL 5 ON A-4. |
| | |
| | 26) FBC 11-4.16.4 REQUIRES THE GRAB BAR BEHIND THE |
| | WATER CLOSET TO BE 36" MINIMUM. |
| | |
| | 27) A SEPARATE PERMIT WILL BE REQUIRED FOR THE STAND |
| | ALONE CANOPY AT GAS PUMPS. |
| | |
| | 28) ADDITIONAL COMMENTS MAY RESULT WHEN THESE COMMENTS |
| | ARE ADDRESSED, DUE TO THE AMOUNT OF MISSING |
| | INFORMATION. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |