| 2006-11-28 09:09:37 | UNSAT |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| | REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL |
| | A GEN/RES PERMIT APPLICATION HAS BEEN |
| | APPROVED BY ZONING FOR |
| | THE GENERATOR LOCATION. |
| | NOTE: PLEASE BE AWARE THAT IF GENERATOR LOCATION |
| | CHANGES BECAUSE OF ZONING ISSUES THE GAS DRAWING MUST |
| | CORRELATE WITH THESE CHANGES. |
| | |
| | 2. PLEASE PROVIDE MANUFACTURER INSTALLATION |
| | INSTRUCTIONS OF GENERATOR REGAURDING CLEARENCES TO |
| | STRUCTURES. |
| | |
| | 3. PLEASE PROVIDE A CURRENT SURVEY (2 COPIES) WITH |
| | DIMENSIONS OF PROPOSED GENERATOR TO STRUCTURES AND |
| | PROPERTY LINES. |
| | |
| | 4. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL) ON |
| | THE GAS ISOMETRIC DRAWINGS. |
| | |
| | 5. PLEASE BE AWARE THAT IF THE GAS SYSTEM IS NATURAL |
| | GAS FOR THE PROPOSED GENERATOR THAT THE BTU LOAD |
| | INDICATED ON THE GAS ISOMETRIC DRAWING IS WRONG, IT |
| | SHOULD BE 723,000 NOT 698,000 PER THE SUBMITTED |
| | MANUFACTURER SPECIFICATIONS. PLEASE CORRECT FOR THE |
| | RESUBMITTAL. |
| | |
| | 6. NOTE: PLEASE BE AWARE THAT A GAS PERMIT IS REQUIRED |
| | FOR THE PROPOSED GENERATOR AND THAT THERE WAS NOT A GAS |
| | CONTRACTOR SIGNED ON THE GEN/RES PERMIT APPLICATION |
| | EVEN THOUGH THERE WAS A GAS ISOMETRIC DRAWING |
| | SUBMITTED. PLEASE CLARIFY THIS ON THE RESUBMITTAL. |
| | |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |
| | |
| | |
| | |
| | |