Plan Review Notes
Plan Review Notes For Permit 06101156
Permit Number 06101156
Review Stop B
Sequence Number 1
Notes
Date Text
2006-11-15 13:43:43DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT MUST
 BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE CODE THAT IS CURRENTLY IN EFFECT IS THE 2004
 FLORIDA BUILDING CODE. PLEASE CORRECT GENERAL NOTE #1
 ON SHEET A-1.
  
 4) SPECIFY THE CONSTRUCTION TYPE BASED ON THE 2004 FBC
 DESIGNATIONS. SPECIFY A OR B. SEE FBC TABLE 601.
  
 5) SPECIFY THE OCCUPANCY TYPE. SEE FBC 302.1.
  
 6) PROVIDE SURVEY/SITE PLANS INDICATING THE LOCATION OF
 THE STRUCTURE, DISTANCE TO PROPERTY LINES, DISTANCES TO
 OTHER STRUCTURES ON THE PROPERTY FOR DETERMINING FIRE
 SEPARATION DISTANCES. SEE FBC 702, 704.8 AND TABLE 602.
  
 7) PLEASE CLARIFY THE SCOPE OF WORK. THE APPLICATION
 INDICATES THAT THIS IS A REMODEL OF AN EXISTING
 BUILDING AND THE PLANS APPEAR TO BE FOR NEW
 CONSTRUCTION.
  
 8) IF THIS IS A REMODEL, SUBMIT A DEMO PLAN FOR THE
 EXISTING STRUCTURE.
  
 9) IF REMODEL, SPECIFY THE LEVEL OF ALTERATION FOR THE
 WORK AS SPECIFIED IN THE 2004 FBC EXISTING BUILDING
 CODE.
  
 10) SUBMIT ENERGY CALCULATIONS FOR THE STRUCTURE AS
 REQUIRED BY FBC 13-4.
  
 11) SPECIFY THE DESIGN DATA FOR THE STRUCTURE REQUIRED
 BY FBC 1603.1.4.
  
 12) SUBMIT PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS,
 DOORS, STOREFRONTS, MULLIONS, ROOFING MATERIAL, IMPACT
 PROTECTION PRODUCTS, ETC.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 13) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 14) SPECIFY HOW IMPACT PROTECTION OF OPENINGS WILL BE
 PROVIDED AS REQUIRED BY FBC 1609.1.4.
  
 15) SUBMIT TRUSS DRAWINGS AND LAYOUT SIGNED, SEALED AND
 DATED BY THE TRUSS ENGINEER AND REVIEWED AND APPROVED
 BY THE DESIGNER OF RECORD OF THE STRUCTURE. FBC
 106.3.5* CITY AMENDMENTS. NOTE: THE UPLIFT AT HIP
 GIRDER TRUSSES MAY EXCEED 1500#.
  
 16) INDICATE WHERE ON THE FOUNDATION PLAN THE STEEL
 COLUMN IN DETAIL 2 ON A-3 IS LOCATED.
  
 17) SPECIFY THE LOCATION AND SIZE OF THE ATTIC ACCESS
 REQUIRED BY FBC 1209.2.
  
 18) WALL SECTION 1 ON A-4 SPECIFIES ASPHALT ROOF
 SHINGLES AND THE ELEVATIONS SHOW A METAL ROOF. PLEASE
 CORRECT.
  
 19) 2603.4 THERMAL BARRIER.
 EXCEPT AS PROVIDED FOR IN SECTIONS 2603.4.1 AND 2603.8
 , FOAM PLASTIC SHALL BE SEPARATED FROM THE INTERIOR OF
 A BUILDING BY AN APPROVED THERMAL BARRIER OF 0.5-INCH
 (12.7 MM) GYPSUM WALLBOARD OR EQUIVALENT THERMAL
 BARRIER MATERIAL THAT WILL LIMIT THE AVERAGE
 TEMPERATURE RISE OF THE UNEXPOSED SURFACE TO NOT MORE
 THAN 250?F (120?C) AFTER 15 MINUTES OF FIRE EXPOSURE,
 COMPLYING WITH THE STANDARD TIME-TEMPERATURE CURVE OF
 ASTM E 119. THE THERMAL BARRIER SHALL BE INSTALLED IN
 SUCH A MANNER THAT IT WILL REMAIN IN PLACE FOR 15
 MINUTES BASED ON FM 4880, UL 1040, NFPA 286 OR UL 1715.
 COMBUSTIBLE CONCEALED SPACES SHALL COMPLY WITH SECTION
 717 .
 2603.4.1 THERMAL BARRIER NOT REQUIRED.
 THE THERMAL BARRIER SPECIFIED IN SECTION 2603.4 IS NOT
 REQUIRED UNDER THE CONDITIONS SET FORTH IN SECTIONS
 2603.4.1.1 THROUGH 2603.4.1.13 .
 2603.4.1.2 COOLER AND FREEZER WALLS.
 FOAM PLASTIC INSTALLED IN A MAXIMUM THICKNESS OF 10
 INCHES (254 MM) IN COOLER AND FREEZER WALLS SHALL: 1.
 HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE
 TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS.
 2. HAVE FLASH IGNITION AND SELF-IGNITION TEMPERATURES
 OF NOT LESS THAN 600?F AND 800?F (316?C AND 427?C),
 RESPECTIVELY.
 3. HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8 MM)
 ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT
 ANY POINT.
 4. BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. WHERE
 THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH THE
 COOLER OR FREEZER AND THAT PART OF THE BUILDING IN
 WHICH IT IS LOCATED SHALL BE SPRINKLERED.
 WALK IN COOLERS
 2603.4.1.3 WALK -IN COOLERS .
 IN NONSPRINKLERED BUILDINGS, FOAM PLASTIC HAVING A
 THICKNESS THAT DOES NOT EXCEED 4 INCHES (102 MM) AND A
 MAXIMUM FLAME SPREAD INDEX OF 75 IS PERMITTED IN WALK
 -IN COOLERS OR FREEZER UNITS WHERE THE AGGREGATE FLOOR
 AREA DOES NOT EXCEED 400 SQUARE FEET (37 M 2 ) AND THE
 FOAM PLASTIC IS COVERED BY A METAL FACING NOT LESS THAN
 0.032-INCH-THICK (0.81 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL
 THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO
 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A
 THERMAL BARRIER.
 SHOW HOW WALK-IN COOLER COMPLIES. PROVIDE
 MANUFACTURER'S SPECIFICATIONS AND DETAILS.
  
 20) SUBMIT SITE PLANS SHOWING ACCESSIBLE PARKING,
 ACCESSIBLE ROUTE TO THE BUILDING ENTRANCE, RAMPS, CURB
 CUTS, ETC. AS REQUIRED BY FBC 11-4.1.3.
  
 21) ALL DOORS ON THE ACCESSIBLE ROUTES ARE REQUIRED TO
 HAVE ADA COMPLIANT HARDWARE. SEE FBC 11-4.13.9.
  
 22) SHOW THE REQUIRED CLEAR FLOOR SPACE AT THE WATER
 CLOSET AND LAVATORY SPECIFY DIMENSIONS. SEE FBC
 11-4.16.2 AND 11-4.19.3.
  
 23) PROVIDE AN ACCESSIBLE COUNTER AS REQUIRED BY FBC
 11-7.2.
  
 24) DOORS 03 AND 04 DO NOT HAVE THE MANEUVERING
 CLEARANCES REQUIRED BY FBC 11-4.13.6. A MINIMUM OF 18"
 IS REQUIRED ON THE PULL SIDE AT THE LATCH OF SIDE SWING
 DOORS.
  
 25) FBC 11-4.16.3 REQUIRES THE HEIGHT OF WATER CLOSETS
 TO BE 17" TO 19" MEASURED TO TOP OF THE TOILET SEAT.
 PLEASE CORRECT DETAIL 5 ON A-4.
  
 26) FBC 11-4.16.4 REQUIRES THE GRAB BAR BEHIND THE
 WATER CLOSET TO BE 36" MINIMUM.
  
 27) A SEPARATE PERMIT WILL BE REQUIRED FOR THE STAND
 ALONE CANOPY AT GAS PUMPS.
  
 28) ADDITIONAL COMMENTS MAY RESULT WHEN THESE COMMENTS
 ARE ADDRESSED, DUE TO THE AMOUNT OF MISSING
 INFORMATION.
  